Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 75 kW |
| Standby kVA | 94 |
| Prime power | 70 kW |
| Emissions | Tier 3 |
| Controller | Digital generator controller |
| Voltage options | 120/240 V, 120/208 V, 277/480 V, 347/600 V |
| Phase | 1 or 3 |
| Battery group | 4D |
| Battery voltage | 12 V |
| Dimensions (L×W×H) | 1940×774×1397 mm |
| Wet weight | 1225 kg |
| Fuel tank | 400.0 L |
Engine
| Displacement | 4.4 L |
|---|---|
| Aspiration | Turbocharged, charge air cooled |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the JCB 4.4L Tier 3 Emergency Standby| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Oil | 500 hour oil change interval | — | 500 hr |
Service intervals
2| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Engine oil | Change | 500 hr | 500 hour oil change interval | |
| oil | Change | 500 hr |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
How many kW is the Westquip WQ75T3?
The Westquip WQ75T3 is rated 75 kW standby (94.0 kVA).
What engine is in the Westquip WQ75T3?
The Westquip WQ75T3 is powered by the JCB 4.4L Tier 3 Emergency Standby engine.
What kind of fuel does the Westquip WQ75T3 run on?
The Westquip WQ75T3 runs on Diesel.
What is the continuous rating of the Westquip WQ75T3?
The Westquip WQ75T3 is rated 70 kW prime (88 kVA), against 75 kW standby.
What size fuel tank does the Westquip WQ75T3 have?
The Westquip WQ75T3 has a 400 liter (106 US gallon) fuel tank.
What voltages is the Westquip WQ75T3 available in?
The Westquip WQ75T3 is offered in 120/240 V, 120/208 V, 277/480 V, 347/600 V, 1 or 3-phase.
Available documents
This page was generated from the 2 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.