Specifications
| Fuel | diesel |
|---|---|
| Frequency | 50.0 Hz |
| Prime power | 2600 kW |
| Emissions | NC |
| Oil capacity | 626.0 L |
| Alternator | Generator weight approx 11340 kg |
| Phase | three |
| Power factor | 0.8 |
| Dimensions (L×W×H) | 4511×1961×3937 mm |
| Dry weight | 19000 kg |
Engine
| Oil capacity | 626.0 L |
|---|---|
| Coolant capacity | 721.0 L |
| Displacement | 148.0 L |
| Aspiration | TA |
| Rated speed | 900 rpm |
Maintenance & consumables
for the Caterpillar C280-8| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | dual element | — | |||
| Fuel filter | — | ||||
| Oil filter | — |
Service intervals
1| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Lube oil (deep sump oil pan) | Change | 1000 hr | Deep sump oil pan — 1000 hour |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
29| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Air cleaner inlet temperature, maximum | 60 | °C | |
| Other | Compression Ratio | 13:1 | ||
| Other | Gross Input Torque (TH55-E70) | 12 667 | N•m (9350 lb-ft) | |
| Other | Gross Input Torque (TH55-E90) | 12 677 | N•m (9350 lb-ft) | |
| Other | Rated altitude @ 25°C | 150 | m | 25°C |
| Other | Rating condition (diesel 7 L and higher) | 99 kPa (29.31 in Hg) dry barometer, 25°C (77°F) | SAE J1995 inlet air standard | |
| Other | Rating condition (diesel up to 6.6 L) | 100 kPa (29.5 in Hg) total barometric pressure, 1 kPa (.295 in Hg) vapor pressure, 25°C (77°F) | ISO/TR14396 inlet air standard | |
| Other | Rating condition (gas) | 100 kPa (29.61 in Hg) and 25°C (77°F) | SAE J1349 standard | |
| Other | Rotation (from flywheel end) | Counterclockwise | ||
| Other | SCAC flow rate | 200-230 | gpm | ambient 30°C (86°F) |
| Other | Stall Torque Ratio (TH55-E70) | 2.23 | ||
| Other | Stall Torque Ratio (TH55-E90) | 2.23 | ||
| Pressure | BMEP @ 100% Load | 2201 | kPa | @100% load |
| Pressure | Firing pressure, maximum | 17300 | kPa | |
| Pressure | WS255 pump plunger load | 238,000 | lb (107,960 kg) | |
| Pressure | WS273XD pump plunger load | 275,000 | lb (124 738 kg) | |
| Pressure | WS305XD pump plunger load | 250,000 | lb (113 398 kg) | |
| Speed | Low Idle Speed | 350 | rpm | |
| Speed | Maximum Input Speed (TH55-E70/TH55-E90 transmissions) | 1970 | rpm | |
| Speed | Mean Piston Speed | 10 | m/s | @100% load |
| Speed | Mean piston speed | 9 | m/s | |
| Speed | Rated Input Speed (TH55-E70/TH55-E90 transmissions) | 1900 | rpm | |
| Speed | Rated Speed | 1000 | rpm | Marine MCR |
| Speed | Rated speed | 900 | rpm | |
| Temperature | Aftercooler Water | 60 | C | |
| Temperature | Aftercooler water | 32 | °C | |
| Temperature | Jacket Water Outlet | 90 | C | |
| Temperature | SCAC cooling water to aftercooler inlet | 32 | °C | |
| Temperature | SCAC thermostat setting (aftercooler coolant minimum) | 30 | °C |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | Cat DEAC | Diesel; 3,000 Service Hours or Three Years; annual S·O·SSM Level 2 coolant sampling and analysis | |||
| Coolant | Cat ELC | Diesel; 12,000 Service Hours or Six Years; add Cat ELC Extender at 6,000 service hours or one half of service life; annual S·O·SSM Level 2 coolant sampling and analysis | |||
| Coolant | Cat NGEC | Natural Gas; 16,000 Service Hours or Three Years; use interval that occurs first | |||
| Engine oil | EPA 2D 89.330-96 (fuel reference, Diesel <6.6 L, density 0,845-0,850 kg/L a 15 °C) | Reference condition only, not a lubricant recommendation | |||
| Engine oil | Cat NGEO | Natural Gas | |||
| Engine oil | Cat Arctic DEO SYN SAE 0W-30 | -40°C to 30°C | Engine Crankcase; Industrial Engines | ||
| Engine oil | Cat DEO SYN SAE 5W-40 | -30°C to 50°C | Engine Crankcase; Industrial Engines | ||
| Engine oil | Cat DEO SAE 10W-30 | -18°C to 40°C | Engine Crankcase; Industrial Engines | ||
| Engine oil | Cat DEO SAE 15W-40 | -9°C to 50°C | Engine Crankcase; Industrial Engines | ||
| Fuel | 35° API, LHV 42 780 kJ/kg (18,390 Btu/lb), density 838,9 g/L (Diesel ≥7 L rating condition) | Reference fuel for Diesel rating conditions | |||
| Fuel | 35° API gravity at 60°F (16°C) | LHV 18,390 Btu/lb (42 780 kJ/kg) | Fuel at 85°F (29°C) weighing 7.001 lbs/U.S. gal (838.9 g/liter) | ||
| Fuel | 35° API gravity, LHV 42 780 kJ/kg (18,390 btu/lb) | SAE J1995 | Diesel engines 7 liter and higher; used at 29°C (84.2°F) with density 838.9 g/L | ||
| Fuel | Distillate | 35 API | Engine operates on MDO; lower heating value 42,780 kJ/kg; density 838.9 g/liter | ||
| Fuel | EPA 2D 89.330-96 | EPA 2D 89.330-96 | Diesel engines up to 6.6 liter; density 0.845-0.850 kg/L @ 15°C (59°F); fuel inlet temperature 40°C (104°F) | ||
| Fuel | MDO / Distillate, 35 API gravity | Lower heating value 42,780 kJ/kg; used at 29 C with density 838.9 g/liter | |||
| Fuel | dry natural gas, LHV 35.54 MJ/Nm3 (905 btu/ft3) | Gas ratings based on SAE J1349 standard conditions of 100 kPa (29.61 in Hg) and 25°C (77°F) | |||
| Grease | Cat Generator Set Grease | Part Number 108-8611 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What engine is in the Caterpillar C280-8?
The Caterpillar C280-8 is powered by the Caterpillar C280-8 engine.
What kind of fuel does the Caterpillar C280-8 run on?
The Caterpillar C280-8 runs on diesel.
What is the oil capacity of the Caterpillar C280-8?
The Caterpillar C280-8 engine in the Caterpillar C280-8 has an oil capacity of 626.0 liters.
What is the coolant capacity of the Caterpillar C280-8?
The Caterpillar C280-8 cooling system holds 721 liters (190.5 US gallons) for the engine, per the manufacturer specification sheet.
How much does the Caterpillar C280-8 weigh?
The Caterpillar C280-8 has a dry weight of 19000 kg (41887 lb).
Which alternator is fitted to the Caterpillar C280-8?
The Caterpillar C280-8 uses a Generator weight approx 11340 kg alternator.
Parts
58model familyCompiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 100% | 4.54 | 1.2 |
Available documents
This page was generated from the 11 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.