HomeCummins/OnanCummins/Onan DHA Series

Cummins/Onan DHA Series Generator Set

The Cummins/Onan DHA Series is a 300 kW (375 kVA) Diesel standby generator set powered by a Detroit Diesel V12-71T engine. It is available at 120/208 V, 127/220 V, 139/240 V, 240/416 V, 254/440 V, 277/480 V, 110/190 V, 115/200 V, 220/380 V, 230/400 V, 347/600 V, 120/240 V and 240/480 V, 3-phase, 60 Hz and rated 1042 A. It holds about 34.1 L (9.0 gal) of oil and 52 L (13.7 gal) of coolant. Starting uses 2 group-8 batteries rated 225 CCA at 24 V. The set measures 1780×1650×2900 mm (70.1×65.0×114.2 in) and weighs about 3655 kg (8058 lb). An integrated tank holds 94 L (24.8 gal).

300 kW
Standby
13.96 L
Displacement
34.1 L
Oil capacity
1
Document types

How to read your Cummins/Onan serial & model number →

Compare with other 300–305 kW Diesel generators →

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power300 kW
Standby kVA375
Prime power250 kW
ControllerDetroit Diesel
Oil capacity34.1 L
AlternatorCummins/Onan YB (4-pole)
Voltage options120/208 V, 60 V, 127/220 V, 139/240 V, 240/416 V, 254/440 V, 277/480 V, 110/190 V, 50 V, 115/200 V, 220/380 V, 230/400 V, 347/600 V, 120/240 V, 240/480 V
Phase3
Rated current1042 A
Power factor0.8
Circuit breaker1042 A
Battery group8D
Battery cranking225 CCA
Battery voltage24 V
Battery quantity2
Coolant capacity52 L
Dimensions (L×W×H)1780×1650×2900 mm
Dry weight3655 kg
Fuel tank94.0 L

Engine

Detroit Diesel V12-71T
Oil capacity34.1 L
Coolant capacity52.0 L
Displacement13.96 L
AspirationTurbocharged
Rated speed1800 rpm

Common questions

What is the power rating of the Cummins/Onan DHA Series?

The Cummins/Onan DHA Series is rated 300 kW standby (375.0 kVA).

What engine does the Cummins/Onan DHA Series use?

The Cummins/Onan DHA Series is powered by the Detroit Diesel V12-71T engine.

What fuel does the Cummins/Onan DHA Series use?

The Cummins/Onan DHA Series runs on Diesel.

What is the oil capacity of the Cummins/Onan DHA Series?

The Detroit Diesel V12-71T engine in the Cummins/Onan DHA Series has an oil capacity of 34.1 liters.

What alternator does the Cummins/Onan DHA Series use?

The Cummins/Onan DHA Series uses a Cummins/Onan YB alternator. It has 4 poles.

Troubleshooting

12

Fault codes

CodeMeaningRemedy
*Low oil pressureLow oil pressure shutdown.Check— a. Oil level. Replenish if necessary. b. Sensor. Faulty sensor will shut down engine. c. Refer to engine service manual for troubleshooting guide for oil system.
*High engine temperatureHigh engine temperature shutdown.Check— a. Coolant level. Replenish if necessary. b. City water cooled sets. Check water flow, valves, etc. c. Check sensor; check thermostat. d. Radiator model, check fan belts, radiator for obstructions, etc.
OverspeedOverspeed shutdown.Check governor and throttle linkages for freedom of movement. Check overspeed switch.
*Low oil pressureLow oil pressure light ON.Disconnect wire at TB11-30. Light No shutdown. ON after relay reset. Replace engine monitor board.
*High engine temperatureHigh engine temperature light ON.Disconnect wire at TB11-31. Light No shutdown. ON after relay reset. Replace engine monitor board.

Symptoms & remedies

SymptomCauseRemedy
Engine stops cranking and fault lamp lights, after cranking approximately 75 seconds.See engine service manual for troubleshooting fuel system. After correcting problem, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset, then back to the required running position.
Fault lamp lights immediately after engine starts.Overspeed condition as engine starts.
Fault lamp lights and engine shuts down after running for a period.Check the following: a. Oil level. Engine will shut down if sensor is closed. b. Check engine manual for troubleshooting oil system. c. High engine temperature. Check coolant level; check water flow (city water cooled systems); check radiator for free air flow, and fan belts for tightness. See engine manual for troubleshooting cooling system. d. Check for faulty oil pressure sensor or faulty high engine temperature sensor.
Engine runs, shuts down and cranks for 75-seconds. Cranking cycle stops; fault lamp lights.Check fuel supply.
Fault lamp lights, no fault exists.To check a no-fault condition, disconnect leads from TB11 terminals 29, 30 and 31. If fault lamp lights with leads disconnected, replace engine monitor board. Reconnect leads.
Overcrank fault lamp lights and engine stops cranking after approximately 75-seconds.See engine service manual for troubleshooting fuel system. After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position.
Overspeed light ON, no shutdown.Disconnect wire at TB11-29. Light ON after reset; replace engine monitor board.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

3
Part #DescriptionQtySystem
1A751p pe i1Service part / kit PartsGeek
B182ENGINE HEATER1Service part / kit PartsGeek
B193WOODWARD GOVERNOR1Service part / kit PartsGeek

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime100%94.024.8
Standby100%94.024.8

Available documents

Parts manual — 945-0301 Onan DHA Operator's and Parts Manual (1-1975) (Cummins/Onan)

Other sets with this engine