Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 38 kW |
| Standby kVA | 160 |
| Prime power | 36 kW |
| Emissions | Tier-3 |
| Controller | Digital auto-start microprocessor based control panel with remote start capability |
| Oil capacity | 11.0 L |
| Alternator | Stamford/AvK UCI224 series |
| Voltage options | 120/240 V, 120/208 V, 277/480 V, 347/600 V |
| Phase | 1 |
| Rated current | 140 A |
| Power factor | 0.8 |
| Circuit breaker | 148 A |
| Battery group | 4D |
| Battery cranking | 1000 CCA |
| Battery voltage | 12 V |
| Battery quantity | 1 |
| Coolant capacity | NA L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 1676×736×939 mm |
| Dry weight | 684 kg |
Common questions
How many kW is the Simson-Maxwell SDAC40 T6-T3?
The Simson-Maxwell SDAC40 T6-T3 is rated 38 kW standby (160.0 kVA).
What engine does the Simson-Maxwell SDAC40 T6-T3 use?
The Simson-Maxwell SDAC40 T6-T3 is powered by the Deutz D914L04 engine.
What fuel does the Simson-Maxwell SDAC40 T6-T3 use?
The Simson-Maxwell SDAC40 T6-T3 runs on Diesel.
What's the oil capacity on a Simson-Maxwell SDAC40 T6-T3?
The Deutz D914L04 engine in the Simson-Maxwell SDAC40 T6-T3 has an oil capacity of 11.0 liters.
Which alternator is fitted to the Simson-Maxwell SDAC40 T6-T3?
The Simson-Maxwell SDAC40 T6-T3 uses a Stamford/AvK UCI224 series alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 4.2 | 1.11 |
| Prime | 50% | 6.5 | 1.72 |
| Prime | 75% | 9.3 | 2.46 |
| Prime | 100% | 12.3 | 3.25 |
| Standby | 25% | 4.6 | 1.22 |
| Standby | 50% | 7.2 | 1.9 |
| Standby | 75% | 10.2 | 2.69 |
| Standby | 100% | 13.5 | 3.57 |