Cummins/Onan DYH Series Generator Set

The Cummins/Onan DYH Series is a 200 kW ASTM No. 2 Diesel standby generator set powered by a Allis-Chalmers 21000 MKII engine. It holds about 29.3 L (7.7 gal) of oil and 62.5 L (16.5 gal) of coolant.

200 kW
Standby
13.8 L
Displacement
29.3 L
Oil capacity
1
Document types

How to read your Cummins/Onan serial & model number →

Specifications

FuelASTM No. 2 Diesel
Standby power200 kW
Oil capacity29.3 L
AlternatorCummins/Onan YB17/1 (4-pole)

Engine

Allis-Chalmers 21000 MKII
Oil capacity29.3 L
Coolant capacity62.5 L
Displacement13.8 L
Rated speed1800 rpm

Common questions

What is the power rating of the Cummins/Onan DYH Series?

The Cummins/Onan DYH Series is rated 200 kW standby.

What engine does the Cummins/Onan DYH Series use?

The Cummins/Onan DYH Series is powered by the Allis-Chalmers 21000 MKII engine.

What fuel does the Cummins/Onan DYH Series use?

The Cummins/Onan DYH Series runs on ASTM No. 2 Diesel.

What is the oil capacity of the Cummins/Onan DYH Series?

The Allis-Chalmers 21000 MKII engine in the Cummins/Onan DYH Series has an oil capacity of 29.3 liters.

What alternator does the Cummins/Onan DYH Series use?

The Cummins/Onan DYH Series uses a Cummins/Onan YB17/1 alternator. It has 4 poles.

Troubleshooting

6

Symptoms & remedies

SymptomRemedy
Overcrank fault lamp lights and engine stops cranking after approximately 75-seconds.See engine service manual for troubleshooting fuel system. After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position.
Engine runs, shuts down, cranks for 75-seconds, cranking cycle stops, overcrank light ON.1. See engine service manual for troubleshooting fuel system. After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position. 2. Check fuel supply.
Low oil pressure shutdown.3. Check — a. Oil level. Replenish if necessary. b. Sensor. Faulty sensor will shut down engine. c. Refer to engine service manual for troubleshooting guide for oil system.
High engine temperature shutdown.4. Check — a. Coolant level. Replenish if necessary. b. City water cooled sets. Check water flow, valves, etc. c. Check sensor; check thermostat. d. Radiator model, check fan belts, radiator for obstructions, etc.
Engine stops cranking and fault lamp lights, after cranking approximately 75 seconds.See engine service manual for troubleshooting fuel system. After correcting problem, reset engine monitor relay by placing Run-Stop/Reset-Retrieve switch to Stop/Reset, then back to the required running position.
Fault lamp lights immediately after engine starts.Check for: Overspeed condition as engine starts.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Fuel consumption

RatingLoadL/hgal/h
100%58.715.5

Available documents

Operator's manual — 21000 engine (Cummins/Onan)