Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 2240 kW |
| Standby kVA | 2630 |
| Prime power | 2200 kW |
| Controller | NEA (ORDE) optimized |
| Oil capacity | 390.0 L |
| Alternator | Leroy-Somer LSA52.3 UL16 (4-pole, Class H insulation) |
| Voltage options | 380 V, 400 V, 415 V |
| Phase | three-phase |
| Rated current | 4254 A |
| Power factor | 0.8 |
| Circuit breaker | 4254 A |
| Coolant capacity | 2590 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 5760×1887×2332 mm |
| Dry weight | 16919 kg |
Engine
| Oil capacity | 390.0 L |
|---|---|
| Coolant capacity | 205.0 L |
| Displacement | 95.4 L |
| Aspiration | Exhaust turbocharging (ETC) with charge-air cooling (CAC) |
| Rated speed | 1500 rpm |
Maintenance & consumables
for the MTU 20 V 4000 G23| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Dry | — | |||
| Fuel filter | — | ||||
| Oil filter | — | ||||
| Battery | — | ||||
| Belt | — | ||||
| Coolant | 205.0 l | — | |||
| Oil | 390.0 l | — | |||
| Spark plug | — |
Common questions
How many kW is the MTU 20V4000 DS2750?
The MTU 20V4000 DS2750 is rated 2240 kW standby (2630.0 kVA).
What engine does the MTU 20V4000 DS2750 use?
The MTU 20V4000 DS2750 is powered by the MTU 20 V 4000 G23 engine.
What kind of fuel does the MTU 20V4000 DS2750 run on?
The MTU 20V4000 DS2750 runs on Diesel.
What's the oil capacity on a MTU 20V4000 DS2750?
The MTU 20 V 4000 G23 engine in the MTU 20V4000 DS2750 has an oil capacity of 390.0 liters.
Which alternator is fitted to the MTU 20V4000 DS2750?
The MTU 20V4000 DS2750 uses a Leroy-Somer LSA52.3 UL16 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 320.25 | 84.6 |
| Prime | 75% | 457.0 | 120.5 |
| Standby | 50% | 293.0 | 81.0 |
| Standby | 75% | 419.9 | 116.0 |
| Standby | 100% | 554.0 | 150.0 |