Specifications
| Fuel | gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 600 kW |
| Standby kVA | 750 |
| Oil capacity | 122.0 L |
| Alternator | Leroy-Somer LSA 49.1 M5 |
| Voltage options | 208 V, 240 V, 380 V, 480 V, 600 V, 4160 V |
| Phase | 3 |
| Power factor | 0.8 |
| Battery group | 8D |
| Battery cranking | 2800 CCA |
| Battery voltage | 24 V |
| Battery quantity | 4 |
| Coolant capacity | 236 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 4742×2222×2457 mm |
| Dry weight | 8500 kg |
| Sound level | 94.3 dBA @ 7 m |
Engine
| Oil capacity | 122.0 L |
|---|---|
| Coolant capacity | 88.1 L |
| Displacement | 31.8 L |
| Aspiration | Turbo Charge-Air Cooled |
| Rated speed | 1800 rpm |
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Diesel #2 | Recommended Fuel for diesel gensets (e.g. DS30, DS40, DS50, DS80, DS100, DS125, DS150, DS180, DS200, DS230, DS250, DS275, DS300, DS350, DS400, DS450, DS500) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 208V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 240V | 1 | 12 LEAD | Example from MTU 4R0063 GS30 SYSTEM RATINGS connection row | |
| 240V | 1 | 4 LEAD | Example from MTU 4R0063 GS30 | |
| 240V | 3 | 12 LEAD DELTA | Example from MTU 4R0063 GS30 | |
| 380V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 480V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 600V | 3 | 4 LEAD WYE DOUBLE DELTA | Example from MTU 4R0063 GS30 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the MTU 12V0265 GS600?
The MTU 12V0265 GS600 is rated 600 kW standby (750.0 kVA).
What engine does the MTU 12V0265 GS600 use?
The MTU 12V0265 GS600 is powered by the Power Solutions International 31.8L CAC engine.
What kind of fuel does the MTU 12V0265 GS600 run on?
The MTU 12V0265 GS600 runs on gas.
How much oil does the MTU 12V0265 GS600 take?
The Power Solutions International 31.8L CAC engine in the MTU 12V0265 GS600 has an oil capacity of 122.0 liters.
How much coolant does the MTU 12V0265 GS600 hold?
The MTU 12V0265 GS600 cooling system holds 236 liters (62.3 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the sound level of the MTU 12V0265 GS600?
The MTU 12V0265 GS600 is rated at 94.3 dBA at 7 m, per the manufacturer specification sheet.
What is the dry weight of the MTU 12V0265 GS600?
The MTU 12V0265 GS600 has a dry weight of 8500 kg (18739 lb).
What voltage does the MTU 12V0265 GS600 produce?
The MTU 12V0265 GS600 is offered in 208 V, 240 V, 380 V, 480 V, 600 V, 4160 V, 3-phase.
What size battery does the MTU 12V0265 GS600 need?
The MTU 12V0265 GS600 uses 4 batteryies, 24 V each, 2800 CCA, group 8D, per the manufacturer specification sheet.
What alternator does the MTU 12V0265 GS600 use?
The MTU 12V0265 GS600 uses a Leroy-Somer LSA 49.1 M5 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 30.4 | 8.03 |
| Prime | 75% | 42.5 | 11.23 |
| Prime | 100% | 56.1 | 14.82 |
| Standby | 50% | 5.2 | 1.4 |
| Standby | 75% | 7.5 | 2.0 |
| Standby | 100% | 9.9 | 2.6 |
Available documents