HomeMTUMTU 12V4000G14

MTU 12V4000G14 Generator Set

The MTU 12V4000G14 is a 1352 kW (1600 kVA) diesel standby generator set powered by a MTU 12V4000G14F engine. It is available at 380 V, 400 V, 415 V and 11 V, three-phase-phase, 50 Hz and rated 2431 A. It holds about 260 L (68.7 gal) of oil and 160 L (42.3 gal) of coolant, with a maximum ambient rating of not specified °C. Starting uses 1 group-not specified battery rated 1420 CCA at 24 V. The set measures 4059×1810×2330 mm (159.8×71.3×91.7 in), weighs about 10654 kg (23488 lb) and produces not specified dBA at not specified m. An integrated tank holds not specified L (None gal), roughly not specified hours of runtime.

1352 kW
Standby
57.2 L
Displacement
260.0 L
Oil capacity
1
Document types

How to read your MTU serial & model number →

Compare with other 1350–1355 kW Diesel generators →

Specifications

Fueldiesel
Frequency50.0 Hz
Standby power1352 kW
Standby kVA1600
Prime power1352 kW
EmissionsNOx emission optimized
ControllerBasler controller
Oil capacity260.0 L
AlternatorLeroy-Somer LSA52.3 S5
Voltage options380 V, 400 V, 415 V, 11 V
Phasethree-phase
Rated current2431 A
Circuit breaker2431 A
Battery groupnot specified
Battery cranking1420 CCA
Battery voltage24 V
Battery quantity1
Coolant capacity160 L
Max ambientnot specified °C
Dimensions (L×W×H)4059×1810×2330 mm
Dry weight10654 kg
Tank runtimenot specified hr

Engine

MTU 12V4000G14F
Oil capacity260.0 L
Coolant capacity200.0 L
Displacement57.2 L
Aspirationwater charge air cooling
Rated speed1500 rpm

Common questions

What is the power rating of the MTU 12V4000G14?

The MTU 12V4000G14 is rated 1352 kW standby (1600.0 kVA).

What engine does the MTU 12V4000G14 use?

The MTU 12V4000G14 is powered by the MTU 12V4000G14F engine.

What fuel does the MTU 12V4000G14 use?

The MTU 12V4000G14 runs on diesel.

What is the oil capacity of the MTU 12V4000G14?

The MTU 12V4000G14F engine in the MTU 12V4000G14 has an oil capacity of 260.0 liters.

What alternator does the MTU 12V4000G14 use?

The MTU 12V4000G14 uses a Leroy-Somer LSA52.3 S5 alternator.

Fuel consumption

RatingLoadL/hgal/h
Prime50%184.8
Prime75%272.075.2
Prime100%373.0103.7
Standby50%200.21272.0
Standby75%274.61304.0
Standby100%342.21296.0

Available documents

Reference — 1650kva-mtu-engines (MTU)Reference — 3237471 PG spec 12V4000DS1650 1600kVA 3B FC 50Hz (MTU)Reference — 3237481 PG spec 12V4000DS1750 1700kVA 3B FC 50Hz (MTU)Reference — 3237641 PG spec 12V4000DS1650 1600kVA 3B NOx 50Hz (MTU)Reference — 3237651 PG spec 12V4000DS1750 1700kVA 3B NOx 50Hz (MTU)Reference — 3237741 PG spec 12V4000DS1750 1700kVA 3B NEA 50Hz (MTU)Reference — 3238381 PG spec 12V4000DS1650 1600kVA 3F FC 50Hz (MTU)Reference — 3238541 PG spec 12V4000DS1650 1600kVA 3E NEA 50Hz (MTU)Reference — 3238551 PG spec 12V4000DS1750 1700kVA 3E NEA 50Hz (MTU)Reference — 3238781 PG spec 12V4000DS1650 1600kVA 3E NOx 50Hz (MTU)Reference — 3238791 PG spec 12V4000DS1750 1700kVA 3E NOx 50Hz (MTU)Reference — 3238861 PG spec 12V4000DS1650 1600kVA 3F NOx 50Hz (MTU)Reference — 3238871 PG spec 12V4000DS1750 1700kVA 3F NOx 50Hz (MTU)Reference — MTU REACH SVHC 2021-03-17-EN final (MTU)

Other sets with this engine