Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 640 kW |
| Standby kVA | 800 |
| Prime power | 582 kW |
| Alternator | Leroy-Somer LSA491M7A |
| Voltage options | 415/240 V, 400/230 V, 380/220 V, 240/120 V, 230/115 V, 220/110 V |
| Phase | 3 |
| Power factor | 0.8 |
| Dimensions (L×W×H) | 3981×1630×1950 mm |
| Dry weight | 5216 kg |
Common questions
What is the power rating of the SDMO X800K?
The SDMO X800K is rated 640 kW standby (800.0 kVA).
What engine does the SDMO X800K use?
The SDMO X800K is powered by the MTU 12V2000G63E engine.
What fuel does the SDMO X800K use?
The SDMO X800K runs on Diesel.
What alternator does the SDMO X800K use?
The SDMO X800K uses a Leroy-Somer LSA491M7A alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 80.0 | 21.1 | |
| Prime | 75% | 119.0 | 31.4 |
| Prime | 100% | 161.0 | 42.5 |
| Standby | 110% | 175.0 | 46.2 |
Available documents
Spec sheet — X800K (SDMO)