Specifications
| Fuel | diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 2024 kW |
| Standby kVA | 2530 |
| Prime power | 1912 kW |
| Emissions | NEA (ORDE) optimized |
| Controller | Basler controller |
| Oil capacity | 85.0 L |
| Alternator | Leroy-Somer LSA52.3 L12 |
| Voltage options | 380 V, 400 V, 415 V, 11 V |
| Phase | three-phase |
| Rated current | 3844 A |
| Power factor | 0.8 |
| Circuit breaker | 3965 A |
| Battery voltage | 24 V |
| Battery quantity | 1 |
| Coolant capacity | 175 L |
| Dimensions (L×W×H) | 4766×1810×2330 mm |
| Dry weight | 13395 kg |
Engine
| Oil capacity | 300.0 L |
|---|---|
| Coolant capacity | 175.0 L |
| Displacement | 76.3 L |
| Aspiration | water charge air cooling |
| Rated speed | 1500 rpm |
Filters for the MTU 16V4000G84F
1Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Fuel / water separator | P552006 | Fuel Filter, Water Separator Spin-On Twist&Drain | MTU 4202934, NAPA 3645, BALDWIN BF1262, SISU 1273400331 | FridayParts $42.88 |
Common questions
How many kW is the MTU 16V4000G84F?
The MTU 16V4000G84F is rated 2024 kW standby (2530.0 kVA).
Which engine powers the MTU 16V4000G84F?
The MTU 16V4000G84F is powered by the MTU 16V4000G84F engine.
What fuel does the MTU 16V4000G84F use?
The MTU 16V4000G84F runs on diesel.
How much oil does the MTU 16V4000G84F take?
The MTU 16V4000G84F engine in the MTU 16V4000G84F has an oil capacity of 300.0 liters.
What is the coolant capacity of the MTU 16V4000G84F?
The MTU 16V4000G84F cooling system holds 175 liters (46.2 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the MTU 16V4000G84F?
The MTU 16V4000G84F is rated 1912 kW prime (2390 kVA), against 2024 kW standby.
How much does the MTU 16V4000G84F weigh?
The MTU 16V4000G84F has a dry weight of 13395 kg (29530 lb).
What voltages is the MTU 16V4000G84F available in?
The MTU 16V4000G84F is offered in 380 V, 400 V, 415 V, 11 V, three-phase-phase.
How many cold cranking amps does the MTU 16V4000G84F require?
The MTU 16V4000G84F uses 1 battery, 24 V each, per the manufacturer specification sheet.
What alternator comes on the MTU 16V4000G84F?
The MTU 16V4000G84F uses a Leroy-Somer LSA52.3 L12 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 50% | 271.2 | 206.0 |
| Standby | 75% | 394.9 | 200.0 |
| Standby | 100% | 526.5 | 200.0 |
Available documents
This page was generated from the 3 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.