Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 128 kW |
| Standby kVA | 160 |
| Prime power | 116 kW |
| Controller | DECISION-MAKER 1000 |
| Oil capacity | 33.0 L |
| Alternator | Fast-Response PMG (Class Class H insulation) |
| Voltage options | 480 V |
| Phase | 3-phase |
| Circuit breaker | 400 A |
| Coolant capacity | 25.8 L |
| Tank runtime | 26 hr |
Engine
| Oil capacity | 33.0 L |
|---|---|
| Coolant capacity | 25.8 L |
| Displacement | 6.8 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Filters for the John Deere 6068HFS82
6Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P550779 | Lube Filter, Spin-On Full Flow | JOHN DEERE RE504836, JOHN DEERE RE50486, NAPA 7750S, SKYJACK 13502869 | KuduParts $19.00 |
| Oil filter | P551352 | Lube Filter, Spin-On Full Flow | JOHN DEERE DZ118286, JOHN DEERE PMLF3703, NAPA 401062, BALDWIN B40168 | buy |
| Fuel filter | P550090 | Fuel Filter, In-Line | JOHN DEERE AE20952, JOHN DEERE AT101565, ASV INCORPORATED 0201914, LOESING 025125 | FridayParts $45.66 |
| Fuel filter | P551130 | Fuel Filter, Box | JOHN DEERE AR50041, JOHN DEERE R16951, NAPA 3370, BALDWIN BF909 | KuduParts $37.00 |
| Fuel / water separator | P551424 | Fuel Filter, Water Separator Spin-On | JOHN DEERE RE503198, JOHN DEERE RE522868, NAPA 3532, NAPA 600094 | KuduParts $16.00 FridayParts $18.50 |
| Fuel / water separator | P551422 | Fuel Filter, Water Separator Cartridge | JOHN DEERE AT274723, JOHN DEERE RE22878, NAPA 3978, CLAAS 0011318200 | KuduParts $22.00 FridayParts $24.50 |
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12-lead optional voltage connections | 12 | Alternator optional feature | ||
| 4-lead dedicated voltages | 4 | Alternator standard feature | ||
| 110/127/139/240/254/277 | single-phase | switchable | Towable generator model specifications; some models n/a | |
| 208/220/240/415/440/480 | 3-phase | reconnectable | Towable generator model specifications | |
| 208/220/240/415/440/480 | 3-phase | switchable | Towable generator model specifications |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the Kohler 125REOZT?
The Kohler 125REOZT is rated 128 kW standby (160.0 kVA).
What engine is in the Kohler 125REOZT?
The Kohler 125REOZT is powered by the John Deere 6068HFS82 engine.
What kind of fuel does the Kohler 125REOZT run on?
The Kohler 125REOZT runs on Diesel.
How much oil does the Kohler 125REOZT take?
The John Deere 6068HFS82 engine in the Kohler 125REOZT has an oil capacity of 33.0 liters.
How much coolant does the Kohler 125REOZT hold?
The Kohler 125REOZT cooling system holds 25.8 liters (6.8 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the Kohler 125REOZT?
The Kohler 125REOZT is rated 116 kW prime (145 kVA), against 128 kW standby.
What voltage does the Kohler 125REOZT produce?
The Kohler 125REOZT is offered in 480 V, 3-phase-phase.
What alternator comes on the Kohler 125REOZT?
The Kohler 125REOZT uses a Fast-Response PMG alternator. Insulation class Class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 21.76 | 5.7 |
| Prime | 75% | 29.41 | 7.8 |
| Prime | 100% | 33.74 | 8.9 |