Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 1019 kW |
| Standby kVA | 1274 |
| Prime power | 922 kW |
| Emissions | Tier 2 |
| Controller | DSE 8610 |
| Oil capacity | 102.0 L |
| Alternator | Stamford/AvK HCI 634 K (WDG 311) - HCI 634 J (WDG 17) |
| Voltage options | 120/208 V, 277/480 V, 347/600 V |
| Phase | 3 |
| Power factor | 0.8 |
| Circuit breaker | 3200 A |
| Battery cranking | 950 CCA |
| Battery voltage | 24 volt V |
| Battery quantity | 4 |
| Coolant capacity | 206 L |
| Dimensions (L×W×H) | 6057×2438×2590 mm |
| Dry weight | 12100 kg |
| Sound level | 75.0 dBA @ 7 m |
| Fuel tank | 2000.0 L |
| Tank runtime | 8.3 hr |
Engine
| Oil capacity | 102.0 L |
|---|---|
| Coolant capacity | 206.0 L |
| Displacement | 31.84 L |
| Aspiration | Turbocharged, aftercooled |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the Hipower HRMW 1150 T6?
The Hipower HRMW 1150 T6 is rated 1019 kW standby (1274.0 kVA).
What engine does the Hipower HRMW 1150 T6 use?
The Hipower HRMW 1150 T6 is powered by the MTU Detroit Diesel 16V 2000 G85 engine.
What fuel does the Hipower HRMW 1150 T6 use?
The Hipower HRMW 1150 T6 runs on Diesel.
What is the oil capacity of the Hipower HRMW 1150 T6?
The MTU Detroit Diesel 16V 2000 G85 engine in the Hipower HRMW 1150 T6 has an oil capacity of 102.0 liters.
What alternator does the Hipower HRMW 1150 T6 use?
The Hipower HRMW 1150 T6 uses a Stamford/AvK HCI 634 K (WDG 311) - HCI 634 J (WDG 17) alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 70.0 | 18.38 |
| Prime | 50% | 125.08 | 33.04 |
| Prime | 75% | 184.0 | 43.63 |
| Prime | 100% | 240.76 | 63.6 |