Specifications
| Frequency | 60.0 Hz |
|---|---|
| Standby power | 74 kW |
| Standby kVA | 99 |
| Oil capacity | 15.5 L |
| Alternator | Marathon 362PSL1667 |
| Voltage options | 600 V, 480 V, 208 V, 240 V |
| Rated current | [{'kva': 79, 'amps': 76}, {'kva': 78, 'amps': 93}, {'kva': 66, 'amps': 184}, {'kva': 0, 'amps': 0}] A |
| Power factor | [{'kva': 72, 'pf': 1}, {'kva': 72, 'pf': 0.8}] |
| Circuit breaker | 300 A |
| Battery cranking | 720 CCA |
| Battery voltage | 12 V |
| Battery quantity | 1 |
| Coolant capacity | 26.0 L |
| Dimensions (L×W×H) | 2440×970×1580 mm |
| Dry weight | 1543 kg |
| Sound level | 68.0 dBA @ 23 m |
| Fuel tank | 556.0 L |
| Tank runtime | 24 hr |
Maintenance & consumables
for the John Deere PE4045TF285| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Check the condition of the air filter by viewing the level of vacuum draw on the filter minder gauge. Replace the air filter when the yellow center bar reaches the red section on the gauge (20 in. H2O). | — | find | ||
| Fuel filter | Check fuel filter/water separator bowl as required. Replace primary air cleaner when dust valve restriction indicator gauge shows a vacuum of 25 in. H2O. | — | find | ||
| Oil filter | Change the oil and oil filter after the first 100 hours, then every 250 hours. If John Deere Plus 50 II engine oil is used, the interval can be increased to every 500 hours. | — | find | ||
| Belt | Check belt tensioners. John Deere engines use two types of belt tensioners: manual and automatic. | — | find | ||
| Coolant | Check the coolant level daily. The coolant is checked by visually inspecting the level in the coolant overflow jug, located near the radiator. | — | |||
| Oil | Check oil level daily before starting the engine. DO NOT start the generator if the oil level is below the 'ADD' mark on the dipstick. | — |
Common questions
What is the power rating of the John Deere PE4045TF285?
The John Deere PE4045TF285 is rated 74 kW standby (99.0 kVA).
What engine does the John Deere PE4045TF285 use?
The John Deere PE4045TF285 is powered by the John Deere PE4045TF285 engine.
What alternator does the John Deere PE4045TF285 use?
The John Deere PE4045TF285 uses a Marathon 362PSL1667 alternator.
Troubleshooting
8Fault codes
| Code | Meaning |
|---|---|
| Sd Gen L1 <V | Shutdown Generator Line 1 Voltage Low |
| Sd Gen L2 <V | Shutdown Generator Line 2 Voltage Low |
| Sd Gen L3 <V | Shutdown Generator Line 3 Voltage Low |
Symptoms & remedies
| Symptom | Remedy |
|---|---|
| Oil pressure value does not read 5 psi (34 kPa) within five seconds | Visually inspect the engine for oil leaks. If the oil level is good, restart the unit and verify the loss of oil pressure. Shut the engine down immediately if the oil pressure value does not read 5 psi (34 kPa) within five seconds. Check the oil sender. |
| LOW COOLANT LEVEL | Allow the engine to cool. Check the coolant level in the radiator. To access the radiator cap, you must remove the access panel from the top of the enclosure directly above the radiator. Add coolant until it is 3/4 in. (1.9 cm) below the filler neck. Secure the radiator cap back into its original position. Inspect coolant hoses, engine block and water pump for visible leaks. Check the engine oil to verify no coolant has mixed with it (oil will appear milky if coolant is present). Consult the engine operator’s manual for additional information. |
| HIGH COOLANT TEMPERATURE | Check the coolant level in the overflow jug. Restart the engine and read the coolant temperature to verify a high coolant temperature shutdown. Stop the engine immediately if the coolant temperature is 230°F (110°C) or more. Allow the engine to cool. Add coolant to the overflow jug if it is low and then check the level of coolant in the radiator. To access the radiator cap, you must remove the access panel from the top of the enclosure directly above the radiator. Add coolant until it is 3/4 in. (1.9 cm) below the filler neck. Secure the radiator cap back into its original position. Check the radiator shroud and ducting for blockage and remove any foreign matter. Inspect coolant hoses, engine block and water pump for visible leaks. Check the tension of the serpentine drive belt for the water pump. If no other problems are found, remove the load on the generator and restart the engine. Check the coolant temperature and shut the engine down immediately if it starts to overheat. Consult the engine operator’s manual for additional information on engine overheating. |
| OVERCRANK SHUTDOWN | Check the fuel level in the tank. Check for proper operation of the fuel pump. Check the air filter for blockage. If the engine will not start, consult the engine operator’s manual for additional information on trouble-shooting starting problems. |
| OVERSPEED OR UNDERSPEED SHUTDOWN | Disconnect all loads and restart the generator. Read the frequency (Hz) on the LCD display. With no loads on the generator, the frequency should read 60.0 Hz. If the frequency is above or below 60.0 Hz, the engine speed will have to be adjusted. Refer to the engine operator’s manual for throttle adjustments on mechanical governed units and see the electronic governor manual for electronically controlled units. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.
Parts
5| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 01-4 | High-Pressure Fuel Pump Serial Number | Fuel pump | PartsGeek | |
| 361PSL1670 | Generator Model | 1 | Generator | PartsGeek |
| 362PSL1667 | Generator Model | 1 | Generator | PartsGeek |
| RG13718 | High-Pressure Fuel Pump Model Number | Fuel pump | PartsGeek | |
| RG5419 | High-Pressure Fuel Pump Serial Number | Fuel pump | PartsGeek |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.