HomeHIDHID HDI-200F

HID HDI-200F Generator Set

The HID HDI-200F is a 200 kW (250 kVA) Diesel standby generator set powered by a Iveco/FPT C87TE3F engine. It is available at 120/240 V, 120/208 V, 139/240 V, 277/480 V and 347/600 V, 3-phase, 60 Hz and rated 694 A. It holds about 23 L (6.1 gal) of oil and 28 L (7.4 gal) of coolant, with a maximum ambient rating of 50 °C. Starting uses 1 group-24 battery rated 650 CCA at 24 V.

200 kW
Standby
8.7 L
Displacement
23.0 L
Oil capacity
1
Document types

Compare with other 200–205 kW Diesel generators →

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power200 kW
Standby kVA250
EmissionsTier 3
ControllerDigital control panel with manual and automatic start and stop features. Many programmable automatic functions for local and remote controls with LED lights and tamper proof engine hour recorder.
Oil capacity23.0 L
AlternatorStamford/AvK UCI274H
Voltage options120/240 V, 120/208 V, 139/240 V, 277/480 V, 347/600 V
Phase3
Rated current694 A
Power factor0.8
Circuit breaker602 A
Battery group24F
Battery cranking650 CCA
Battery voltage24 V
Battery quantity1
Coolant capacity28 L
Max ambient50 °C

Engine

Iveco/FPT C87TE3F
Oil capacity23.0 L
Coolant capacity28.0 L
Displacement8.7 L
AspirationTurbocharged aftercooled air/air
Rated speed1800 rpm

Maintenance & consumables

for the Iveco/FPT C87TE3F
ItemSpecCapacityPart #Interval
Air filterHeavy duty - single cartridge find
Fuel filterSecondary 5 Microns @ 98% Efficiency find
Oil filterSecondary 5 Microns @ 98% Efficiency find
BeltFlexible fuel lines find

Common questions

What is the power rating of the HID HDI-200F?

The HID HDI-200F is rated 200 kW standby (250.0 kVA).

What engine does the HID HDI-200F use?

The HID HDI-200F is powered by the Iveco/FPT C87TE3F engine.

What fuel does the HID HDI-200F use?

The HID HDI-200F runs on Diesel.

What is the oil capacity of the HID HDI-200F?

The Iveco/FPT C87TE3F engine in the HID HDI-200F has an oil capacity of 23.0 liters.

What alternator does the HID HDI-200F use?

The HID HDI-200F uses a Stamford/AvK UCI274H alternator.

Fuel consumption

RatingLoadL/hgal/h
Standby25%15.94.2
Standby50%31.48.3
Standby75%45.412.0
Standby100%59.415.7

Available documents

Reference — HIPOWER-HDI200F (HID)