Home›MTU›MTU DS 3310 D5S

MTU DS 3310 D5S Generator Set

The MTU DS 3310 D5S is a generator set powered by a MTU 20V 4000 G63L engine. It is available at 400 V, 50 Hz. It holds about 390 L (103.0 gal) of oil and 205 L (54.2 gal) of coolant, with a maximum ambient rating of 40 °C. The set measures 6320×1840×2730 mm (248.8×72.4×107.5 in), weighs about 16583 kg (36559 lb) and produces 108 dBA at 1 m.

95.4 L
Displacement
390.0 L
Oil capacity
1
Document types

How to read your MTU serial & model number →

Specifications

Frequency50.0 Hz
Standby kVA3310
Oil capacity390.0 L
Alternator1030FDL7005
Voltage options400 V
Max ambient40 °C
Dimensions (L×W×H)6320×1840×2730 mm
Dry weight16583 kg
Sound level108.0 dBA @ 1 m

Engine

MTU 20V 4000 G63L
Oil capacity390.0 L
Coolant capacity205.0 L
Displacement95.4 L
AspirationExhaust turbocharging (ETC) with charge-air cooling (CAC)
Rated speed1500 rpm

Common questions

Which engine powers the MTU DS 3310 D5S?

The MTU DS 3310 D5S is powered by the MTU 20V 4000 G63L engine.

What is the oil capacity of the MTU DS 3310 D5S?

The MTU 20V 4000 G63L engine in the MTU DS 3310 D5S has an oil capacity of 390.0 liters.

How much coolant does the MTU DS 3310 D5S hold?

The MTU DS 3310 D5S cooling system holds 205 liters (54.2 US gallons) for the engine, per the manufacturer specification sheet.

What is the sound level of the MTU DS 3310 D5S?

The MTU DS 3310 D5S is rated at 108.0 dBA at 1 m, per the manufacturer specification sheet.

How much does the MTU DS 3310 D5S weigh?

The MTU DS 3310 D5S has a dry weight of 16583 kg (36559 lb).

What voltages is the MTU DS 3310 D5S available in?

The MTU DS 3310 D5S is offered in 400 V.

What alternator does the MTU DS 3310 D5S use?

The MTU DS 3310 D5S uses a 1030FDL7005 alternator.

Fuel consumption

RatingLoadL/hgal/h
Standby50%306.0210.0
Standby75%435.0192.0
Standby100%563.0193.0

Available documents

Spec sheet — 2870-3310 KVA (MTU)

This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Other sets with this engine