HomeCummins/OnanCummins/Onan DFM Series 50Hz

Cummins/Onan DFM Series 50Hz Generator Set

The Cummins/Onan DFM Series 50Hz is a 210 kW (262.5 kVA) Diesel standby generator set powered by a Cummins/Onan NTA855-G engine. It is available at 110/190 V, 115/200 V, 120/208 V, 127/220 V, 220/380 V, 230/400 V, 240/416 V and 254/440 V, 3-phase, 50 Hz and rated 798 A. It holds about 40 L (10.6 gal) of oil and 55 L (14.5 gal) of coolant. Starting uses 2 group-8 batteries rated 225 CCA at 24 V. The set measures 2896×1118×1829 mm (114.0×44.0×72.0 in) and weighs about 2867 kg (6321 lb).

210 kW
Standby
14.0 L
Displacement
40.0 L
Oil capacity
0
Document types

How to read your Cummins/Onan serial & model number →

Service parts for the DFM Series 50Hz

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

FuelDiesel
Frequency50.0 Hz
Standby power210 kW
Standby kVA262
ControllerYB Type
Oil capacity40.0 L
AlternatorYB
Voltage options110/190 V, 115/200 V, 120/208 V, 127/220 V, 220/380 V, 230/400 V, 240/416 V, 254/440 V
Phase3
Rated current798 A
Power factor0.8
Battery group8D
Battery cranking225 CCA
Battery voltage24 V
Battery quantity2
Coolant capacity55 L
Dimensions (L×W×H)2896×1118×1829 mm
Dry weight2867 kg

Engine

Cummins/Onan NTA855-G
Oil capacity40.0 L
Coolant capacity55.0 L
Displacement14.0 L
AspirationTurbocharged
Rated speed1800 rpm

Maintenance & consumables

for the Cummins/Onan NTA855-G
ItemSpecCapacityPart #Interval
Air filterAir Cleaner Assembly140-1346 Amazon eBay
Fuel filter500 hr
Oil filter500 hr
Belt
Coolant55.0 liters2000 hr
OilASTM D240.0 liters500 hr

Common questions

What size generator is the Cummins/Onan DFM Series 50Hz?

The Cummins/Onan DFM Series 50Hz is rated 210 kW standby (262.5 kVA).

What engine is in the Cummins/Onan DFM Series 50Hz?

The Cummins/Onan DFM Series 50Hz is powered by the Cummins/Onan NTA855-G engine.

What fuel does the Cummins/Onan DFM Series 50Hz use?

The Cummins/Onan DFM Series 50Hz runs on Diesel.

How much oil does the Cummins/Onan DFM Series 50Hz take?

The Cummins/Onan NTA855-G engine in the Cummins/Onan DFM Series 50Hz has an oil capacity of 40.0 liters.

Which alternator is fitted to the Cummins/Onan DFM Series 50Hz?

The Cummins/Onan DFM Series 50Hz uses a YB alternator.

What air filter does the Cummins/Onan DFM Series 50Hz use?

The Cummins/Onan DFM Series 50Hz uses air filter part number 140-1346.

Troubleshooting

6

Symptoms & remedies

SymptomRemedy
Engine stops cranking and fault lamp lights, after cranking approximately 75 seconds.See engine service manual for troubleshooting fuel system. After correcting problem, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, then back to the required running position.
Fault lamp lights immediately after engine starts.Check for: Overspeed condition as engine starts.
Fault lamp lights and engine shuts down after running for a period.A. Oil level. Engine will shut down if sensor is closed. b. Check engine manual for troubleshooting oil system. c. High engine temperature. Check coolant level; check water flow (city water cooled systems); check radiator for free air flow, and fan belts for tightness. See engine manual for troubleshooting cooling system. d. Check for faulty oil pressure sensor or faulty high engine temperature sensor.
Engine runs, shuts down and cranks for 75-seconds. Cranking cycle stops; fault lamp lights.Check fuel supply.
Fault lamp lights, no fault exists.To check a no-fault condition, disconnect leads from TBl terminals 29, 30 and 31. If fault lamp lights with leads disconnected, replace engine monitor board. Reconnect leads.
Overcrank fault lamp lights and engine stops cranking after approximately 75-seconds.See engine service manual for troubleshooting fuel system. After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan DFM Series 50Hz troubleshooting guide (14 entries) →

Parts

2
Part #DescriptionQtySystem
140-1346Air Cleaner (Includes Element)1Air filter Amazon eBay
100-1359Engine, Replacement (Cummins NTA855G)1Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Standby100%18.44.86

Available documents

Other sets with this engine