Perkins 4012 Generator Set

The Perkins 4012 is a 1376 kW (1720 kVA) Diesel standby generator set. It operates at 50 Hz.

1376 kW
Standby
3
Document types

How to read your Perkins serial & model number →

Service parts for the 4012

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required
P4012-0001Air filtersee priceAmazon

Fuel system

1 required
P4012-0003Fuel filtersee priceAmazon

Oil system

1 required
P4012-0002Oil filtersee priceAmazon

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

FuelDiesel
Frequency50.0 Hz
Standby power1376 kW
Standby kVA1720
AlternatorBelt Driven

Maintenance & consumables

ItemSpecCapacityPart #Interval
Air filterAir Filter ElementP4012-0001 Amazon eBay
Fuel filterFuel FilterP4012-0003 Amazon eBay
Oil filterOil FilterP4012-0002 Amazon eBay

Common questions

What size generator is the Perkins 4012?

The Perkins 4012 is rated 1376 kW standby (1720.0 kVA).

What fuel does the Perkins 4012 use?

The Perkins 4012 runs on Diesel.

What alternator comes on the Perkins 4012?

The Perkins 4012 uses a Belt Driven alternator.

What oil filter fits the Perkins 4012?

The Perkins 4012 uses oil filter part number P4012-0002.

What fuel filter does the Perkins 4012 use?

The Perkins 4012 uses fuel filter part number P4012-0003.

Which air filter part number does the Perkins 4012 take?

The Perkins 4012 uses air filter part number P4012-0001.

Troubleshooting

1

Symptoms & remedies

SymptomCauseRemedy
Heavier than normal lubricating oil consumption, and oil leaks from the air and exhaust manifoldsTurbocharger oil seals are not fully effective on light load which results in oil being delivered together with the air into the engine air manifolds. The cylinder temperatures are too low to ensure complete burning of all the fuel delivered.Running on light load should be avoided or reduced to the minimum period. If weekly exercising on no load is carried out, the running period should be kept down to say, 10 minutes, or until the battery charging rate returns to normal. Periodically site load should be applied (min 25%) through the year. Every year the engine or generator set should be run for four hours, to burn off accumulations of carbon in the engine and exhaust system. This will require the use of a 'dummy load', which should be built up gradually from zero to the maximum over a four hour run. On standby sets, air cleaner elements should be changed annually. Lubricating oil and fuel filter elements should be changed every six months. The fuel pump injectors should be checked every 2 years.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

6
Part #DescriptionQtySystem
P4012-0001Air Filter Element1Air filter Amazon eBay
P4012-0002Oil Filter1Oil filter Amazon eBay
P4012-0003Fuel Filter1Fuel filter Amazon eBay
P4012-0004Spark Plug1Spark plug Amazon eBay
T6253/292Dismantling tool for centrifugal oil filter1Oil filter buy
T6253/293Extraction tool for centrifugal oil filter1Oil filter buy

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Spec sheet — PE1720SWD 50 TECH DATA REV.1 ENG (Perkins)Owner's manual — TSL4186F (Perkins)Owner's manual — TSL4186S (Perkins)Service manual — TSL4186E (Perkins)Service manual — notice-moteur-perkins-serie-4016-tsl4186f2-type-dga (Perkins)