Specifications
| Fuel | Natural Gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 625 kW |
| Standby kVA | 1041 |
| Prime power | 590 kW |
| Oil capacity | 174.0 L |
| Alternator | Stamford/AvK HCI634 (4-pole, Class H insulation) |
| Voltage options | 120/208 V, 277/480 V, 347/600 V |
| Phase | 3 |
| Rated current | 2169 A |
| Power factor | 0.8 |
| Circuit breaker | 2169 A |
| Battery group | 2X8D |
| Battery cranking | 1500 CCA |
| Battery voltage | 24 V |
| Battery quantity | 1 |
| Coolant capacity | 219 L |
| Dimensions (L×W×H) | 4064×1651×2540 mm |
| Dry weight | 18632 kg |
Engine
| Oil capacity | 174.0 L |
|---|---|
| Coolant capacity | 219.0 L |
| Displacement | 35.9 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the Simson-Maxwell SGWW625 T6?
The Simson-Maxwell SGWW625 T6 is rated 625 kW standby (1041.67 kVA).
What engine is in the Simson-Maxwell SGWW625 T6?
The Simson-Maxwell SGWW625 T6 is powered by the Waukesha L36GL engine.
What kind of fuel does the Simson-Maxwell SGWW625 T6 run on?
The Simson-Maxwell SGWW625 T6 runs on Natural Gas.
What's the oil capacity on a Simson-Maxwell SGWW625 T6?
The Waukesha L36GL engine in the Simson-Maxwell SGWW625 T6 has an oil capacity of 174.0 liters.
What is the coolant capacity of the Simson-Maxwell SGWW625 T6?
The Simson-Maxwell SGWW625 T6 cooling system holds 219 liters (57.9 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Simson-Maxwell SGWW625 T6?
The Simson-Maxwell SGWW625 T6 is rated 590 kW prime (983 kVA), against 625 kW standby.
What is the dry weight of the Simson-Maxwell SGWW625 T6?
The Simson-Maxwell SGWW625 T6 has a dry weight of 18632 kg (41076 lb).
What voltage does the Simson-Maxwell SGWW625 T6 produce?
The Simson-Maxwell SGWW625 T6 is offered in 120/208 V, 277/480 V, 347/600 V, 3-phase.
What size battery does the Simson-Maxwell SGWW625 T6 need?
The Simson-Maxwell SGWW625 T6 uses 1 battery, 24 V each, 1500 CCA, group 2X8D, per the manufacturer specification sheet.
What alternator comes on the Simson-Maxwell SGWW625 T6?
The Simson-Maxwell SGWW625 T6 uses a Stamford/AvK HCI634 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 0.2112 | 0.0559 |
| Prime | 50% | 0.4224 | 0.1118 |
| Prime | 75% | 0.6337 | 0.1675 |
| Prime | 100% | 0.8449 | 0.2236 |
| Standby | 25% | 0.2112 | 0.0559 |
| Standby | 50% | 0.4224 | 0.1118 |
| Standby | 75% | 0.6337 | 0.1675 |
| Standby | 100% | 0.8449 | 0.2236 |
Available documents
This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.