Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 72 kW |
| Standby kVA | 91 |
| Prime power | 65 kW |
| Oil capacity | 12.0 L |
| Voltage options | 400 V, 380 V, 220 V |
| Phase | 3 |
| Rated current | 118 A |
| Power factor | 0.8 |
| Coolant capacity | 48 L |
| Dimensions (L×W×H) | 3200×1100×1850 mm |
| Dry weight | 2190 kg |
Maintenance & consumables
for the Doosan D1146| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Maintenance due for air filter. | — | find | ||
| Fuel filter | Maintenance due for fuel filter. | — | find | ||
| Oil filter | Maintenance due for oil filter. | 2474Y9037A | PartsGeek |
Compatible filters for the Doosan D1146 — cross-referenced via Donaldson. Options to verify against your serial number, not confirmed for this exact unit.
- Fuel filter: Doosan 65125035016B Doosan 65125035001A Donaldson P550860 Donaldson P551001 Donaldson P550060
Common questions
What is the power rating of the Doosan G80XW/XF?
The Doosan G80XW/XF is rated 72 kW standby (91.0 kVA).
What engine does the Doosan G80XW/XF use?
The Doosan G80XW/XF is powered by the Doosan D1146 engine.
What fuel does the Doosan G80XW/XF use?
The Doosan G80XW/XF runs on Diesel.
What is the oil capacity of the Doosan G80XW/XF?
The Doosan D1146 engine in the Doosan G80XW/XF has an oil capacity of 12.0 liters.
Troubleshooting
8Symptoms & remedies
| Symptom | Remedy |
|---|---|
| Unit is inoperative | Read/Write configuration does not operate Check the battery and wiring to the unit. Check the DC supply. Check the DC fuse. |
| Unit shuts down | Check DC supply voltage is not above 35 Volts or below 9 Volts. Check the operating temperature is not above 70°C. Check the DC fuse. |
| Fail to Start is activated after pre-set number of attempts to start | Check wiring of fuel solenoid. Check fuel. Check battery supply. Check battery supply is present on the Fuel output of the module. Check the speed-sensing signal is present on the module's inputs. Refer to engine manual. |
| Continuous starting of generator when in the Auto Mode | Check that there is no signal present on the 'Remote Start' input. Check configured polarity is correct. Check the mains supply is available and within configured limits. |
| Generator fails to start on receipt of Remote Start signal | Check Start Delay timer has timed out. Check signal is on 'Remote Start' input. Confirm correct configuration of input is configured to be used as 'Remote Start'. |
| Check that the oil pressure switch or sensor is indicating low oil pressure to the controller | Depending upon configuration, then set will not start if oil pressure is not low. |
| Pre-heat inoperative | Check wiring to engine heater plugs. Check battery supply. Check battery supply is present on the Pre-heat output of module. Check pre-heat configuration is correct. |
| Starter motor inoperative | Check wiring to starter solenoid. Check battery supply. Check battery supply is present on the Starter output of module. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.