Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 500 kW |
| Standby kVA | 625 |
| Prime power | 450 kW |
| Emissions | EPA Certified |
| Controller | Inteligen |
| Oil capacity | 54.0 L |
| Alternator | Marathon Magna Max |
| Voltage options | 120/208 V, 277/480 V |
| Phase | 3 |
| Power factor | 0.8 |
| Battery cranking | 800 CCA |
| Battery voltage | 24 V |
| Coolant capacity | 159 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 6045×2438×3810 mm |
| Fuel tank | 3028.0 L |
Engine
| Oil capacity | 54.0 L |
|---|---|
| Coolant capacity | 159.0 L |
| Displacement | 16.0 L |
| Aspiration | Turbocharged, Air to Water Aftercooled |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the MQ Power EGC500DD?
The MQ Power EGC500DD is rated 500 kW standby (625.0 kVA).
What engine does the MQ Power EGC500DD use?
The MQ Power EGC500DD is powered by the Detroit Diesel 8V2000-G81 engine.
What fuel does the MQ Power EGC500DD use?
The MQ Power EGC500DD runs on Diesel.
What is the oil capacity of the MQ Power EGC500DD?
The Detroit Diesel 8V2000-G81 engine in the MQ Power EGC500DD has an oil capacity of 54.0 liters.
What alternator does the MQ Power EGC500DD use?
The MQ Power EGC500DD uses a Marathon Magna Max alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| 25% | 38.2 | 10.1 | |
| 50% | 68.5 | 18.1 | |
| 75% | 101.4 | 26.8 | |
| 100% | 142.7 | 37.7 |