Home›Kohler›Kohler 45EFOZ CJ

Kohler 45EFOZ CJ Generator Set

The Kohler 45EFOZ CJ is a 45 kW (56 kVA) Diesel standby generator set. It is available at 110/190 V, 110/220 V, 115/230 V, 220/380 V, 230/400 V and 240/416 V, 3-phase, 50 Hz and rated 171 A. It holds about 14 L (3.7 gal) of oil and 14 L (3.7 gal) of coolant. Starting uses battery rated 625 CCA at 12 V. The set measures 1549×738×961 mm (61.0×29.1×37.8 in) and weighs about 934 kg (2059 lb).

45 kW
Standby
14.0 L
Oil capacity
3
Document types

How to read your Kohler serial & model number →

Typical fuel consumption for 45–50 kW Diesel generators →

Compare with other 45–50 kW Diesel generators →

Specifications

FuelDiesel
Frequency50.0 Hz
Standby power45 kW
Prime power44 kW
EmissionsStage V
ControllerDecision-Maker 3500
Oil capacity14.0 L
Alternator4P8X (4-pole, Class H insulation)
Voltage options110/190 V, 110/220 V, 115/230 V, 220/380 V, 230/400 V, 240/416 V
Phase3
Rated current171 A
Battery cranking625 CCA
Battery voltage12 V
Coolant capacity14.0 L
Dimensions (L×W×H)1549×738×961 mm
Dry weight934 kg

Maintenance & consumables

ItemSpecCapacityPart #Interval
Coolant14.0 L—
Oil14.0 L—

Common questions

How many kW is the Kohler 45EFOZ CJ?

The Kohler 45EFOZ CJ is rated 45 kW standby.

Is the Kohler 45EFOZ CJ diesel or gas?

The Kohler 45EFOZ CJ runs on Diesel.

What is the coolant capacity of the Kohler 45EFOZ CJ?

The Kohler 45EFOZ CJ cooling system holds 14 liters (3.7 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

How much oil does the Kohler 45EFOZ CJ take?

The Kohler 45EFOZ CJ has an engine oil capacity of 14 liters (14.8 US quarts), per the manufacturer specification sheet.

What is the continuous rating of the Kohler 45EFOZ CJ?

The Kohler 45EFOZ CJ is rated 44 kW prime (56 kVA), against 45 kW standby.

How much does the Kohler 45EFOZ CJ weigh?

The Kohler 45EFOZ CJ has a dry weight of 934 kg (2059 lb).

What voltage does the Kohler 45EFOZ CJ produce?

The Kohler 45EFOZ CJ is offered in 110/190 V, 110/220 V, 115/230 V, 220/380 V, 230/400 V, 240/416 V, 3-phase.

What battery does the Kohler 45EFOZ CJ use?

The Kohler 45EFOZ CJ uses 12 V each, 625 CCA, per the manufacturer specification sheet.

What alternator does the Kohler 45EFOZ CJ use?

The Kohler 45EFOZ CJ uses a 4P8X alternator. It has 4 poles. Insulation class H.

Parts

6model family
Part #DescriptionQtySystem
100EFOZCJGenerator † Model1Service part / kit buy
125EFOZCJGenerator † Model1Service part / kit buy
125EOZCJGenerator † Model1Service part / kit buy
150EOZCJGenerator † Model1Service part / kit buy
33EFOZCJGenerator † Model1Service part / kit buy
40EOZCJGenerator † Model1Service part / kit buy

Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime25%5.671.5
Prime50%9.652.55
Prime75%13.663.61
Prime100%17.644.66

Available documents

Spec sheet (Kohler)Spec sheet — 007165-01 MAR Commercial SpecificationSheetRevise v2 (Kohler)Spec sheet — Commercial SpecSheet (Kohler)Spec sheet — g2162 (Kohler)Owner's manual — tp6861 (Kohler)Parts manual — MAR CommercialBroch2015 (Kohler)

This page was generated from the 6 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.