Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 275 kW |
| Standby kVA | 343 |
| Emissions | EPA Tier 3 |
| Oil capacity | 46.0 L |
| Voltage options | 208 V, 240 V, 380 V, 440 V, 480 V, 600 V |
| Phase | 3 |
| Power factor | 0.8 |
| Battery cranking | 950 CCA |
| Battery voltage | 24 V |
| Coolant capacity | 82 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3658×1883×1855 mm |
| Dry weight | 3134 kg |
| Sound level | 86.9 dBA @ 7 m |
Engine
| Oil capacity | 29.0 L |
|---|---|
| Coolant capacity | 45.0 L |
| Displacement | 10.5 L |
| Aspiration | Turbocharged, aftercooled |
| Rated speed | 1800 rpm |
Common questions
What size generator is the MTU 6R1600 DS275?
The MTU 6R1600 DS275 is rated 275 kW standby (343.0 kVA).
What engine is in the MTU 6R1600 DS275?
The MTU 6R1600 DS275 is powered by the MTU 6R 1600 G70S engine.
Is the MTU 6R1600 DS275 diesel or gas?
The MTU 6R1600 DS275 runs on Diesel.
What is the oil capacity of the MTU 6R1600 DS275?
The MTU 6R 1600 G70S engine in the MTU 6R1600 DS275 has an oil capacity of 29.0 liters.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 50% | 46.0 | 12.2 |
| Standby | 75% | 60.0 | 15.9 |
| Standby | 100% | 74.0 | 19.7 |