HomeMTUMTU 20V 4000 DS4000

MTU 20V 4000 DS4000 Generator Set

The MTU 20V 4000 DS4000 is a 3160 kW (3630 kVA) diesel standby generator set powered by a MTU 20V4000G44LF engine. It is available at 11 V, three-phase-phase, 50 Hz and rated 191 A. It holds about 390 L (103.0 gal) of oil and 260 L (68.7 gal) of coolant, with a maximum ambient rating of 40 °C. The set measures 6339×1887×2415 mm (249.6×74.3×95.1 in), weighs about 19350 kg (42659 lb) and produces 10 dBA at 1 m.

3160 kW
Standby
95.4 L
Displacement
390.0 L
Oil capacity
3
Document types

How to read your MTU serial & model number →

Specifications

Fueldiesel
Frequency50.0 Hz
Standby power3160 kW
Standby kVA3630
Prime power2904 kW
EmissionsFuel consumption optimized
ControllerBasler, Deif
Oil capacity390.0 L
AlternatorLeroy-Somer LSA54.2 ZL12
Voltage options11 V
Phase3
Rated current191 A
Power factor0.8
Battery voltage24 V
Coolant capacity260 L
Max ambient40 °C
Dimensions (L×W×H)6339×1887×2415 mm
Dry weight19350 kg
Sound level10.0 dBA @ 1 m

Engine

MTU 20V4000G44LF
Oil capacity390.0 L
Coolant capacity260.0 L
Displacement95.4 L
Aspirationwater charge air cooling
Rated speed1500 rpm

Common questions

What is the power rating of the MTU 20V 4000 DS4000?

The MTU 20V 4000 DS4000 is rated 3160 kW standby (3630.0 kVA).

What engine does the MTU 20V 4000 DS4000 use?

The MTU 20V 4000 DS4000 is powered by the MTU 20V4000G44LF engine.

What fuel does the MTU 20V 4000 DS4000 use?

The MTU 20V 4000 DS4000 runs on diesel.

What is the oil capacity of the MTU 20V 4000 DS4000?

The MTU 20V4000G44LF engine in the MTU 20V 4000 DS4000 has an oil capacity of 390.0 liters.

What alternator does the MTU 20V 4000 DS4000 use?

The MTU 20V 4000 DS4000 uses a Leroy-Somer LSA54.2 ZL12 alternator.

Fuel consumption

RatingLoadL/hgal/h
50%403.0
75%565.0
100%806.0
Prime
Prime50%368.0
Prime75%517.0
Prime100%711.0
Standby
Standby50%429.0
Standby75%598.0
Standby100%818.0

Available documents

Brochure — 16120643 PowerGeneration Solutionguide 1 2020 (MTU)Brochure — PG UseCase HVO Datacenter (MTU)Spec sheet — 16120827 PG spec 20V4000DS4000 3630kVA 3F FC 50Hz (MTU)Spec sheet — 16120831 PG spec 20V4000DS4000 3630kVA 3F NEA 50Hz (MTU)Spec sheet — 16120969 PG spec 20V4000DS4000 3630kVA 3B FC 50Hz (MTU)Spec sheet — 16121005 PG spec 20V4000DS4000 3630kVA 3B NEA T2 50Hz (MTU)Spec sheet — 32310771 PG spec 20V4000DS4000 4000kVA 3D NEA 50Hz (MTU)Spec sheet — 32310781 PG spec 20V4000DS4000 4000kVA 3D FC 50Hz (MTU)Spec sheet — 32311371 PG spec 20V4000DS4000 3630kVA 3E FC 50Hz (MTU)Spec sheet — 32311381 PG spec 20V4000DS4000 3630kVA 3E NEA 50Hz (MTU)Spec sheet — 4000-Оптимизация-расхода-топлива (MTU)Reference — Application Variation V002 Descision Document - 20052025 (MTU)