HomeDynaGenDynaGen GSC400

DynaGen GSC400 Generator Set

The DynaGen GSC400 is a generator set. It is available at 120 V, 240 V, 208 V and 480 V. The set measures 139×113×65 mm (5.5×4.4×2.6 in) and weighs about 0.45 kg (1 lb).

3
Document types

Specifications

ControllerGSC400 Automatic Gen-Set
Voltage options12/24 V
Dimensions (L×W×H)139×113×65 mm
Dry weight0 kg

Troubleshooting

8

Symptoms & remedies

SymptomCauseRemedy
High Engine Temperature reads around 1300F.This is normal when engine temperature is set to pin 3 or 4.Set to “Dat Pin2” (firmware 2.04.06 and higher) and change sender to pin 2. For firmware 2.04.03 and below set signal source to pin 2, and then once this is done program the “DatCon K – LowZ” to the controller using the GSC400 programmer and PC configurator. The high engine temperature will then read down to 720F.
High Engine Temperature or Low Oil Pressure not reading correctly.1. Confirm that the sender is connected to the correct input pin terminal. Check the wiring for continuity. Check that the GSC400 is setup correctly in the advanced menu. 2. With the generator not running, unplug the sensor (analog inputs) plug from the controller. It’s the 2x4 pin connector on the bottom. On the GSC400 sensor terminal, measure the DC voltage of the input pin to battery negative. Do this on the GSC400 terminal, not the plug. It should read 5VDC. If it does not, there may be a problem with the controller. 3. Plug the sensor connector back in. You may need to do this step with or without the generator running. Look at the display on the GSC400 and note the value displayed. Then measure the DC voltage from the output of the sensor to battery negative. Note the reading. Lookup the pressure or temperature value using this voltage in the tables below. If it matches the value displayed on the GSC400 then the sender may be bad. If it does not, there is an issue with the wiring or setup or the controller may be bad. 4. Disconnect the sensor plug again and measure the resistance from the pin on the plug to battery negative. Refer to the below tables. Does the value from the table match the expected value? If not, the sender or wiring may be bad.
Speed is zero, generator won’t stop cranking.Speed 1 and 2 terminals (J17, J18) need to be connected to generator output.
Turns off starter prematurely or does not turn on starter and then goes into a low speed or low AC voltage failure without starting the generator.1. Check that there are no breakers off. This can unload the GSC400 sensing inputs allowing the wiring to act as an antenna. 2. Check the AC voltage and frequency during cranking. If it reads a few volts then it is likely the GSC400 is picking this up. If the frequency reads 50/60Hz, then the controller will assume the generator has started already. Try another L-L or L-N connection. 3. If necessary, install an isolation transformer to prevent stray signals.
Fuel, Crank, and/or Extra Relay outputs are not turning on.1. Check that the proper relay (12VDC or 24VDC) is used based on the system voltage. 2. Check that the fuse beside each relay is not blown.
GSC400 speed sensing terminals picking up stray signals during crankingThe GSC400 is sensitive to low voltages and frequency readings of 50/60Hz can cause it to think the generator has started.1. Check that there are no breakers off. 2. Check AC voltage and frequency during cranking. 3. Install an isolation transformer.
High Engine Temperature reads around 1300FSet to “Dat Pin2” (firmware 2.04.06 and higher) and change sender to pin 2. For firmware 2.04.03 and below set signal source to pin 2, and then once this is done program the “DatCon K – LowZ” to the controller using the GSC400 programmer and PC configurator.
High Engine Temperature or Low Oil Pressure not reading correctly1. Confirm that the sender is connected to the correct input pin terminal. 2. Check wiring for continuity. 3. With the generator not running, unplug the sensor (analog inputs) plug from the controller and measure DC voltage on GSC400 terminal. 4. Plug the sensor connector back in and measure DC voltage from output of the sensor to battery negative. 5. Disconnect the sensor plug again and measure resistance from pin on the plug to battery negative.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

11
Part #DescriptionQtySystem
ACC0027Temperature sender (Datcon 02022-00, 1/8” NPTF-27) (consult with factory for other thread sizes)1Sensor PartsGeek
ACC0086GSC400 Cable Set consisting of: AC Current Sensing Harness (1375R2-5), Sensor Inputs Harness (1376R2-5), and the Configurable Switched Input Harness (1378R2-5). All are 5 feet long.1Sensor PartsGeek
ACC0108Oil pressure sender (Stewart & Warner 279B-F, 1/8” NPT)1Sensor PartsGeek
ACC0122Oil pressure sender (Sensata 67CP-0320150GFNA0C, 1/4” NPTF-2A) – This is a 0-5V electronic sensor for severe vibration and continuous duty applications. This sensor also requires DWG1410R2-5 (GSC400 5ft wires – pack of 5) and ACC0125 (SENSATA - 27710-2, harness, 40”).1Sensor PartsGeek
ACC0125SENSATA - 27710-2, harness, 40”1Service part / kit PartsGeek
DWG1373R3-5J1939 harness with a built-in 120Ohm resistorService part / kit PartsGeek
DWG1375R2-5J1939 harness without a built-in terminating resistorService part / kit PartsGeek
DWG1377R2-5GSC400 Switched Outputs Harness. Needed if you require additional switched outputs outside of those provided with the three on-board relays: Fuel, Crank, and Extra Relay.1Service part / kit PartsGeek
DWG1410R2-5GSC400 5ft wires – pack of 51Service part / kit PartsGeek
DWG1454mates to the GSC400 RS485 connector and provides pig tails for customer connections1Service part / kit PartsGeek
UGSC400GSC400 Automatic Gen-Set ControllerService part / kit PartsGeek

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Reference — GSC400 Calibration Utility Manual (DynaGen)Reference — es52 sensata installationmanual acc0122 man-0090r2-0 (DynaGen)Owner's manual — GSC400 User Manual (DynaGen)Owner's manual — MAN-0076R5.0, GSC400 User Manual (DynaGen)Service manual — dynagen gsc400 quick-start-guide man-0091r2-0 (DynaGen)