Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 1350 kW |
| Standby kVA | 1686 |
| Prime power | 1350 kW |
| Emissions | EPA Tier 2 |
| Controller | Digital control panel(s) |
| Oil capacity | 260.0 L |
| Alternator | MTU 641-S55 (4-pole, Class F insulation) |
| Voltage options | 380 V, 416 V, 440 V, 480 V, 600 V, 160 V, 12 V, 470 V, 13 V, 200 V, 800 V |
| Phase | 3 |
| Rated current | 2564 A |
| Power factor | 0.8 |
| Circuit breaker | 2564 A |
| Battery group | 8D |
| Battery cranking | 2800 CCA |
| Battery voltage | 24 V |
| Battery quantity | 4 |
| Coolant capacity | 693 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 5851×2565×2934 mm |
| Dry weight | 16917 kg |
| Sound level | 90.9 dBA @ 7 m |
| Fuel tank | 362.0 L |
| Tank runtime | 96 hr |
Engine
| Oil capacity | 260.0 L |
|---|---|
| Coolant capacity | 160.0 L |
| Displacement | 57.2 L |
| Aspiration | natural |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the MTU 12V4000G15S?
The MTU 12V4000G15S is rated 1350 kW standby (1686.0 kVA).
What engine does the MTU 12V4000G15S use?
The MTU 12V4000G15S is powered by the MTU 12V4000G15S engine.
What fuel does the MTU 12V4000G15S use?
The MTU 12V4000G15S runs on diesel.
What is the oil capacity of the MTU 12V4000G15S?
The MTU 12V4000G15S engine in the MTU 12V4000G15S has an oil capacity of 260.0 liters.
What alternator does the MTU 12V4000G15S use?
The MTU 12V4000G15S uses a MTU 641-S55 alternator. It has 4 poles. Insulation class F.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 197.0 | 52.0 |
| Prime | 75% | 274.0 | 72.0 |
| Prime | 100% | 362.0 | 96.0 |
| Standby | 50% | 197.0 | 52.0 |
| Standby | 75% | 274.0 | 72.0 |
| Standby | 100% | 362.0 | 96.0 |