| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 2032 kW |
| Standby kVA | 3056 |
| Prime power | 1844 kW |
| Emissions | Tier-1 |
| Controller | Digital auto-start microprocessor based |
| Oil capacity | 200.0 L |
| Alternator | Stamford/AvK PI734 (4-pole, Class Class H insulation) |
| Voltage options | 120/240 V, 208/480 V, 600 V |
| Phase | 3 |
| Rated current | 353 A |
| Power factor | 0.8 |
| Circuit breaker | 3056 A |
| Battery group | 2X8D |
| Battery cranking | 1500 CCA |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 413 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 4800×2260×3429 mm |
| Dry weight | 12064 kg |
| Fuel tank | 12219.2 L |
| Tank runtime | 24 hr |
Engine
| Oil capacity | 250.0 L |
|---|---|
| Coolant capacity | 170.0 L |
| Displacement | 65.4 L |
| Aspiration | Turbocharged, Air-to-Air Charge Cooled |
| Rated speed | 1800 rpm |
Same engine, other brands
1 brandThe Mitsubishi S16R-Y1PTAA2-1 in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Kohler | 2000ROZM |
Common questions
What is the power rating of the Simson-Maxwell SMW2000 T6-T1?
The Simson-Maxwell SMW2000 T6-T1 is rated 2032 kW standby (3056.0 kVA).
Which engine powers the Simson-Maxwell SMW2000 T6-T1?
The Simson-Maxwell SMW2000 T6-T1 is powered by the Mitsubishi S16R-Y1PTAA2-1 engine.
What kind of fuel does the Simson-Maxwell SMW2000 T6-T1 run on?
The Simson-Maxwell SMW2000 T6-T1 runs on Diesel.
How much oil does the Simson-Maxwell SMW2000 T6-T1 take?
The Mitsubishi S16R-Y1PTAA2-1 engine in the Simson-Maxwell SMW2000 T6-T1 has an oil capacity of 250.0 liters.
What is the coolant capacity of the Simson-Maxwell SMW2000 T6-T1?
The Simson-Maxwell SMW2000 T6-T1 cooling system holds 413 liters (109.1 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Simson-Maxwell SMW2000 T6-T1?
The Simson-Maxwell SMW2000 T6-T1 is rated 1844 kW prime (2773 kVA), against 2032 kW standby.
What is the dry weight of the Simson-Maxwell SMW2000 T6-T1?
The Simson-Maxwell SMW2000 T6-T1 has a dry weight of 12064 kg (26596 lb).
How big is the fuel tank on the Simson-Maxwell SMW2000 T6-T1?
The Simson-Maxwell SMW2000 T6-T1 has a 12219.2 liter (3228 US gallon) fuel tank, giving about 24 hours of runtime.
What voltage does the Simson-Maxwell SMW2000 T6-T1 produce?
The Simson-Maxwell SMW2000 T6-T1 is offered in 120/240 V, 208/480 V, 600 V, 3-phase.
What battery does the Simson-Maxwell SMW2000 T6-T1 use?
The Simson-Maxwell SMW2000 T6-T1 uses 2 batteryies, 24 V each, 1500 CCA, group 2X8D, per the manufacturer specification sheet.
Which alternator is fitted to the Simson-Maxwell SMW2000 T6-T1?
The Simson-Maxwell SMW2000 T6-T1 uses a Stamford/AvK PI734 alternator. It has 4 poles. Insulation class Class H.
Parts
3| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 37411-04200 | Rear oil seal slinger | Seal | Amazon | |
| 37425-08201 | Front oil seal slinger | Seal | Amazon eBay | |
| 37594-01300 | ThreeBond 1211 liquid gasket | Gasket | Amazon eBay |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 242.3 | 67.3 | |
| Prime | 25% | 141.6 | 39.3 |
| Prime | 75% | 348.3 | 96.3 |
| Prime | 100% | 461.4 | 127.6 |
| Standby | 25% | 151.4 | 41.6 |
| Standby | 50% | 262.3 | 72.3 |
| Standby | 75% | 380.8 | 100.4 |
| Standby | 100% | 509.1 | 151.4 |
Available documents
This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.