Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 213 kW |
| Standby kVA | 266 |
| Prime power | 194 kW |
| Controller | DECISION-MAKER 1000 |
| Oil capacity | 33.0 L |
| Alternator | Fast-Response PMG (Class Class H insulation) |
| Voltage options | 480 V |
| Phase | 3-phase |
| Circuit breaker | 630 A |
| Coolant capacity | 25.8 L |
| Dimensions (L×W×H) | 5360×2005×2159 mm |
| Dry weight | 4708 kg |
| Tank runtime | 17 hr |
Engine
| Oil capacity | 33.0 L |
|---|---|
| Coolant capacity | 25.8 L |
| Displacement | 6.8 L |
| Aspiration | Turbocharged, Aftercooled |
| Rated speed | 1800 rpm |
Filters for the John Deere 6068HFS89
6Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P550779 | Lube Filter, Spin-On Full Flow | JOHN DEERE RE504836, JOHN DEERE RE50486, NAPA 7750S, SKYJACK 13502869 | KuduParts $19.00 |
| Oil filter | P551352 | Lube Filter, Spin-On Full Flow | JOHN DEERE DZ118286, JOHN DEERE PMLF3703, NAPA 401062, BALDWIN B40168 | buy |
| Fuel filter | P550090 | Fuel Filter, In-Line | JOHN DEERE AE20952, JOHN DEERE AT101565, ASV INCORPORATED 0201914, LOESING 025125 | FridayParts $45.66 |
| Fuel filter | P551130 | Fuel Filter, Box | JOHN DEERE AR50041, JOHN DEERE R16951, NAPA 3370, BALDWIN BF909 | KuduParts $37.00 |
| Fuel / water separator | P551424 | Fuel Filter, Water Separator Spin-On | JOHN DEERE RE503198, JOHN DEERE RE522868, NAPA 3532, NAPA 600094 | KuduParts $16.00 FridayParts $18.50 |
| Fuel / water separator | P551422 | Fuel Filter, Water Separator Cartridge | JOHN DEERE AT274723, JOHN DEERE RE22878, NAPA 3978, CLAAS 0011318200 | KuduParts $22.00 FridayParts $24.50 |
Filters & service parts
model family| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | — | ||||
| Fuel filter | — | ||||
| Oil filter | — | ||||
| Coolant | — | ||||
| Oil | — | 250 hr |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.
Service intervals
3| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| External load bank test | Test | 2 hr | Load generator to 100% of rated load for a period of two (2) hours; provide complete report with recommendations | |
| Generator transfer switch testing | Test | 6 mo | Testing of the generator transfer switch to be completed bi-annually on each generator | |
| Preventative maintenance | Other | 6 mo | Required semi-annually for: Ingersol-Rand Trailer; Kohler Trailer; Service Center - PW; South WWTP; North WWTP; Pine Street Water Well; Water Well 5 & 6 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
2Preventative Maintenance Tasks (Quarterly and Semi-Annual) maintenance
- Replace oil, air, water, and fuel filters with new filters, if needed
- Check and tighten all electrical connections on generators
- Check and clean battery connections; check and record battery charge rates
- Start and load generator; while running check and record coolant temperature
- Check function of day tank pump
- Check voltage and hertz; adjust if needed
- Check for exhaust leaks
- Check fuel level
- Check all fluid levels
- Check for fluid leaks
- Check and tighten all belts; replace if necessary
- Provide report listing conditions of all systems
- Tighten all electrical connections in transfer switches; may require non-business hours at no additional charge
- Provide one (1) external load bank test to 100% of rated load for two (2) hours; provide complete report with recommendations
- Test the generator transfer switch bi-annually on each generator
Scheduled Maintenance Tasks (Requested) maintenance
- Start and run generator unloaded
- Check voltage and frequency; adjust if necessary
- Check all fluid levels
- Check for fluid leaks
- Check and adjust all belts, if necessary
- Oil changes based on run times/month
- Provide report listing conditions of all systems
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12-lead optional voltage connections | 12 | Alternator optional feature | ||
| 4-lead dedicated voltages | 4 | Alternator standard feature | ||
| 110/127/139/240/254/277 | single-phase | switchable | Towable generator model specifications; some models n/a | |
| 208/220/240/415/440/480 | 3-phase | reconnectable | Towable generator model specifications | |
| 208/220/240/415/440/480 | 3-phase | switchable | Towable generator model specifications |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Kohler 200REOZT?
The Kohler 200REOZT is rated 213 kW standby (266.0 kVA).
Which engine powers the Kohler 200REOZT?
The Kohler 200REOZT is powered by the John Deere 6068HFS89 engine.
Is the Kohler 200REOZT diesel or gas?
The Kohler 200REOZT runs on Diesel.
How much oil does the Kohler 200REOZT take?
The John Deere 6068HFS89 engine in the Kohler 200REOZT has an oil capacity of 33.0 liters.
What is the coolant capacity of the Kohler 200REOZT?
The Kohler 200REOZT cooling system holds 25.8 liters (6.8 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the Kohler 200REOZT?
The Kohler 200REOZT is rated 194 kW prime (242 kVA), against 213 kW standby.
How much does the Kohler 200REOZT weigh?
The Kohler 200REOZT has a dry weight of 4708 kg (10380 lb).
What voltages is the Kohler 200REOZT available in?
The Kohler 200REOZT is offered in 480 V, 3-phase-phase.
What alternator comes on the Kohler 200REOZT?
The Kohler 200REOZT uses a Fast-Response PMG alternator. Insulation class Class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 25.29 | 6.7 |
| Prime | 75% | 30.0 | 7.9 |
| Prime | 100% | 51.88 | 13.7 |
Available documents