Stadco CD40T4 Generator Set

The Stadco CD40T4 is a 40 kW standby generator set powered by a Deutz TD2011L04o engine. It holds about 14.3 L (3.8 gal) of oil.

40 kW
Standby
14.3 L
Oil capacity
0
Document types

Specifications

Standby power40 kW
Controller1790 Digital
Oil capacity14.3 L
AlternatorStadco P0-1-MAN

Engine

Deutz TD2011L04o
Oil capacity14.3 L
Rated speed1800 rpm

Common questions

What is the power rating of the Stadco CD40T4?

The Stadco CD40T4 is rated 40 kW standby.

What engine is in the Stadco CD40T4?

The Stadco CD40T4 is powered by the Deutz TD2011L04o engine.

How much oil does the Stadco CD40T4 take?

The Deutz TD2011L04o engine in the Stadco CD40T4 has an oil capacity of 14.3 liters.

What alternator comes on the Stadco CD40T4?

The Stadco CD40T4 uses a Stadco P0-1-MAN alternator.

Troubleshooting

7

Symptoms & remedies

SymptomCauseRemedy
Engine starts but the crank output does not turn offThe controller is not receiving a speed signal.1. Verify the Sensors -> Engine Speed -> Signal Source setting is set correctly. 2. Verify the Timers -> Engine Logic -> RPM Disconnect setting is set correctly. 3. Ensure the correct wiring to the controller. For magnetic pickup, Speed Sensing A and B terminals are used. For generator voltage, the AC voltage connections are used.
Sender always displayed its lowest or highest valueThe sender could either be open (not connected) or shorted to ground.Verify your connections and ensure the correct sender table is loaded.
No voltage build-up when starting set1. Check speed 2. Check residual voltage. 3. Follow separate excitation test procedure to check generator
Unstable voltage (either on no-load or with load)1. Check speed stability 2. Check stability setting
High voltage (either on no-load or with load)1. Check speed. 2. Check that generator load is not capacitive (leading power factor).
Low voltage (no-load)1. Check speed. 2. Check link 1-2 or external hand trimmer leads for continuity.
Low voltage (on-load)1. Check speed. 2. Check UFRO setting. 3. Follow separate excitation procedure to check generator and AVR.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.