HomeMTUMTU 6R0225 DS400

MTU 6R0225 DS400 Generator Set

The MTU 6R0225 DS400 is a 400 kW (500 kVA) diesel standby generator set powered by a John Deere 6135HFG84 engine. It is available at 208 V, 240 V, 380 V, 480 V and 600 V, 3-phase, 60 Hz and rated 1388 A. It holds about 40 L (10.6 gal) of oil and 47.7 L (12.6 gal) of coolant, with a maximum ambient rating of 50 °C. Starting uses 2 group-31 batteries rated 950 CCA at 24 V. The set measures 3480×2045×2418 mm (137.0×80.5×95.2 in), weighs about 3464 kg (7637 lb) and produces 89.2 dBA at 7 m. The same 6135HFG84 engine also powers generator sets from AKSA and Kohler.

400 kW
Standby
13.5 L
Displacement
40.0 L
Oil capacity
2
Document types

How to read your MTU serial & model number →

Specifications

Fueldiesel
Frequency60.0 Hz
Standby power400 kW
Standby kVA500
Prime power365 kW
EmissionsEPA Tier 3
Oil capacity40.0 L
Alternator572RSL4025
Voltage options208 V, 240 V, 380 V, 480 V, 600 V
Phase3
Rated current1388 A
Power factor0.8
Battery group31
Battery cranking950 CCA
Battery voltage24 V
Battery quantity2
Coolant capacity47.7 L
Max ambient50 °C
Dimensions (L×W×H)3480×2045×2418 mm
Dry weight3464 kg
Sound level89.2 dBA @ 7 m

Engine

John Deere 6135HFG84
Oil capacity40.0 L
Coolant capacity18.0 L
Displacement13.5 L
AspirationTurbocharged, Charge Air-Cooled
Rated speed1800 rpm

Maintenance & consumables

for the John Deere 6135HFG84
ItemSpecCapacityPart #Interval
Fuel filterPrimaryGM80460 PartsGeek
Fuel filterSecondary find
Oil filterCartridge×1GM80434 Amazon eBay PartsGeek

Common questions

What is the power rating of the MTU 6R0225 DS400?

The MTU 6R0225 DS400 is rated 400 kW standby (500.0 kVA).

What engine does the MTU 6R0225 DS400 use?

The MTU 6R0225 DS400 is powered by the John Deere 6135HFG84 engine.

What fuel does the MTU 6R0225 DS400 use?

The MTU 6R0225 DS400 runs on diesel.

What is the oil capacity of the MTU 6R0225 DS400?

The John Deere 6135HFG84 engine in the MTU 6R0225 DS400 has an oil capacity of 40.0 liters.

What alternator does the MTU 6R0225 DS400 use?

The MTU 6R0225 DS400 uses a 572RSL4025 alternator.

Fuel consumption

RatingLoadL/hgal/h
Prime50%54.014.3
Prime75%77.920.6
Prime100%104.127.5
Standby50%63.017.0
Standby75%91.024.0
Standby100%110.029.0

Available documents

Brochure — 16120643 PowerGeneration Solutionguide 1 2020 (MTU)Spec sheet — 231118 PG Spec 6R0225DS400 400kW 3D T3 60Hz (MTU)Spec sheet — 231118 PG Spec 6R0225DS400 400kW 3D T3 SCAQMD 60Hz (MTU)Spec sheet — 231251 PG Spec 6R0225DS400 400kW 3D T4 SCAQMD 60Hz (MTU)Spec sheet — 231257 PG Spec 6R0225DS400 365kW 3B T4 SCAQMD 60Hz (MTU)Spec sheet — EngineersGuidebook (MTU)