HomeMTUMTU 16V4000 DS2750

MTU 16V4000 DS2750 Generator Set

The MTU 16V4000 DS2750 is a 2240 kW (2800 kVA) diesel standby generator set powered by a MTU 16V4000G94F engine. It is available at 380 V, 400 V, 415 V and 11 V, 3-phase, 50 Hz and rated 4254 A. It holds about 300 L (79.3 gal) of oil and 175 L (46.2 gal) of coolant, with a maximum ambient rating of not specified °C. Starting uses not specified group-not specified battery at not specified V. The set measures 4880×1810×2350 mm (192.1×71.3×92.5 in), weighs about 14550 kg (32077 lb) and produces not specified dBA at not specified m. An integrated tank holds not specified L (None gal), roughly not specified hours of runtime.

2240 kW
Standby
76.3 L
Displacement
300.0 L
Oil capacity
2
Document types

How to read your MTU serial & model number →

Compare with other 2240–2245 kW Diesel generators →

Specifications

Fueldiesel
Frequency50.0 Hz
Standby power2240 kW
Standby kVA2800
Prime power2240 kW
EmissionsTier 2
ControllerBasler controller
Oil capacity300.0 L
AlternatorLeroy-Somer LSA52.3 UL16 (4-pole, Class H insulation)
Voltage options380 V, 400 V, 415 V, 11 V
Phasethree-phase
Rated current4254 A
Power factor0.8
Circuit breaker4254 A
Battery groupnot specified
Battery voltagenot specified V
Battery quantitynot specified
Coolant capacity175 L
Max ambientnot specified °C
Dimensions (L×W×H)4880×1810×2350 mm
Dry weight14550 kg
Tank runtimenot specified hr

Engine

MTU 16V4000G94F
Oil capacity300.0 L
Coolant capacity175.0 L
Displacement76.3 L
Aspirationwater charge air cooling
Rated speed1500 rpm

Common questions

How many kW is the MTU 16V4000 DS2750?

The MTU 16V4000 DS2750 is rated 2240 kW standby (2800.0 kVA).

What engine does the MTU 16V4000 DS2750 use?

The MTU 16V4000 DS2750 is powered by the MTU 16V4000G94F engine.

What kind of fuel does the MTU 16V4000 DS2750 run on?

The MTU 16V4000 DS2750 runs on diesel.

What is the oil capacity of the MTU 16V4000 DS2750?

The MTU 16V4000G94F engine in the MTU 16V4000 DS2750 has an oil capacity of 300.0 liters.

What alternator does the MTU 16V4000 DS2750 use?

The MTU 16V4000 DS2750 uses a Leroy-Somer LSA52.3 UL16 alternator. It has 4 poles. Insulation class H.

Fuel consumption

RatingLoadL/hgal/h
Prime50%254.0194.0
Prime75%371.0189.0
Prime100%508.0194.0
Standby50%192.050.72
Standby75%188.049.66
Standby100%197.052.04

Available documents

Spec sheet — 16120835 PG spec 16V4000DS2750 2600kVA 3F NEA 50Hz (MTU)Reference — 16120834 PG spec 16V4000DS2750 2600kVA 3F FC 50Hz (MTU)Reference — 16120968 PG spec 16V4000DS2750 2600kVA 3B FC 50Hz (MTU)Reference — 32311621 PG spec 16V4000DS2750 2870kVA 3D FC 50Hz (MTU)