Home›MTU›MTU 18V 2000 B26F

MTU 18V 2000 B26F Generator Set

The MTU 18V 2000 B26F is a 887 kW (1010 kVA) Diesel standby generator set powered by a MTU 18V2000B26F engine. It is available at 380 V, 400 V and 415 V, 3-phase, 50 Hz and rated 1535 A. It holds about 110 L (29.1 gal) of oil and 73 L (19.3 gal) of coolant, with a maximum ambient rating of not specified °C. Starting uses not specified group-not specified battery at not specified V. The set measures 4720×1990×2200 mm (185.8×78.3×86.6 in), weighs about 7850 kg (17306 lb) and produces not specified dBA at not specified m. An integrated tank holds not specified L (None gal), roughly not specified hours of runtime.

887 kW
Standby
40.2 L
Displacement
110.0 L
Oil capacity
2
Document types

How to read your MTU serial & model number →

Specifications

FuelDiesel
Frequency50.0 Hz
Standby power887 kW
Standby kVA1010
Prime power887 kW
EmissionsEPA Tier 2
ControllerBasler controller, Deif controller
Oil capacity110.0 L
AlternatorLeroy-Somer SA 50.2 L7
Voltage options380 V, 400 V, 415 V
Phasethree-phase
Rated current1535 A
Power factor0.8
Circuit breaker1535 A
Battery groupnot specified
Battery voltagenot specified V
Battery quantitynot specified
Coolant capacity73 L
Max ambientnot specified °C
Dimensions (L×W×H)4720×1990×2200 mm
Dry weight7850 kg
Tank runtimenot specified hr

Engine

MTU 18V2000B26F
Oil capacity110.0 L
Coolant capacity73.0 L
Displacement40.2 L
Aspiration4-cycle
Rated speed1500 rpm

Filters for the MTU 18V2000B26F

1

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:

SystemFilterDescriptionCross-references
Fuel / water separatorP502404Fuel Filter, Water Separator Spin-OnMTU 0020920601, MTU 20920601, BALDWIN BF7987, SDMO 330510032 KuduParts $18.00 FridayParts $20.68

Common questions

What size generator is the MTU 18V 2000 B26F?

The MTU 18V 2000 B26F is rated 887 kW standby (1010.0 kVA).

What engine does the MTU 18V 2000 B26F use?

The MTU 18V 2000 B26F is powered by the MTU 18V2000B26F engine.

Is the MTU 18V 2000 B26F diesel or gas?

The MTU 18V 2000 B26F runs on Diesel.

What's the oil capacity on a MTU 18V 2000 B26F?

The MTU 18V2000B26F engine in the MTU 18V 2000 B26F has an oil capacity of 110.0 liters.

What is the cooling system capacity of the MTU 18V 2000 B26F?

The MTU 18V 2000 B26F cooling system holds 73 liters (19.3 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the dry weight of the MTU 18V 2000 B26F?

The MTU 18V 2000 B26F has a dry weight of 7850 kg (17306 lb).

What voltage does the MTU 18V 2000 B26F produce?

The MTU 18V 2000 B26F is offered in 380 V, 400 V, 415 V, three-phase-phase.

What battery does the MTU 18V 2000 B26F use?

The MTU 18V 2000 B26F uses not specified batteryies, not specified V each, group not specified, per the manufacturer specification sheet.

What alternator comes on the MTU 18V 2000 B26F?

The MTU 18V 2000 B26F uses a Leroy-Somer SA 50.2 L7 alternator.

Fuel consumption

RatingLoadL/hgal/h
Standby50%111.0207.0
Standby75%155.0194.0
Standby100%203.0190.0

Available documents

Engine spec — 32310301 MTU Gendrive spec 12V16V18V2000Gx06 3A 3B 3G A2A (MTU)Reference — 3239651 PG spec 18V2000DS1400 1010kVA 3A FC 50Hz (MTU)Reference — MTU REACH SVHC 2021-03-17-EN final (MTU)Reference — MTU REACH SVHC 2025-09-19-EN final (MTU)

This page was generated from the 4 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Other sets with this engine