Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 127 kW |
| Standby kVA | 531 |
| Prime power | 121 kW |
| Emissions | Tier-4I |
| Controller | Digital auto-start microprocessor based control panel with remote start capability |
| Oil capacity | 20.0 L |
| Alternator | Stamford/AvK UCI274 (4-pole, Class H insulation) |
| Voltage options | 120/240 V, 120/208 V, 277/480 V, 347/600 V |
| Phase | 1 |
| Rated current | 531 A |
| Power factor | 0.8 |
| Circuit breaker | 502 A |
| Battery group | 4D |
| Battery cranking | 1000 CCA |
| Battery voltage | 12 V |
| Battery quantity | 1 |
| Coolant capacity | 34 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 2590×889×1447 mm |
| Dry weight | 1569 kg |
Engine
| Oil capacity | 20.0 L |
|---|---|
| Coolant capacity | 34.0 L |
| Displacement | 7.1 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Common questions
How many kW is the Simson-Maxwell SDW115 T6-T4?
The Simson-Maxwell SDW115 T6-T4 is rated 127 kW standby (531.0 kVA).
Which engine powers the Simson-Maxwell SDW115 T6-T4?
The Simson-Maxwell SDW115 T6-T4 is powered by the Deutz TCD2013L062VC engine.
What kind of fuel does the Simson-Maxwell SDW115 T6-T4 run on?
The Simson-Maxwell SDW115 T6-T4 runs on Diesel.
What's the oil capacity on a Simson-Maxwell SDW115 T6-T4?
The Deutz TCD2013L062VC engine in the Simson-Maxwell SDW115 T6-T4 has an oil capacity of 20.0 liters.
What is the cooling system capacity of the Simson-Maxwell SDW115 T6-T4?
The Simson-Maxwell SDW115 T6-T4 cooling system holds 34 liters (9.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Simson-Maxwell SDW115 T6-T4?
The Simson-Maxwell SDW115 T6-T4 is rated 121 kW prime (502 kVA), against 127 kW standby.
How much does the Simson-Maxwell SDW115 T6-T4 weigh?
The Simson-Maxwell SDW115 T6-T4 has a dry weight of 1569 kg (3460 lb).
What voltage does the Simson-Maxwell SDW115 T6-T4 produce?
The Simson-Maxwell SDW115 T6-T4 is offered in 120/240 V, 120/208 V, 277/480 V, 347/600 V, 1-phase.
What battery does the Simson-Maxwell SDW115 T6-T4 use?
The Simson-Maxwell SDW115 T6-T4 uses 1 battery, 12 V each, 1000 CCA, group 4D, per the manufacturer specification sheet.
What alternator does the Simson-Maxwell SDW115 T6-T4 use?
The Simson-Maxwell SDW115 T6-T4 uses a Stamford/AvK UCI274 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 23.6 | 6.23 | |
| Prime | 25% | 13.5 | 3.57 |
| Prime | 75% | 33.7 | 8.9 |
| Prime | 100% | 39.7 | 10.49 |
| Standby | 25% | 14.9 | 3.94 |
| Standby | 50% | 26.0 | 6.87 |
| Standby | 75% | 37.1 | 9.8 |
| Standby | 100% | 43.7 | 11.54 |
Available documents
This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.