Perkins 4008TAG1A Generator Set

The Perkins 4008TAG1A is a 797 kW (996 kVA) standby generator set powered by a Perkins 4008TAG1A engine. It is available at 415/240 V, 400/230 V and 380/220 V, 50 Hz. It holds about 180 L (47.6 gal) of oil and 166 L (43.9 gal) of coolant, with a maximum ambient rating of 50 °C. The set measures 2172×1944×3084 mm (85.5×76.5×121.4 in) and weighs about 7645 kg (16854 lb). An integrated tank holds 1830 L (483.4 gal). The same 4008TAG1A engine also powers generator sets from FG Wilson.

797 kW
Standby
30.6 L
Displacement
180.0 L
Oil capacity
3
Document types

How to read your Perkins serial & model number →

Specifications

Frequency50.0 Hz
Standby power797 kW
Standby kVA996
Prime power724 kW
Oil capacity180.0 L
AlternatorLl8224A P910P1
Voltage options415/240 V, 400/230 V, 380/220 V
Power factor0.8
Coolant capacity166.0 L
Max ambient50.0 °C
Dimensions (L×W×H)2172×1944×3084 mm
Dry weight7645 kg
Fuel tank1830.0 L

Engine

Perkins 4008TAG1A
Oil capacity180.0 L
Coolant capacity297.0 L
Displacement30.6 L
AspirationTurbocharged
Rated speed1500 rpm

Maintenance & consumables

for the Perkins 4008TAG1A
ItemSpecCapacityPart #Interval
Air filter find
Fuel filter find
Oil filter108126 hr find
Belt find
Coolant
Oil

Common questions

What is the power rating of the Perkins 4008TAG1A?

The Perkins 4008TAG1A is rated 797 kW standby (996.0 kVA).

What engine does the Perkins 4008TAG1A use?

The Perkins 4008TAG1A is powered by the Perkins 4008TAG1A engine.

What is the oil capacity of the Perkins 4008TAG1A?

The Perkins 4008TAG1A engine in the Perkins 4008TAG1A has an oil capacity of 180.0 liters.

What alternator does the Perkins 4008TAG1A use?

The Perkins 4008TAG1A uses a Ll8224A P910P1 alternator.

Fuel consumption

RatingLoadL/hgal/h
Prime60%
Standby50%

Available documents

Brochure — GenSet Power Selector Unregulated PN3012 (Perkins)Brochure — GenSet Selector Unregulated Iss2 PN1542 Jan10 (Perkins)Brochure — Perkins In China EP PN3014 (chi)-crosspage (Perkins)Engine spec — 4008TAG1-2A - 844-924kWm Emission Compliant Epak PN1833 (Perkins)Engine spec — 4008TAG1-2A - 844-947kWm ElectropaK PN1832 (Perkins)Engine spec — 4008TAG1A&2A 839-920 kWm ElectropaK (pn1833 75th) (Perkins)Engine spec — 4008TAG1A+2A+Epak+Emission+Compliant+844-924+kWm+PN1833 (Perkins)Engine spec — 4008tag1-2a - 839-920kwm emission comp electropak (pn1833 - mar06) (Perkins)Engine spec — 4008tag1-2a - 839-947kwm electropak (pn1832 - mar06) (Perkins)Spec sheet — GenSet Power Selector Chart Unregulated Territories (PN1542 75th) (Perkins)Spec sheet — GenSet Power Selector Chart Unregulated Territories(pn1542 - Oct06) (Perkins)Spec sheet — GenSet Selector Unregulated (PN1542 Feb09) (Perkins)Spec sheet — GenSet+Power+Selector+Unregulated+Model+Offering+PN1542 (Perkins)Spec sheet — GenSet+Selector+Unregulated+Model+Offering+PN1542 (Perkins)Spec sheet — Gen Set Power Selector (Perkins)Spec sheet — Gen Set Power Selector Chart (Perkins)Spec sheet — GeneratorEngineSelector (Perkins)