Specifications
| Fuel | diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 800 kW |
| Standby kVA | 1000 |
| Prime power | 720 kW |
| Emissions | EPA Nonroad T2 compliant |
| Controller | ECU 9 |
| Oil capacity | 72.5 L |
| Alternator | Leroy-Somer LSA 49.3 L10 (Class H-class insulation) |
| Voltage options | 380 V, 400 V, 415 V |
| Phase | 3-Phase |
| Rated current | 1367 A |
| Power factor | 0.8 |
| Battery voltage | 12 VDC V |
| Battery quantity | 2 |
| Coolant capacity | 65 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 3670×2095×2525 mm |
| Dry weight | 5700 kg |
| Sound level | 77.7 dBA @ 7 m |
| Fuel tank | 800.0 L |
| Tank runtime | 4.7 hr |
Engine
| Oil capacity | 72.5 L |
|---|---|
| Coolant capacity | 65.0 L |
| Displacement | 22.44 L |
| Aspiration | turbocharged |
| Rated speed | 1500 rpm |
Common questions
How many kW is the MTU 12V1600 DS1000?
The MTU 12V1600 DS1000 is rated 800 kW standby (1000.0 kVA).
What engine does the MTU 12V1600 DS1000 use?
The MTU 12V1600 DS1000 is powered by the MTU 12V1600G31F engine.
What kind of fuel does the MTU 12V1600 DS1000 run on?
The MTU 12V1600 DS1000 runs on diesel.
What's the oil capacity on a MTU 12V1600 DS1000?
The MTU 12V1600G31F engine in the MTU 12V1600 DS1000 has an oil capacity of 72.5 liters.
What is the coolant capacity of the MTU 12V1600 DS1000?
The MTU 12V1600 DS1000 cooling system holds 65 liters (17.2 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the MTU 12V1600 DS1000?
The MTU 12V1600 DS1000 is rated 720 kW prime (900 kVA), against 800 kW standby.
What is the sound level of the MTU 12V1600 DS1000?
The MTU 12V1600 DS1000 is rated at 77.7 dBA at 7 m, per the manufacturer specification sheet.
What is the dry weight of the MTU 12V1600 DS1000?
The MTU 12V1600 DS1000 has a dry weight of 5700 kg (12566 lb).
What size fuel tank does the MTU 12V1600 DS1000 have?
The MTU 12V1600 DS1000 has a 800 liter (211 US gallon) fuel tank, giving about 4.7 hours of runtime.
What voltages is the MTU 12V1600 DS1000 available in?
The MTU 12V1600 DS1000 is offered in 380 V, 400 V, 415 V, 3-Phase-phase.
What battery does the MTU 12V1600 DS1000 use?
The MTU 12V1600 DS1000 uses 2 batteryies, 12 VDC V each, per the manufacturer specification sheet.
What alternator comes on the MTU 12V1600 DS1000?
The MTU 12V1600 DS1000 uses a Leroy-Somer LSA 49.3 L10 alternator. Insulation class H-class.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 90.3 | 23.85 |
| Prime | 75% | 130.0 | 34.34 |
| Prime | 100% | 170.7 | 45.09 |
| Standby | 50% | 99.2 | 26.21 |
| Standby | 75% | 143.7 | 37.96 |
| Standby | 100% | 190.7 | 50.38 |
Available documents