Service parts for the CFP30E
Grouped by system, with how many of each the parts manual calls for.
Air intake
1 requiredOil system
1 requiredCooling system
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
Ratings spec sheet not in our library yet — see the documents below.
Filters & service parts
model family| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | primary element | AF26124 | Amazon $145.55 eBay $60.00 KuduParts $107.00 | ||
| Fuel filter | Cummins 3308638 | FS1212 | Amazon $49.00 eBay $23.95 FridayParts $59.99 | ||
| Fuel filter | secondary | FF5612 | Amazon $24.99 eBay $22.97 | ||
| Oil filter | LF3970 | Amazon $36.06 eBay $177.58 FridayParts $62.99 | |||
| Battery | Keep clean. Check specific gravity of electrolyte (1.260 fully charged, replace if below 1.215). Check wiring and cable connections for loose, corroded, worn, or damaged cables. Clean terminals with baking soda solution. Check electrolyte level monthly, fill with distilled water if low. Check for continuity and insulation resistance. | — | |||
| Belt | — | ||||
| Coolant | mixture of 50% water and 50% ethylene-glycol base or propylene-glycol antifreeze (or pre-mixed solution) to protect the engine to -37 °C (-34 °F) year-around | 57.0 liters | — | ||
| Coolant filter | Cummins Filtration WF2073 | WF2073 | Amazon $26.99 eBay $14.40 | ||
| Oil | SAE 15W-40 lubricating oil | 12.0 | — |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.
Service intervals
18| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Coolant pump | Inspect | 24 mo | Every two years | |
| Coolant pump/alternator belt | Inspect | 12 mo | Annual | |
| Coolant pump/alternator belt | Replace | 48 mo | Every four years | |
| Coolant thermostat | Replace | 48 mo | Every four years (removal/installation) | |
| Cooling system - heat exchanger | Clean | 24 mo | Drain and flush if contaminated | |
| Cooling system - heat exchanger | Drain | 24 mo | Every two years; drain and flush the cooling system | |
| Drive shaft | Lubricate | 12 mo | Grease universal joint fittings | |
| Electrical components | Inspect | 12 mo | Annual | |
| Electrical components, wiring harness, gauges | Inspect | 12 mo | ||
| Engine oil and filter | Change | 12 mo | Change the oil at least once annually | |
| Engine supports | Inspect | 12 mo | Check torque on support capscrews | |
| Fuel pumps and filters | Inspect | 12 mo | Annual | |
| Heat exchanger | Test | 12 mo | Pressure test | |
| Raw water zinc anode | Inspect | 12 mo | Replace if eroded more than 50% | |
| Turbocharger | Inspect | 12 mo | Annual | |
| Turbocharger mounting nuts | Adjust | 12 mo | Torque to recommended value | |
| Turbocharger mounting nuts | Check | 12 mo | Annual; torque to recommended value | |
| Valve lash | Adjust | 48 mo | Every four years; by a skilled technician |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
60| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Belt tensioner spring case to arm maximum clearance | 3 | mm | |
| Other | Battery specific gravity (fully charged) | 1.260 | ||
| Other | Battery specific gravity (replace threshold) | 1.215 | ||
| Other | Battery specific gravity replacement threshold | 1.215 | below this value replace the battery | |
| Other | Battery specific gravity, fully charged | 1.260 | ||
| Other | Maximum resistance of starting circuit | 0.002 | Ohms | 12V |
| Other | Maximum resistance of starting circuit | 0.004 | Ohms | 24V |
| Other | Pressure sensing line nominal size inside diameter | 1/2 | in. (12.7 mm) | connected between the transducer (located under the FPDP) and the pump discharge flange and the discharge check valve |
| Pressure | Coolant expansion pressure/fill cap minimum pressure | 10 | kPa (15 psi) | |
| Pressure | Cooling loop cooling water pressure limit | 270 | psi | installations where the discharge pressure is greater than 270 psi (pressure reducing valve required upstream of the cooling loop) |
| Pressure | Cooling loop pressure regulator setting | 276 | kPa (40 psi) | |
| Pressure | Cooling loop pressure regulator setting | 345 | kPa (50 psi) | |
| Pressure | Discharge set point pressure / maximum control pressure | 100/110, 170/175, or 240/250 | psi | set by the factory and not adjustable; specify at time of order |
| Pressure | Heat exchanger pressure test | 276 | kPa (40 psi) | air pressure applied; monitor 5 minutes |
| Pressure | Heat exchanger pressure test (applied air) | 276 | kPa | hold 5 minutes, no pressure change |
| Pressure | Maximum cooling water pressure on local gauge | 414 | kPa (60 psi) | |
| Pressure | Minimum oil pressure during test run | 69 | kPa (10 psi) | engine running |
| Pressure | Oil pressure minimum during test run | 69 | kPa | running |
| Pressure | Oil pressure range at rated | 276-414 | kPa | at rated |
| Pressure | Oil pressure range at rated | 40-60 | PSI (276-414 kPa) | at rated |
| Pressure | Raw water working pressure range at heat exchanger | 60 | PSI (413 kPa) MAX | |
| Pressure | VSPLC set point range | 100 to 400 | psi | |
| Pressure | VSPLC transducer pressure offset limit | +/-10 | PSI | resolution 0.1 PSI |
| Resistance | Maximum resistance of starting circuit | 0.001 | Ohms | |
| Speed | Crank termination setpoint | 600 | RPM | factory-set; should not be changed |
| Speed | Minimum crank speed | 100 | RPM | |
| Speed | Minimum crank speed | 110 | RPM | |
| Speed | Minimum crank speed | 120 | RPM | |
| Speed | Minimum crank speed | 125 | RPM | |
| Speed | Minimum crank speed | 130 | RPM | |
| Speed | Minimum crank speed | 150 | RPM | |
| Speed | Operating speed | 1470 | RPM | |
| Speed | Operating speed | 1760 | RPM | |
| Speed | RPM adjustment increment | 10 | RPM | max +/-50 RPM |
| Speed | Typical cranking speed | 120 | RPM | 12V and 24V |
| Speed | Typical cranking speed | 130 | RPM | 12V and 24V |
| Temperature | Coolant temperature alarm (TB-5) | 100 | °C | high engine temperature |
| Temperature | Coolant temperature for oil change | 70 | C (158 F) | before shutting off engine |
| Temperature | Coolant temperature operating range | 70-107 | C (158-225 F) | test run check |
| Temperature | Cooling system leak test temperature | 82 | C (180 F) | operate engine until reached |
| Temperature | Engine coolant heater minimum temperature | 49 | °C | 24 h after shutdown |
| Temperature | Engine coolant heater temperature | 49 | C (120 F) | or above |
| Temperature | Low engine temperature signal (TB-312) | 37.8 | °C | |
| Temperature | Maximum fuel temperature at lift pump inlet | 160 | F (71 C) | |
| Temperature | Maximum temperature rise between ambient air and engine air inlet | 30 | F (16.7 C) | |
| Temperature | Normal operating temperature | 180-212 | F (82-100 C) | |
| Temperature | Normal operating temperature | 82-100 | °C | |
| Temperature | Standard thermostat range | 180-203 | F (82-95 C) | modulating |
| Torque | 1/2 in. pipe plug into cast iron | 55 | N-m | |
| Torque | 1/2-13 SAE grade 5 cap screw into cast iron | 95 | N-m | |
| Torque | 1/4 in. pipe plug into cast iron | 25 | N-m | |
| Torque | 1/8 in. pipe plug into cast iron | 20 | N-m | |
| Torque | 3/4-10 SAE grade 5 cap screw into cast iron | 325 | N-m | |
| Torque | 3/8-16 SAE grade 5 cap screw into cast iron | 40 | N-m | |
| Torque | 5/16-18 SAE grade 5 cap screw into cast iron | 20 | N-m | |
| Torque | M10 class 8.8 cap screw into cast iron | 45 | N-m | |
| Torque | M12 class 8.8 cap screw into cast iron | 80 | N-m | |
| Torque | M16 class 8.8 cap screw into cast iron | 195 | N-m | |
| Torque | M8 class 8.8 cap screw into cast iron | 23 | N-m | |
| Torque | Metric cap screw, M10 | 45 | N-m (33 ft-lb) | Class 8.8 cast iron, lubricated threads |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | Ethylene-Glycol 40% = -23 C (-10 F); 50% = -37 C (-34 F); 60% = -54 C (-65 F); 68% = -71 C (-96 F) | above -71°C | Freeze protection chart | ||
| Coolant | Propylene-Glycol 40% = -21 C (-6 F); 50% = -33 C (-27 F); 60% = -54 C (-65 F); 68% = -63 C (-82 F) | above -63°C | Freeze protection chart | ||
| Coolant | 50% ethylene glycol antifreeze and 50% water | Fleetguard ES COMPLEAT EG or Fleetguard PG Plus | above -37°C | 22.3 L (engine only) | Use 50% concentration (40% to 60% range) with SCA required for wet-sleeved engines. Antifreeze at 68% provides maximum freeze protection and must never be exceeded. Use soft or distilled water not exceeding 300 ppm hardness. |
| Coolant | 50% ethylene-glycol / 50% water | Fleetguard ES COMPLEAT EG or Fleetguard PG Plus | above -37°C | 12.3 L | Antifreeze concentration chart: 40%=-23C, 50%=-37C, 60%=-54C, 68%=-71C; never exceed 68% |
| Engine oil | 15W-40 | Premium Blue or equivalent | Cummins recommends Premium Blue 15W-40 oil for most climates. Do not use special break-in oils. Oil capacity of pan (high-low) 20-16 qt (18.9-15.1 L); total system capacity 6.3 gal (23.8 L). | ||
| Fuel | No. 2 diesel | ASTM no. 2D | Do not use copper or galvanized pipe for supply/return lines | ||
| Fuel | No. 2 diesel (ASTM no. 2D) | ASTM no. 2 diesel fuel specifications | Use ONLY no. 2 diesel fuel. Do not mix gasoline, alcohol, gasohol, ethanol, or methanol with diesel fuel. | ||
| Grease | NLGI #2 lithium complex | Good quality semi-synthetic, molybdenum-fortified | -47°C to 204°C | For drive shaft universal joint grease fittings; protects from -47 to 204 C (-54 to 400 F). |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
26| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 111 | Engine Control Module Critical Internal Failure | Engine Control Module Critical Internal Failure - Bad Intelligent Device or Component | Shutdown | |
| 1117 | Power Lost With Ignition On | Power Lost With Ignition On - Data Erratic, Intermittent, or Incorrect | ||
| 115 | Engine Speed/Position Sensor Circuit | Engine Speed/Position Sensor Circuit - lost both of two signals from the magnetic pickup sensor - Data Erratic | Shutdown | |
| 122 | Intake Manifold Pressure Sensor Circuit | Intake Manifold Pressure Sensor Circuit - Voltage Above Normal, or Shorted to High Source | Warning | |
| 123 | Intake Manifold Pressure Sensor Circuit | Intake Manifold Pressure Sensor Circuit - Voltage Below Normal, or Shorted to Low Source | Warning | |
| 135 | Oil Pressure Sensor Circuit | Oil Pressure Sensor Circuit - Voltage Above Normal, or Shorted to High Source | Warning | |
| 141 | Oil Pressure Sensor Circuit | Oil Pressure Sensor Circuit - Voltage Below Normal, or Shorted to Low Source | Warning | |
| 143 | Oil Pressure Low | Oil Pressure Low - Data Valid But Below Normal Operational Range - Moderately Severe Level | Warning | |
| 144 | Coolant Temperature Sensor Circuit | Coolant Temperature Sensor Circuit - Voltage Above Normal or Shorted to High Source | Warning | |
| 145 | Coolant Temperature Sensor Circuit | Coolant Temperature Sensor Circuit - Voltage Below Normal or Shorted to Low Source | Warning | |
| 146 | Coolant Temperature High | Coolant Temperature High - Data Valid But Above Normal Operational Range - Moderately Severe Level | Warning | |
| 151 | Coolant Temperature Low | Coolant Temperature Low - Data Valid But Above Normal Operational Range - Most Severe Level | Shutdown | |
| 221 | Barometric Pressure Sensor Circuit | Barometric Pressure Sensor Circuit - Voltage Above Normal, or Shorted to High Source | Warning | |
| 234 | Engine Speed High | Engine Speed High - Data Valid But Above Normal Operational Range - Most Severe Level | Shutdown | |
| 235 | Coolant Level Low | Coolant Level Low - Data Valid But Below Normal Operational Range - Most Severe Level | Shutdown | |
| 415 | Oil Pressure Low | Oil Pressure Low - Data Valid But Below Normal Operational Range - Most Severe Level | Shutdown | |
| 418 | Water in Fuel Indicator High | Water in Fuel Indicator High - Data Valid But Above Normal Operational Range - Least Severe Level | Warning | |
| 441 | Auxiliary Temperature Sensor Input #1 | Auxiliary Temperature Sensor Input #1 - Special Instructions | Shutdown | |
| 442 | Auxiliary Pressure Sensor Input #1 | Auxiliary Pressure Sensor Input #1 - Special Instructions | Shutdown | |
| 451 | Injector Solenoid Cylinder #1 Circuit | Injector Solenoid Cylinder #1 Circuit - Current Below Normal, or Open Circuit | Warning | |
| 452 | Injector Solenoid Cylinder #5 Circuit | Injector Solenoid Cylinder #5 Circuit - Current Below Normal, or Open Circuit | Warning | |
| 453 | Injector Solenoid Cylinder #3 Circuit | Injector Solenoid Cylinder #3 Circuit - Current Below Normal, or Open Circuit | Warning | |
| 561 | Injector Solenoid Cylinder #5 | Injector Cylinder #5 - Mechanical System Not Responding Properly or Out Of Adjustment | Warning | |
| 689 | ECM Program Memory (RAM) Corruption | ECM Program Memory (RAM) Corruption - Condition Exists | Warning | |
| 731 | Starter Relay Circuit | Starter Relay Circuit - Voltage Above Normal, or Shorted to High Source | Warning | |
| 755 | ECM Data Lost | Electronic Control Module data lost - Condition Exists | Warning |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Engine speed adjustment (CFP83 F-10, F-20, F-30) adjustment
⚠ The maximum engine speed should only be altered by a Cummins technician.
- Start the engine.
- Observe that the engine accelerates to the currently adjusted speed setpoint.
- Locate the threaded linkage rod on the fuel pump side of the engine.
- Loosen the locking nuts against the stops on the threaded rod.
- To increase speed, turn the bolt on the right side of the throttle bracket clockwise.
- To decrease speed, turn the bolt counter-clockwise.
- When the rated speed is correct, tighten the locking nut against the stop.
- Adjust the left-side threaded bolt for maximum speed if needed.
- Stop the engine and repeat until the desired speed is attained.
Heat exchanger pressure test diagnostic
⚠ Use Teflon tape or pipe sealant when installing test setup.
Tools: pressure gauge 689 kPa (100 psi)
- Install an adapter at the cooling water outlet of the heat exchanger.
- Install a pressure test setup with 689 kPa (100 psi) gauge at the cooling water inlet.
- Apply air pressure at 276 kPa (40 psi).
- Isolate pressure source and monitor gauge for five minutes.
- Release pressure and remove test equipment.
Overspeed test diagnostic
- From the User Interface screen press the MENU soft key.
- Press the OVERSPEED TEST soft key from the Settings Menu.
- Press the RUN soft button.
- When the dialog box appears, proceed with the test and select Yes.
- When the timer expires, ENGINE OVERSPEED flashing in red appears at the top of the FPDP screen.
- The engine will enter MANUAL mode until reset.
- Press the RESET/STOP switch on the FPDP to reset the fire pump drive engine.
Terminal block test diagnostic
Tools: Digital multimeter
- From the User Interface screen press the MENU soft key.
- Press the ENGINE SETUP soft key from the Settings menu.
- Enter password 806 in the Engine Setup Login screen.
- Press the TERMINAL BLOCKS soft key from the Engine Setup menu.
- Press the soft key corresponding to the terminal block requiring verification.
- Press the RETURN soft key to exit the Terminal Block Test menu.
Battery installation installation
⚠ Battery electrolyte (sulfuric acid) is highly caustic.
⚠ Batteries can emit explosive gases during charging.
⚠ Remove the negative (-) battery cable first and attach it last.
Tools: Neoprene gloves, Safety goggles or full face shield
- Install the battery cable kit or equivalent customer-supplied wiring.
- Install battery sets in a well-ventilated or otherwise protected location.
- Provide adequate room for servicing or replacing the batteries.
- Locate the batteries near the engine or increase conductor size as required.
- Check the battery cables and connections.
- Coat the terminals with petroleum jelly to prevent corrosion.
Cooling water supply installation installation
⚠ The cooling water supply must be immediately available when the engine is started.
⚠ Do not operate without a pressure cap.
Tools: Appropriate-sized container
- Provide a cooling water discharge line at the heat exchanger outlet and a supply line to the cooling water inlet.
- Check the pressure regulator setting on the cooling loop with water flowing through the heat exchanger.
- Adjust the cooling water based on water flow rather than water pressure.
- Measure the water flow using a container and elapsed time.
- Adjust both pressure regulators to provide flow at or above specifications.
Drive shaft installation installation
⚠ Do not use the engine lifting points for assembly!
Tools: Lifting device, Grease gun
- Ensure the engine and pump are correctly aligned.
- Verify engine position centered on frame side to side within +/- .76 mm (.03 in).
- Align engine center line to pump center line within +/- .76 mm (.03 in).
- Ensure pump center line to engine crankshaft center line (vertical) is 2 degrees +/- 1 degree.
- Ensure drive shaft mounting flanges are parallel.
- Lubricate the grease fittings on the drive shaft universal joint.
- Check engine is installed per pump manufacturer's specifications.
Fuel supply installation installation
⚠ Do not use copper or galvanized pipe for the fuel return or supply lines.
⚠ Do not mix gasoline, alcohol, gasohol, ethanol, or methanol with diesel fuel.
Tools: Container for contaminated fuel
- Install an elevated no. 2 diesel fuel tank or equivalent compatible with ASTM no. 2 diesel specifications.
- Size the fuel tank for the maximum expected full-load operation period.
- Install a fuel return line routed to the bottom of the fuel tank.
- Install a fuel supply line to the fire pump drive engine.
- Open the fuel filter/water separator drain and drain until no water is present.
Coolant pump/alternator belt inspection maintenance
⚠ Disconnect batteries (negative cable first) before service.
Tools: Cummins belt tension gauge 3822524
- Place engine in MANUAL and disconnect both batteries (negative first).
- Remove belt guard capscrews and belt guard.
- Visually inspect belt for frayed, worn, missing pieces or intersecting cracks.
- Check belt tension using Cummins belt tension gauge 3822524 at center span.
- Reinstall battery cables (negative last).
Coolant system preparation maintenance
⚠ Do not remove the pressure/fill cap from a hot engine. Wait until coolant temperature is below 50 C (122 F).
Tools: Refractometer
- Inspect the engine coolant hoses and hose clamps for proper installation and water tightness.
- Ensure the engine coolant heater maintains coolant temperature of 49 C (120 F) or above.
- Ensure coolant is present in the coolant heater before plugging into a dedicated circuit.
- Inspect the heat exchanger weekly for external damage and contamination.
- Add coolant if necessary: with sight gauge, keep level visible at center; without, fill to bottom of fill neck.
- Re-install the pressure/fill cap.
Cooling system drain and flush maintenance
⚠ Do not remove pressure cap from hot engine; wait until below 50 C (120 F).
⚠ Coolant is toxic - dispose per regulations.
Tools: filter wrench, container (57 L)
- Disconnect both batteries (negative first).
- Remove coolant expansion tank pressure/fill cap.
- Disconnect engine coolant heater power supply.
- Place container (min 57 L) under coolant drain valve.
- Open the drain petcock and drain coolant; drain engine heater.
- Flush with clean fresh water or heat exchanger cleaner.
- Install new coolant filter if needed.
- Fill with 50/50 antifreeze mixture and vent air.
- Operate engine to 82 C (180 F) and check for leaks.
Cooling system drain and flush (heat exchanger) maintenance
⚠ Coolant is toxic. Avoid prolonged and repeated skin contact with used antifreeze.
⚠ Never use a sealing additive to stop leaks in the cooling system.
Tools: Container (at least 57 liters/15 gallons), Filter wrench
- Disconnect both batteries at their terminals; remove the negative (-) cable first.
- Press down, unscrew, and remove the coolant expansion tank pressure/fill cap.
- Disconnect the engine coolant heater power supply before draining.
- Place a container holding at least 57 liters (15 gallons) under the coolant drain valve.
- Ensure the coolant filter shut-off valves are OPEN.
- Open the drain petcock on the lower coolant tube and drain the coolant.
- Move the container under the engine coolant heater, disconnect a heater coolant hose, and drain the heater.
- Flush with clean fresh water or heavy-duty heat exchanger cleaner.
- Remove the water coolant filter with a filter wrench, clean the housing, coat the new gasket with 15W-40 oil, and install; tighten an additional 1/4 turn.
- Reconnect the heater coolant hose and close the drain petcock.
- Fill the coolant tanks with 50% water and 50% ethylene-glycol or propylene-glycol antifreeze.
- Check the pressure/fill cap condition and re-install.
- Re-install the heater wiring.
- Reinstall the battery cables; attach the negative (-) battery cable last.
- Operate the engine until it reaches 82 C (180 F) and check for coolant leaks.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What oil filter fits the Cummins/Onan CFP30E?
The Cummins/Onan CFP30E uses oil filter part number LF3970.
Which fuel filter part number does the Cummins/Onan CFP30E take?
The Cummins/Onan CFP30E uses fuel filter part numbers FS1212, FF5612.
What air filter fits the Cummins/Onan CFP30E?
The Cummins/Onan CFP30E uses air filter part number AF26124.
Parts
47model family| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 12865 | SWITCH, PROXIMITY, 2M CABLE, 12-24V | 1 | Sensor | Amazon eBay |
| 13769 | WASHER, PRESSURE SEALING WASHER | 1 | Gasket | Amazon eBay |
| 15155 | DPEM | ECM / ECU | Amazon eBay | |
| 3822524 | Use on v-belts ( 3/8 to 7/8) and v-ribbed belts with 5 ribs or less. | 1 | Belt | Amazon eBay |
| A042B473 | Kit, Fuel Lines CFP59 F15-25 and CFP83 | Hose | eBay | |
| A042E858 | Assembly, Sensors and Harnessing CFP83 | Sensor | eBay | |
| A042G207 | INTAKE MANIFOLD TEMP / PRESSURE | Sensor | Amazon eBay | |
| A042H306 | Harness to pump controller | Pump | eBay | |
| A042H681 | Assembly, Fire Pump, CFP83 F10-F30 | Pump | eBay | |
| A042J117 | ECM POWER BOARD | ECM / ECU | Amazon eBay | |
| A042J657 | General Arrangement, Installation, Fire Pump, CFP83 | Pump | eBay | |
| AF26124 | Air cleaner element - heavy duty primary element (optional) | Air filter | Amazon $145.55 eBay $60.00 KuduParts $107.00 | |
| AF26125 | Air cleaner element - heavy duty secondary element (optional) | Air filter | Amazon $268.00 eBay $39.99 | |
| AH1107 | Recommended air cleaner element (standard) | Air filter | Amazon $128.00 eBay $94.73 KuduParts $60.00 | |
| AH1196 | Recommended air cleaner element - standard (Cummins Filtration) | Air filter | Amazon $76.93 eBay $141.60 KuduParts $96.00 | |
| FF5612 | Fleetguard (Cummins) fuel filter, primary fuel filter location | Fuel filter | Amazon $24.99 eBay $22.97 | |
| FS1212 | Fuel/Water Sep Spin-On | 1 | Fuel filter | Amazon $49.00 eBay $23.95 FridayParts $59.99 |
| FS1251 | Fuel Filter | 1 | Fuel filter | Amazon $34.99 eBay $119.92 |
| LF3970 | Cummins part #3937736 | 1 | Oil filter | Amazon $36.06 eBay $177.58 FridayParts $62.99 |
| LF9009 | Lube Filter | 1 | Oil filter | Amazon $47.99 eBay $110.91 FridayParts $125.00 |
| WF2073 | Coolant Filter | 1 | Coolant filter | Amazon $26.99 eBay $14.40 |
| 13852 | ASSEMBLY, MODIFIED VALVE COVER, CFP_5E | 1 | Service part / kit | Amazon eBay FridayParts $57.98 |
| 17641 | Assembly, Heat Exchanger CFP83, Sea Water | Service part / kit | eBay | |
| 18485 | DPEM | Service part / kit | Amazon eBay | |
| 18487 | POWER BOARD | Service part / kit | Amazon eBay | |
| 18488 | POWER BOARD | Service part / kit | Amazon eBay | |
| 21249 | Assembly, Control Panel Mounting | Service part / kit | eBay | |
| 26288 | Handle, front hood access | 1 | Service part / kit | Amazon eBay |
| 8738-24 | Assembly, Engine, CFP83, 24V | Service part / kit | eBay | |
| 8824-12 | Battery Contactors 12V | Service part / kit | eBay | |
| 8824-24 | Battery Contactors 24V | Service part / kit | eBay | |
| A042A409 | Misc. Piping, Cooling Loop, Sea Water CFP83 | Service part / kit | eBay | |
| A042C868 | Battery Isolator | Service part / kit | Amazon eBay | |
| A042G184 | Assembly, Panel, Digital Mechanical | Service part / kit | eBay | |
| A042H289 | Service part / kit | Amazon eBay | ||
| A042H290 | HARNESS | Service part / kit | Amazon eBay | |
| A042H292 | Service part / kit | Amazon eBay | ||
| A042H724 | Assembly, Raw Water Cooling Loop, 3/4 in. Vertical | Service part / kit | eBay | |
| A042H725 | Assembly, Raw Water Cooling Loop, 3/4 in. Horizontal 12V | Service part / kit | eBay | |
| A042H726 | Assembly, Raw Water Cooling Loop, 3/4 in. Horizontal 24V | Service part / kit | eBay | |
| A042H727 | Assembly, Sea Water Cooling Loop, 3/4 in. Vertical | Service part / kit | eBay | |
| A042H728 | Assembly, Sea Water Cooling Loop, 3/4 in. Horizontal 12V | Service part / kit | eBay | |
| A042H729 | Assembly, Sea Water Cooling Loop, 3/4 in. Horizontal 24V | Service part / kit | eBay | |
| A042J017 | Assembly, Air Intake CFP83 | Service part / kit | eBay | |
| A042J120 | Schematic, Overall CFP83, GEN II FPDP | Service part / kit | eBay | |
| A042J131 | Service part / kit | Amazon eBay | ||
| A042J856 | Assembly, Coolant Heater CFP83 | Service part / kit | eBay |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.