Specifications
| Fuel | diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 2240 kW |
| Standby kVA | 2800 |
| Prime power | 2240 kW |
| Emissions | Tier 2 |
| Controller | Basler controller |
| Oil capacity | 300.0 L |
| Alternator | Leroy-Somer LSA52.3 UL16 (4-pole, Class H insulation) |
| Voltage options | 380 V, 400 V, 415 V, 11 V |
| Phase | three-phase |
| Rated current | 4254 A |
| Power factor | 0.8 |
| Circuit breaker | 4254 A |
| Battery group | not specified |
| Battery voltage | not specified V |
| Battery quantity | not specified |
| Coolant capacity | 175 L |
| Max ambient | not specified °C |
| Dimensions (L×W×H) | 4880×1810×2350 mm |
| Dry weight | 14550 kg |
| Tank runtime | not specified hr |
Engine
| Oil capacity | 300.0 L |
|---|---|
| Coolant capacity | 175.0 L |
| Displacement | 76.3 L |
| Aspiration | water charge air cooling |
| Rated speed | 1500 rpm |
Filters for the MTU 16V4000G94F
1Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Fuel / water separator | P552006 | Fuel Filter, Water Separator Spin-On Twist&Drain | MTU 4202934, NAPA 3645, BALDWIN BF1262, SISU 1273400331 | FridayParts $42.88 |
Common questions
How many kW is the MTU 16V4000 DS2750?
The MTU 16V4000 DS2750 is rated 2240 kW standby (2800.0 kVA).
What engine does the MTU 16V4000 DS2750 use?
The MTU 16V4000 DS2750 is powered by the MTU 16V4000G94F engine.
What kind of fuel does the MTU 16V4000 DS2750 run on?
The MTU 16V4000 DS2750 runs on diesel.
What is the oil capacity of the MTU 16V4000 DS2750?
The MTU 16V4000G94F engine in the MTU 16V4000 DS2750 has an oil capacity of 300.0 liters.
What is the coolant capacity of the MTU 16V4000 DS2750?
The MTU 16V4000 DS2750 cooling system holds 175 liters (46.2 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the dry weight of the MTU 16V4000 DS2750?
The MTU 16V4000 DS2750 has a dry weight of 14550 kg (32077 lb).
What voltages is the MTU 16V4000 DS2750 available in?
The MTU 16V4000 DS2750 is offered in 380 V, 400 V, 415 V, 11 V, three-phase-phase.
What size battery does the MTU 16V4000 DS2750 need?
The MTU 16V4000 DS2750 uses not specified batteryies, not specified V each, group not specified, per the manufacturer specification sheet.
What alternator does the MTU 16V4000 DS2750 use?
The MTU 16V4000 DS2750 uses a Leroy-Somer LSA52.3 UL16 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 254.0 | 194.0 |
| Prime | 75% | 371.0 | 189.0 |
| Prime | 100% | 508.0 | 194.0 |
| Standby | 50% | 192.0 | 50.72 |
| Standby | 75% | 188.0 | 49.66 |
| Standby | 100% | 197.0 | 52.04 |
Available documents
This page was generated from the 4 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.