Specifications
| Fuel | diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 1440 kW |
| Standby kVA | 1800 |
| Prime power | 1432 kW |
| Emissions | NEA (ORDE) optimized |
| Controller | Basler controller |
| Oil capacity | 260.0 L |
| Alternator | Leroy-Somer LSA52.3 S5 |
| Voltage options | 380 V, 400 V, 415 V, 11 V |
| Phase | three-phase |
| Rated current | 2735 A |
| Circuit breaker | 2856 A |
| Battery voltage | 24 V |
| Battery quantity | 1 |
| Coolant capacity | 160 L |
| Dimensions (L×W×H) | 4059×1810×2330 mm |
| Dry weight | 10654 kg |
Engine
| Oil capacity | 260.0 L |
|---|---|
| Coolant capacity | 160.0 L |
| Displacement | 57.2 L |
| Aspiration | water charge air cooling |
| Rated speed | 1500 rpm |
Filters for the MTU 12V4000G74F
1Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Fuel / water separator | P550849 | Fuel Filter, Water Separator Cartridge | NAPA 3763, BALDWIN PF7928, DAVCO 102526, DAVCO 102527 | FridayParts $20.90 KuduParts $39.00 |
Common questions
What size generator is the MTU 12V4000G74F?
The MTU 12V4000G74F is rated 1440 kW standby (1800.0 kVA).
What engine does the MTU 12V4000G74F use?
The MTU 12V4000G74F is powered by the MTU 12V4000G74F engine.
Is the MTU 12V4000G74F diesel or gas?
The MTU 12V4000G74F runs on diesel.
What's the oil capacity on a MTU 12V4000G74F?
The MTU 12V4000G74F engine in the MTU 12V4000G74F has an oil capacity of 260.0 liters.
What is the coolant capacity of the MTU 12V4000G74F?
The MTU 12V4000G74F cooling system holds 160 liters (42.3 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the MTU 12V4000G74F?
The MTU 12V4000G74F is rated 1432 kW prime (1790 kVA), against 1440 kW standby.
How much does the MTU 12V4000G74F weigh?
The MTU 12V4000G74F has a dry weight of 10654 kg (23488 lb).
What voltages is the MTU 12V4000G74F available in?
The MTU 12V4000G74F is offered in 380 V, 400 V, 415 V, 11 V, three-phase-phase.
What size battery does the MTU 12V4000G74F need?
The MTU 12V4000G74F uses 1 battery, 24 V each, per the manufacturer specification sheet.
What alternator does the MTU 12V4000G74F use?
The MTU 12V4000G74F uses a Leroy-Somer LSA52.3 S5 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 1376.0 | 363.5 |
| Prime | 75% | 1448.0 | 382.52 |
| Prime | 100% | 1448.0 | 382.52 |
| Standby | 50% | 200.2 | 53.0 |
| Standby | 75% | 288.9 | 76.0 |
| Standby | 100% | 377.6 | 100.0 |
Available documents
This page was generated from the 4 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.