Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 174 kW |
| Standby kVA | 217 |
| Prime power | 164 kW |
| Emissions | 4i |
| Controller | Power Zone |
| Oil capacity | 31.2 L |
| Alternator | Marathon 431PSL6336 |
| Voltage options | 120 V, 139 V, 208 V, 220 V, 240 V, 277 V, 480 V |
| Phase | 1Ø, 3Ø |
| Rated current | 646 (240V 1Ø) A |
| Power factor | 1 (1Ø), 0.8 (3Ø) |
| Circuit breaker | 800 A |
| Battery group | 31 |
| Battery cranking | 1000 CCA |
| Battery voltage | 12 V |
| Battery quantity | 1 |
| Coolant capacity | 29.8 L |
| Max ambient | 48.9 °C |
| Dimensions (L×W×H) | 3660×1270×1960 mm |
| Dry weight | 3005 kg |
| Wet weight | 4106 kg |
| Sound level | 68.0 dBA @ 7.01 m |
| Fuel tank | 1295.0 L |
| Tank runtime | 24 hr |
Engine
| Oil capacity | 31.2 L |
|---|---|
| Coolant capacity | 29.8 L |
| Displacement | 6.8 L |
| Aspiration | turbocharged |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the John Deere PE6068HFG95| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | — | ||||
| Fuel filter | — | 500 hr | |||
| Oil filter | — | 500 hr | |||
| Battery | — | 500 hr | |||
| Oil | 31.2 qt | — | 500 hr |
Service intervals
4| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Engine mounts | Check | 500 hr | 12 mo | |
| Engine oil and oil filter | Change | 500 hr | 12 mo | After first 100 hours, then every 500 hours; every 250 hours if not using John Deere Plus 50 II |
| Fuel filter elements | Replace | 500 hr | 12 mo | |
| Generator drive plate torque | Check | 3000 hr | 36 mo |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Engine oil | John Deere Plus 50 II recommended | 31.2 qt | Change interval: 500 hours on John Deere Plus 50 II; 250 hours on other oils | ||
| Fuel | Clean diesel fuel | 1295.0 L | Use only clean diesel fuel |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
7| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| Coolant temperature shutdown | Coolant temperature shutdown - 230°F | Shutdown | ||
| Coolant temperature warning | Coolant temperature warning - 220°F | Warning | ||
| Fuel level shutdown | Fuel level shutdown - 5% | Shutdown | ||
| Fuel level warning | Fuel level warning - 15% | Warning | ||
| Oil pressure shutdown | Oil pressure shutdown - 20 psi | Shutdown | ||
| Oil pressure warning | Oil pressure warning - 25 psi | Warning | ||
| Overspeed | Overspeed protection - 115% | Shutdown |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Magnum MMG205?
The Magnum MMG205 is rated 174 kW standby (217.0 kVA).
What engine does the Magnum MMG205 use?
The Magnum MMG205 is powered by the John Deere PE6068HFG95 engine.
What kind of fuel does the Magnum MMG205 run on?
The Magnum MMG205 runs on diesel.
What's the oil capacity on a Magnum MMG205?
The John Deere PE6068HFG95 engine in the Magnum MMG205 has an oil capacity of 31.2 liters.
What alternator comes on the Magnum MMG205?
The Magnum MMG205 uses a Marathon 431PSL6336 alternator.
Troubleshooting
6Fault codes
| Code | Meaning | Remedy |
|---|---|---|
| 00383 | Exhaust Filter Cleaning enabled. | |
| 1 | To Service | Oil Maintenance |
Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| LOW FUEL LEVEL SHUTDOWN | Fuel level on the LCD window is low, fuel tank has leaks, fuel level sender or wiring damaged. | Check and refill fuel. Inspect for leaks. Check fuel level sender and wiring. |
| LOW OIL PRESSURE SHUTDOWN | Oil pressure is less than 20 psi, engine has oil leaks. | Check oil level with dipstick. Visually inspect for leaks. Restart and verify oil pressure. Check oil pressure sender. |
| LOW COOLANT LEVEL SHUTDOWN | Coolant level in the radiator is low, coolant hoses, engine block or water pump have visible leaks. | Check and add coolant. Inspect for leaks. Check engine oil for mixed coolant. |
| HIGH COOLANT TEMPERATURE SHUTDOWN | Coolant temperature is 230°F or more. | Check coolant level in overflow jug. Add coolant if low. Stop engine immediately. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Magnum MMG205 troubleshooting guide (10 entries) →
Parts
1| Part # | Description | Qty | System | |
|---|---|---|---|---|
| P-205-003 | Fuel Filter | 1 | Fuel filter | Amazon eBay |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 24.2 | 6.4 |
| Prime | 75% | 36.3 | 9.6 |
| Prime | 100% | 48.5 | 12.8 |
| Standby | 100% | 28.0 | 7.4 |