Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 155 kW |
| Prime power | 139 kW |
| Emissions | EPA Tier 3 |
| Oil capacity | 23.0 L |
| Alternator | Stamford/AvK UCI274 (4-pole, Class H insulation) |
| Voltage options | 120/240 V, 120/208 V, 277/480 V, 347/600 V |
| Phase | 3 |
| Rated current | 234 A |
| Power factor | 0.8 |
| Battery group | 4D |
| Battery cranking | 1000 CCA |
| Battery voltage | 12 V |
| Coolant capacity | 23.1 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 2616×990×1397 mm |
| Dry weight | 1625 kg |
Engine
| Oil capacity | 23.0 L |
|---|---|
| Coolant capacity | 23.1 L |
| Displacement | 7.15 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Same engine, other brands
1 brandThe Volvo Penta TAD751GE in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Volvo Penta | TAD751GE |
Maintenance & consumables
for the Volvo Penta TAD751GE| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Double stage with cyclone; heavy duty replaceable element | — | |||
| Fuel filter | Fuel filter 0.005mm, Prefilter 0.010mm | — | |||
| Coolant | 23.1 L | — | |||
| Oil | VDS3/VDS2 | 23.0 L | — |
Common questions
How many kW is the Simson-Maxwell SVW140 T6-T3?
The Simson-Maxwell SVW140 T6-T3 is rated 155 kW standby.
What engine is in the Simson-Maxwell SVW140 T6-T3?
The Simson-Maxwell SVW140 T6-T3 is powered by the Volvo Penta TAD751GE engine.
What fuel does the Simson-Maxwell SVW140 T6-T3 use?
The Simson-Maxwell SVW140 T6-T3 runs on Diesel.
What's the oil capacity on a Simson-Maxwell SVW140 T6-T3?
The Volvo Penta TAD751GE engine in the Simson-Maxwell SVW140 T6-T3 has an oil capacity of 23.0 liters.
What is the cooling system capacity of the Simson-Maxwell SVW140 T6-T3?
The Simson-Maxwell SVW140 T6-T3 cooling system holds 23.1 liters (6.1 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Simson-Maxwell SVW140 T6-T3?
The Simson-Maxwell SVW140 T6-T3 is rated 139 kW prime, against 155 kW standby.
How much does the Simson-Maxwell SVW140 T6-T3 weigh?
The Simson-Maxwell SVW140 T6-T3 has a dry weight of 1625 kg (3583 lb).
What voltage does the Simson-Maxwell SVW140 T6-T3 produce?
The Simson-Maxwell SVW140 T6-T3 is offered in 120/240 V, 120/208 V, 277/480 V, 347/600 V, 3-phase.
What size battery does the Simson-Maxwell SVW140 T6-T3 need?
The Simson-Maxwell SVW140 T6-T3 uses 12 V each, 1000 CCA, group 4D, per the manufacturer specification sheet.
Which alternator is fitted to the Simson-Maxwell SVW140 T6-T3?
The Simson-Maxwell SVW140 T6-T3 uses a Stamford/AvK UCI274 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 15.2 | 4.02 |
| Prime | 50% | 24.8 | 6.55 |
| Prime | 75% | 33.7 | 8.9 |
| Prime | 100% | 39.7 | 10.49 |
| Standby | 25% | 17.0 | 4.49 |
| Standby | 50% | 28.0 | 7.4 |
| Standby | 75% | 38.1 | 10.06 |
| Standby | 100% | 45.8 | 12.1 |
Available documents
This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.