Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 200 kW |
| Standby kVA | 250 |
| Emissions | EPA Tier 3 Nonroad Standards |
| Controller | EMCP 4.2 |
| Oil capacity | 39.0 L |
| Alternator | Caterpillar LC5014F (4-pole, Class H insulation) |
| Voltage options | 480 V |
| Power factor | 0.8 |
| Coolant capacity | 46.7 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 2870×1622×2065 mm |
| Dry weight | 2021 kg |
Engine
| Oil capacity | 39.0 L |
|---|---|
| Coolant capacity | 46.7 L |
| Displacement | 8.8 L |
| Aspiration | Air-to-air aftercooled |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the Caterpillar C9 ATAAC?
The Caterpillar C9 ATAAC is rated 200 kW standby (250.0 kVA).
What engine does the Caterpillar C9 ATAAC use?
The Caterpillar C9 ATAAC is powered by the Caterpillar C9 ATAAC engine.
What fuel does the Caterpillar C9 ATAAC use?
The Caterpillar C9 ATAAC runs on Diesel.
What is the oil capacity of the Caterpillar C9 ATAAC?
The Caterpillar C9 ATAAC engine in the Caterpillar C9 ATAAC has an oil capacity of 39.0 liters.
What alternator does the Caterpillar C9 ATAAC use?
The Caterpillar C9 ATAAC uses a Caterpillar LC5014F alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 50% | 34.9 | 9.2 |
| Standby | 75% | 46.6 | 12.3 |
| Standby | 100% | 58.2 | 15.4 |