HomeCummins/OnanCummins/Onan DF

Cummins/Onan DF Generator Set

The Cummins/Onan DF is a 300 kW (375 kVA) Diesel standby generator set powered by a Cummins/Onan HRC-4 engine. It is available at 120/240 V, 120/208 V and 220/380 V, 60-phase, 60 Hz and rated 1042 A. It holds about 13 L (3.4 gal) of oil and 137.5 L (36.3 gal) of coolant, with a maximum ambient rating of 40 °C. Starting uses 2 group-8 batteries rated 200 CCA at 24 V. The set measures 3280×1400×2100 mm (129.1×55.1×82.7 in) and weighs about 4625 kg (10196 lb).

300 kW
Standby
8.15 L
Displacement
13.0 L
Oil capacity
3
Document types

How to read your Cummins/Onan serial & model number →

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power300 kW
Standby kVA375
Prime power140 kW
ControllerBarber-Colman DYNA 1 Governor, Electronic Governor, Onan YB17
Oil capacity13.0 L
AlternatorCummins/Onan YB17/1 (4-pole)
Voltage options110/190 V, 115/200 V, 120/208 V, 127/220 V, 220/380 V, 230/400 V, 240/416 V, 254/440 V
Phase3
Rated current1042 A
Power factor0.8
Battery groupSAE Group 8D
Battery cranking200 CCA
Battery voltage24 V
Battery quantity2
Coolant capacity137.5 L
Max ambient40 °C
Dimensions (L×W×H)3280×1400×2100 mm
Dry weight4625 kg

Engine

Cummins/Onan HRC-4
Oil capacity15.19 L
Displacement8.15 L
Rated speed1800 rpm

Maintenance & consumables

for the Cummins/Onan HRC-4
ItemSpecCapacityPart #Interval
Air filterReplaceable element2500 hr find
Fuel filterSpin-off with water drain2500 hr find
Oil filterSpin-off2500 hr find
BeltFan belt1000 hr find
CoolantEthylene glycol base89.0 L5000 hr
Coolant filter find
OilAPI Class CC/CD50.0 L250 hr

Common questions

What is the power rating of the Cummins/Onan DF?

The Cummins/Onan DF is rated 300 kW standby (375.0 kVA).

What engine does the Cummins/Onan DF use?

The Cummins/Onan DF is powered by the Cummins/Onan HRC-4 engine.

What fuel does the Cummins/Onan DF use?

The Cummins/Onan DF runs on Diesel.

What is the oil capacity of the Cummins/Onan DF?

The Cummins/Onan HRC-4 engine in the Cummins/Onan DF has an oil capacity of 15.19 liters.

What alternator does the Cummins/Onan DF use?

The Cummins/Onan DF uses a Cummins/Onan YB17/1 alternator. It has 4 poles.

Troubleshooting

72

Fault codes

CodeMeaningCauseRemedy
Low oil pressure*Low oil pressure shutdown.A. Oil level. Replenish if necessary. b. Sensor. Faulty sensor will shut down engine.C. Refer to engine service manual for troubleshooting guide for oil system.
High engine temperature*High engine temperature shutdown.A. Coolant level. Replenish is necessary. b. City water cooled sets. Check water flow, valves, etc. c. Check sensor; check thermostat. d. Radiator model, check fan belts, radiator for obstructions, etc.
Generator overvoltageGenerator overvoltage.A. Replace SCR block. b. Replace voltage regulator.
*4Green RUN lamp lights following engine start-up.7. Indicates all engine systems are normal. No corrective action required.
2PRE HI ENGINE TEMP lamp lights. Engine continues to operate.2. Indicates engine has begun to overheat and engine temperature has risen to approximately 205°F (97°C). If generator is powering non-critical and critical loads and cannot be shutdown, use the following: a. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. c. Open doors or windows in generator area to increase ventilation. If engine can be stopped, follow procedure in step 3.
3HI ENG TEMP lamp lights. Engine shuts down.3. Indicates engine has overheated (engine temperature has risen above 215°F/102°C) or coolant level is low (sets with coolant level sensor). Allow engine to cool down completely before proceeding with the following checks: a. Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check for a slipping fan belt and tighten if loose. d, Reset control and restart after locating and correcting problem. Contact an Onan Dealer or Distributor if none of the above.
4PRE LO OIL PRES lamp lights. Engine continues to operate.4. Indicates engine oil pressure has dropped to 20 psi (138 kPa). If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure. If engine can be stopped, follow procedures in step 5.
5LO OIL PRES lamp lights. Engine shuts down.5. Indicates engine oil pressure has dropped to 14 psi (97 kPa). Check oil level, lines and filters. If oil system is okay but oil level is low, replenish. Reset control and restart. Contact an Onan Dealer or Distributor if oil pressure is not in the range of 50 to 70 psi (345 to 483 kPa).
6OVERCRANK lamp lights and engine stops cranking.6. Indicates possible fuel system problem. a. Check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required. b. Check for dirty fuel filter and replace if necessary (see MAINTENANCE section). c. Check for dirty or plugged air filter and replace if necessary (see MAINTENANCE section). d. Refer to Step 5. e. Reset the control and restart after correcting the problem. Contact an Onan Dealer or Distributor for service if none of the above.
7Engine runs and then shuts down, OVERSPEED lamp lights.7. Indicates engine has exceeded normal operating speed. Contact an Onan Dealer or Distributor for service.
8SWITCH OFF lamp flashes.Position which will prevent automatic starting if an automatic transfer switch is used. Move the Run/Stop/Remote switch to the Remote position for automatic starting.
9LO FUEL lamp lights. Engine continues to run.9. Indicates diesel fuel supply is running low. Check fuel supply and replenish as required.
10LO FUEL lamp lights. Engine shuts down and LO OIL PRES lamp lights.10. Indicates engine has run out of fuel. Check fuel level and replenish as required.
11LO ENG TEMP lamp lights. Set is in standby mode but is not operating.(Lamp lights when engine coolant temperature is 70°F (21°C) or lower. Since the lamp goes out after the engine warms up, there should be no cause for alarm even during initial generator set operation.) Indicates engine coolant heater is not operating or is not circulating coolant. Check for the following conditions: a. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low coolant level and replenish if required. Look for possible coolant leakage points and repair as required. c. Contact an Onan Dealer or Distributor if none of the above.

Symptoms & remedies

SymptomCauseRemedy
ALTERNATOR FAILS TO CHARGE OR PUTS OUT LOW OR UNSTEADY CHARGE RATEFaulty regulator.Replace regulator.
Engine stops cranking and fault lamp lights, after cranking approximately 75 seconds.. See engine service manual for troubleshooting fuel system. After correcting problem, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset, then back to the required running position.
Fault lamp lights immediately after engine starts.. Overspeed condition as engine starts.
Fault lamp lights and engine shuts down after running for a period.. Check the following: a. Oil level. Engine will shut down if sensor is closed. b. Check engine manual for troubleshooting oil system. c. High engine temperature. Check coolant level; check water flow (city water cooled systems); check radiator for free air flow, and fan belts for tightness. See engine manual for troubleshooting cooling system. d. Check for faulty oil pressure sensor or faulty high engine temperature sensor.
Engine runs, shuts down and cranks for 75 seconds. Cranking cycle stops; fault lamp lights.. Check fuel supply.
Fault lamp lights, no fault exists.. To check a no-fault condition, disconnect leads from TB11 terminals. 29, 30 and 31. If fault lamp lights with leads disconnected, replace engine monitor board. Reconnect leads.
Overcrank fault lamp lights and engine stops cranking after approximately 75 seconds.. See engine service manual for troubleshooting fuel system. After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position.
Engine runs, shuts down, cranks for 75 seconds, cranking cycle stops, overcrank light ON.. Check fuel supply.
"Low oil pressure shutdown.. Check— a. Oil level. Replenish if necessary. b. Sensor. Faulty sensor will shut down engine. c. Refer to engine service manual for troubleshooting guide for oil system.
"High engine temperature shutdown.. Check— a. Coolant level. Replenish if necessary. b. City water cooled sets. Check water flow, valves, etc. c. Check sensor: check thermostat. d. Radiator model, check fan belts, radiator for obstructions, etc.
Overspeed shutdown.. Check governor and throttle linkages for freedom of movement. —°Check overspeed switch.
"Overspeed light on, no shutdown.. Disconnect wire at TB11-29. Light on after reset; replace engine monitor board.
"Low oil pressure light ON. No shutdown.. Disconnect wire at TB11-30. Light ON after relay reset. Replace engine monitor board.
"High engine temperature light ON. No shutdown.. Disconnect wire at TB11-31. Light ON after relay reset. Replace engine monitor board.
Engine fails to start after a few seconds of cranking, or starts and runs then stops and fault lamp lightsRefer to appropriate troubleshooting chart Table 4 or Table 5
Fault lamp lights immediately after engine starts and unit shuts down.Indicates possible overspeed condition1. Check the governor and throttle linkage for binding and freedom of movement. Contact an Onan Distributor or the engine manufacturer if linkage is not at fault.
Fault lamp tights and engine shuts down after running for a period.1. Check oil level and replenish if necessary. 2. Check coolant level of radiator and heat exchanger sets and replenish if necessary. 3. Check for slipping drive belts or for obstructions to the airflow. 4. Check water flow valve on city water cooled sets and adjust if necessary. 5. Contact an Onan Distributor or the engine manufacturer if none of the above.
Engine runs, shuts down and cranks for 75-seconds. Cranking cycle stops; fault lamp lights.1. Check for dirty fuel filters and replace if necessary. (See MAINTENANCE section) 2. Check for dirty or plugged air filters and replace if necessary. (See MAINTENANCE section)
Overcrank fault lamp lights and engine stops cranking after approximately 75-seconds.1. Check for empty fuel tank, fuel system leaks, or plugged fuel filters and/or supply lines. Correct as required.
Engine runs, shuts down, cranks for 75-seconds, cranking cycle stops, overcrank light on.1. Check for dirty fuel filters and replace if necessary. (See MAINTENANCE section) 2. Check for dirty or plugged air filters and replace if necessary. (See MAINTENANCE section)
Low oil pressure shutdown.1. Check oil level and replenish if necessary. Contact an Onan Distributor if oil level is correct.
High engine temperature shutdown.1. Check coolant level of radiator and heat exchanger sets and replenish if necessary. 2. Check for slipping drive belts or for obstructions to the airflow. 3. Check water flow valve on city water cooled sets and adjust if necessary. 4. Contact an Onan Distributor or the engine manufacturer if none of the above.
Overspeed light on, no shutdown.. Engine monitor board or sensor malfunction. Contact an Onan Distributor.
Fault lamp lights and engine stops cranking after approximately 75-seconds.See engine service manual for troubleshooting fuel system. After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Ret-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position.
Engine runs, shuts down, cranks for 75-seconds, cranking cycle stops, light ON.Check fuel supply.
*Low oil pressure light ON.7. Disconnect wire at TB11-30. Light ON after relay reset. Replace engine monitor board.
*High engine temperature light ON.8. Disconnect wire at TB11-31. Light ON after relay reset. Replace engine monitor board.
Fault lamp lights and engine stops cranking after approximately 75 seconds.See engine service manual for troubleshooting fuel system, ignition system, etc. After correcting problem, reset the engine monitor by holding run-stop-remote switch in stop position, and depressing reset switch. Release and return to run position.
Fault lamp lights after engine is running.Check the following: a. Oil level-engine will shut down after approximately 12-1/2 seconds if low oil pressure sensor does not open. b. Oil pressure sensor may be defective. c. High engine temperature - See engine service manual. d. Faulty high engine temperature sensor. e. Faulty starter disconnect.
Fault lamp lights - no fault condition exists.Be certain that no fault condition exists. Disconnect lead 30 and 31 from T B I l inside control box (refer to wiring diagram). If fault lamp still lights with leads disconnected, remove and replace engine monitor plug-in printed circuit board.
Overcrank fault lamp lights after engine has run for approximately 75 seconds.Replace start-disconnect circuit board.
High engine temperature lamp lights as soon as engine starts.Check for defective sensor or high temperature condition.
Low oil pressure lamp lights after engine is running.Check: a. Oil level - engine will shut down after approximately 12-1/2 seconds if oil pressure is low.
High engine temperature lamp lights after engine is running.Check for: a. High temperature condition. See Engine service manual. b. Defective high engine temperature sensor.
Overspeed lamp lights - no fault condition exists.Replace overspeed circuit board.
Low oil pressure fault lamp lights - no fault condition exists.Be certain that no fault condition exists. Disconnect lead 30 from T B I l inside control box (refer to wiring diagram). If low oil pressure lamp still lights, remove and replace engine monitor plug-in printed circuit board.
High engine temperature fault lamp lights - no fault condition exists.Be certain that no fault condition exists. Remove lead 31 from TB11 inside control box (refer to wiring diagram). If high engine temperature lamp still lights, remove and replace engine monitor plug-in printed circuit board.
When pressing test lamp.button - one or more fault lamps do not light.Fault lamp/lamps burned, out - replace.
Non-StartIf after a few seconds of cranking engine fails to start, or starts and runs then stops and fault lamp lights, refer to appropriate troubleshooting chart, Table 3 or Table 4.
Generator will not build up voltage.Circuit breaker in 'off' or 'tripped' position, Open in circuit breakerReset and close breaker; Stop plant and check breaker continuity.
No AC power to E2 with the plant operating.Check AC voltage at E1-None; Voltage should be five per cent of the rated voltage. If not, check continuity from E1-E2 back to the generator.
Partial loss of residual in Rotor from E2 to heat sink of field rectifier No. 1 until voltage begins to build-up.None; Then remove.
Both Field Rectifiers are defective.Test rectifiers and replace both if defective.
Output voltage slow to build upOpen in one or both Field Rectifiers 1 and 2 if defectiveTest rectifiers and replace if defective
Output voltage builds up normally with slightly less than rated voltage at no load and low voltage and low voltage and high voltage after build upShorted winding in Control Reactor and Gate windings G1-G2 of Reactor A or B if defectiveTest rectifiers and replace if defective
Output voltage builds up normally but 20 percent above rated voltage after build upShorted turn in Control winding C1-C2 of Reactor A or B if defectiveTest Reactors A and B for shorted turns and replace
Output voltage builds up normally but 125 to 150 percent above rated voltage after build upShorted turn in Control winding C1-C2 of Reactor A or B if defectiveTest Reactors A and B for shorted turns and replace
Output voltage builds up normally but 150 to 200 percent above rated voltage after build upControl winding C1-C2 of Reactor A or B polarized incorrectly
Voltage regulation poorCheck continuity from the junction of Control Rectifiers 3 and 4 to the junction of Control Rectifiers 1 and 2
The external alarm is activatedCheck the conditions that may have caused the fault
The engine does not start.The starter will disengage after a specified period of time and the control will indicate an overcrank fault.Place the Run-Stop-Remote switch in the STOP position and momentarily depress the Reset switch. Wait two minutes for the starter motor to cool and then repeat the starting procedure.
The engine does not run after a second attempt at starting.Refer to the Troubleshooting section.
The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run.Engine standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is timed delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay.
Fault lamp lights but no fault exists. Engine gauges show oil pressure, engine temperature, and frequency (speed) are within normal limits.The monitor board or a sensor may be at fault.Contact an Onan Dealer or Distributor for service.
Engine starts from generator control panel but will not start automatically or from a remote panel, (Note: The Run/Stop/Remote switch must be in the Remote position for automatic or remote starting).Remote circuit breaker is tripped, Reset breaker and restart. Contact an Onan Dealer or Distributor if breaker trips after resetting.
Engine will not crank.Indicates possible fault with control or starting system.Check for the following conditions: a. Fault lamp on. Correct fault and reset control. b. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. c. Discharged or defective battery. Recharge or replace the battery. d. Contact an Onan Dealer or Distributor for assistance if none of the above.
No AC output voltage.Field breaker is tripped.Reset breaker. Contact an Onan Dealer or Distributor if voltage build up causes breaker to trip.
Green RUN lamp does not light following engine start-up.Indicates possible Start/Disconnect relay failure.Contact an Onan Dealer or Distributor for assistance.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

87
Part #DescriptionQtySystem
130-1193Gasket, Radiator Outlet1Gasket PartsGeek
130-1227Gasket, Radiator Inlet4Gasket PartsGeek
130-1229Gasket, Radiator1Gasket PartsGeek
193-0108Sender, Oil Pressure Gauge1Sensor PartsGeek
193-0245Part 193-02451Sensor PartsGeek
1S0A713Bracket, Overspeed Switch1Bracket PartsGeek
1S0A717Switch Assy., Overspeed1Switch PartsGeek
204493Ring, Collector1Ring PartsGeek
2110153Bell, End - Alt, to Exciter1Bell PartsGeek
23201396Support, Gen. Mtg.1Support PartsGeek
2340116Cover, Exciter1Cover PartsGeek
234070Rig Assy., Brush- Incl. Brushes, & Contact Point Band, Gen. - Front Portion(Narrow)1Brush PartsGeek
2348115Bracket, Mtg. - Volt. Cont. Reactor1Bracket PartsGeek
234875Bracket, Gate Reactor Mtg.1Bracket PartsGeek
234C1343-Phase1Phase PartsGeek
234C1373-Phase1Phase PartsGeek
234C140Single Phase1Phase PartsGeek
234C141Single Phase1Phase PartsGeek
2I4AMBrush4Brush PartsGeek
304412515,000-Ohm, 25-W - For 220/380-V, 3-Phase, 4-Wire1Resistor PartsGeek
304A15S Washer, Fixed Resistor Cent. to Alternator End Bell2Washer PartsGeek
304PA76Resistor, Volt. Cont.Reactor (Incl.in Rect.& Resistor A: 305P218)1Resistor PartsGeek
3058227Resistor Assy., Rect, & Incl. (Incl.in Rect. & Resistor A: 305P218)4Resistor PartsGeek
305P233Rectifier Assy., Power (Incl. two #305P234 wire & hardware)2Rectifier PartsGeek
305P234Rectifier Assy., Power (Field) (Incl. in Rect. #305P218)2Rectifier PartsGeek
305P240Rectifier, Volt. Cont.Reactor (Incl.in Rect. & Resistor A: 305P218)4Rectifier PartsGeek
308-0324Switch, Slide2Sensor PartsGeek
309-0304Switch, Thermostat1Thermostat PartsGeek
309-0307Switch, Oil Pressure1Sensor PartsGeek
3320645Strip, Marker - Volt. Con. Reactor (9305P218)1Strip PartsGeek
333-0136Heater, Coolant (240 Volt)1Fluid PartsGeek
333-0142Support, Pressure Switch1Sensor PartsGeek FridayParts $36.80
333-0143Heater, Coolant (208 Volt)1Fluid PartsGeek
3ISA78Rectifier, Voltage Control1Rectifier PartsGeek
503-0788Hose, Radiator4Hose PartsGeek
503-0798Hose1Hose PartsGeek
503-0803Hose, Rubber1Hose PartsGeek
503-0847Hose1Hose PartsGeek
503-0856Hose, Radiator2Hose PartsGeek
503-0860Hose1Hose PartsGeek
511-0059Belt, Alternator1Belt PartsGeek
5208190Stud, Fixed Resistor Mtg.1Stud PartsGeek
805-35Bolt, Place - Gen. Mtg. support to End Bell4Bolt PartsGeek
A956BATTERY (Fig. 8)2Battery PartsGeek
M-1685Engine Sensors1Sensor PartsGeek dieselpartscenter $10.61
SC-1516-2VERTICAL CONTROLLER VOLTAGE REGULATOR VRAS-2Vertical controller voltage regulator vras 2 PartsGeek
VR21Voltage regulator printed circuit module1Sensor PartsGeek
10-86Cummins Engine Manual1Service part / kit PartsGeek
130-1010Radiator1Service part / kit PartsGeek
232A1489Generator support shim, 0.598 in gauge #6, 3x33Service part / kit PartsGeek
232A1490Generator support shim, 0.359 in gauge #20, 3x33Service part / kit PartsGeek
232A1817Generator3Service part / kit PartsGeek
232AI489As Is1Service part / kit PartsGeek
232AI490Onan OE Filter1Service part / kit PartsGeek
232AI817Onan OE Filter1Service part / kit PartsGeek
301021151Box Only, control1Service part / kit PartsGeek
30118301Bracket, Cont.Box Mtg. (Repl. 2-Piece Brkts)1Service part / kit PartsGeek
301A1914Bracket, Panel Stop1Service part / kit PartsGeek
301A2727Handle , Control Box1Service part / kit PartsGeek
302-21360-Cycle1Service part / kit PartsGeek
302-234.Cycle1Service part / kit PartsGeek
3028448Plate, Mater Face1Service part / kit PartsGeek
302P411~~ Scale Reads 0-200 (1-Phase Use 2)1Service part / kit PartsGeek
302P412Scale Reads 0-2501Service part / kit PartsGeek
302P414Scale Reads 0-500 (1-Phase Use 2)1Service part / kit PartsGeek
302P415Scale Reads 0-750 (I-Phase Use 2)1Service part / kit PartsGeek
302P421Scale Reads 0-3001Service part / kit PartsGeek
302P422Scale Reads 0-6001Service part / kit PartsGeek
302P423Scale Reads 0-750 on side of Gen1Service part / kit PartsGeek
302P465RUNNING-TIME METERS 120-240V (1PH)1Service part / kit PartsGeek
302P466For 220/380-V, 3-Ph, 60-Cycle (Model H)1Service part / kit PartsGeek
302P467For 277/480-V, 3-Ph, 60-Cycle1Service part / kit PartsGeek
302P468For 120/208-V,120/240-V, & 347/600-V 3PH. 50 Cy!. (825-Ohm, 75-Watt)1Service part / kit PartsGeek
302P469For 220/380-V, 3Ph. 50-Cycle1Service part / kit PartsGeek
302P470For 277/480-V, 3-Ph, 50-Cyclo (5-P!)1Service part / kit PartsGeek
303-111Rheostat, Volt. Reg. - 175-Ohm, (Model H)1Service part / kit PartsGeek
303-32Knob, Rheos1Service part / kit PartsGeek
304030545, 000-Ohm, 10-W - For 480-V , 3-Ph, 3-Wire & 277/480-V, 3+ Ph.1Service part / kit PartsGeek
308-22Switch, Volt. & Current Selector Ammeter1Service part / kit PartsGeek FridayParts $47.99
320823-Phase Models1Service part / kit PartsGeek
320B18Single Phase Models1Service part / kit PartsGeek
337A44Strap, Ground1Service part / kit PartsGeek
402-78Rubber, Mtg. - Cont. Box4Service part / kit PartsGeek
960-0134Generator Set Operator's Manual1Service part / kit PartsGeek
CB21Exciter circuit breaker for generator protection1Service part / kit PartsGeek
CR1-CR6Rotating diodes on exciter rotor assembly6Service part / kit PartsGeek
CR21SCR bridge assembly containing diodes CR1-CR3 and SCRs CR4-CR51Service part / kit PartsGeek

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime
Standby
Standby75%117.331.0
Standby100%133.235.2

Available documents

Operator's manual — 955-0301 Onan DFD Operator's andParts Manual (2-1968) (Cummins/Onan)Operator's manual — 960-0120 Onan DFM Operator's Manual (8-1982) (Cummins/Onan)Operator's manual — 960-0127 Onan DFW Operator's Manual (12-1977) (Cummins/Onan)Operator's manual — 960-0310 Onan DFT Operator's and Parts Manual (9-1973) (Cummins/Onan)Parts manual (Cummins/Onan)Parts manual — 0932-0112 Onan Post-Sale Literature Index (07-1998) (Cummins/Onan)Parts manual — 960-0223 Onan DFS Parts Spec A-C (12-1980) (Cummins/Onan)Parts manual — 960-0226 Onan DFV Parts Manual (1-1978) (Cummins/Onan)Parts manual — ONAN 400KW DFN PARTS MANUAL 9600224 (Cummins/Onan)Service manual — 072024 (Cummins/Onan)Service manual — 960-0303 Onan DFT Parts Manual (4-1968) (Cummins/Onan)Service manual — 964-0302 Onan DFQ Operator's and Parts Manual (12-1968)