Home›Fault codes›Leroy-Somer

Leroy-Somer Fault Codes

58 Leroy-Somer generator fault/alarm codes with symptom, cause and remedy — compiled from Leroy-Somer service and controller documentation.

Fault / alarm codes

58
CodeMeaning / symptomCauseRemedy Models affected
00-1Generator set emergency stopLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
01-1External emergency stopLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
02-1Engine oil pressureLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
03-1Engine water temperatureLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
04-1Daily fuel tank level lowLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
05-1Radiator water level lowLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
06-1Alternator overload or short-circuitLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
07-1Engine overspeedLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
08-1Max. battery voltageLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
09-1Max. alternator voltageLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
12-1Max. alternator frequencyLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
25-0Normal contactor open (system side)Leroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
26-0Emergency contactor open (generating set side)Leroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
27-1Oil temperatureLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
28-1Oil level lowLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
34-1Battery charger faultLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
46-1Main circuit breaker openLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
47-0OverloadLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
AC.LtDrive is in current limitSee Menu 10 in the Digidrive SK Advanced User GuideLeroy-Somer Digidrive SK Size 2 to 6
br.rSBraking resistor overloadSee Menu 10 in the Digidrive SK Advanced User GuideLeroy-Somer Digidrive SK Size 2 to 6
C.AccSmartStick read/write failBad connection or faulty SmartStickLeroy-Somer Digidrive SK Size 2 to 6
C.dAtSmartStick data does not existNew/empty SmartStick being readReset the drive.Leroy-Somer Digidrive SK Size 2 to 6
C.ErrSmartStick data errorBad connection or memory corrupt within SmartStickLeroy-Somer Digidrive SK Size 2 to 6
C.rtgSmartStick/drive rating changeAlready programmed SmartStick read by a drive of a different ratingLeroy-Somer Digidrive SK Size 2 to 6
cL1Analog input 1 current mode, current loss — Input current less than 3mA when 4-20 or 20-4mA modes selectedLeroy-Somer Digidrive SK Size 2 to 6
EEFInternal drive EEPROM trip — Possible loss of parameter valuesSet default parameters (see Pr 29 on page 59)Leroy-Somer Digidrive SK Size 2 to 6
FAILFailed attempt to read stickAn attempt was made to read the stick when the drive was not disabled or tripped, or the stick is read onlyLeroy-Somer Digidrive SK Size 2 to 6
FdLField loss conditionLeroy-Somer FXMP25
HF06Unexpected interruptHardware fault - return to supplierLeroy-Somer FXMP25
HF07Watchdog failureHardware fault - return to supplierLeroy-Somer FXMP25
HF08Interrupt clashHardware fault - return to supplierLeroy-Somer FXMP25
HF11Access to the EEPROM failedHardware fault - return to supplierLeroy-Somer FXMP25
HF17No comms from power processorHardware fault - return to supplierLeroy-Somer FXMP25
HF19Flash failureHardware fault - return to supplierLeroy-Somer FXMP25
HF21Power processor - Watchdog failureHardware fault - return to supplierLeroy-Somer FXMP25
HF22Power processor - Unexpected interruptHardware fault - return to supplierLeroy-Somer FXMP25
HF23Power processor - Level overrunHardware fault - return to supplierLeroy-Somer FXMP25
HF24Power processor - No frequency at power upHardware fault - return to supplierLeroy-Somer FXMP25
HF29Fan faultHardware fault - return to supplierLeroy-Somer FXMP25
HFxxHardware faultsInternal drive hardware fault (see Digidrive SK Advanced User Guide)Leroy-Somer Digidrive SK Size 2 to 6
hotHeatsink/IGBT temperature highReduce ambient temperature or reduce motor currentLeroy-Somer Digidrive SK Size 2 to 6
It.ACI2t on drive output currentExcessive mechanical load High impedance phase to phase or phase to ground short circuit at drive outputDrive requires re-autotuning to motorLeroy-Somer Digidrive SK Size 2 to 6
It.brI2t on braking resistorExcessive braking resistor energyLeroy-Somer Digidrive SK Size 2 to 6
Motor thermistor tripExcessive motor temperatureLeroy-Somer Digidrive SK Size 2 to 6
O.cLOverload on current loop inputInput current exceeds 25mALeroy-Somer Digidrive SK Size 2 to 6
O.ht1FXMP5 overheat (SCR junction) based on thermal modelReduce ambient temperature or field current. Check the fans are operating and venting is not blocked.Leroy-Somer FXMP25
O.ht1IGBT over heat based on drives thermal modelOverheat software thermal modelLeroy-Somer Digidrive SK Size 2 to 6
O.ht2Heatsink over temperatureReduce ambient temperature or field current. Check the fans are operating and venting is not blocked.Leroy-Somer FXMP25
O.ht2Over heat based on drives heatsinkHeatsink temperature exceeds allowable maximumLeroy-Somer Digidrive SK Size 2 to 6
O.ht3Drive over-heat based on driveLeroy-Somer Digidrive SK Size 2 to 6
O.ht4Power module rectifier over temperature. — Power module rectifier temperature exceeds allowable maximumLeroy-Somer Digidrive SK Size 2 to 6
O.SPdOver speedExcessive motor speed (typically caused by mechanical load driving the motor)Leroy-Somer Digidrive SK Size 2 to 6
Oil pressure fault/shutdownRed LED onLeroy-Somer LSA 46.2, Leroy-Somer LSA 47.1
OVDC bus over voltageDeceleration rate set too fast for the inertia of the machine. Mechanical load driving the motorLeroy-Somer Digidrive SK Size 2 to 6
OVL.dI x t overload (I = current, t = time)Reduce motor current (Load)Leroy-Somer Digidrive SK Size 2 to 6
PHInput phase imbalance or input phase loss — One of the input phases has become disconnected from the drive (not dual rated drives)Leroy-Somer Digidrive SK Size 2 to 6
rSFailure to measure motors stator resistanceMotor too small for drive; Motor cable disconnected during measurementLeroy-Somer Digidrive SK Size 2 to 6
SCLSerial communications loss time-out — Loss of communication when drive is under remote controlLeroy-Somer Digidrive SK Size 2 to 6
tunEAutotune stopped before completionRun command removed before autotune completeLeroy-Somer Digidrive SK Size 2 to 6
UVDC bus under voltageLow AC supply voltage Low DC bus voltage when supplied by an external DC power supplyLeroy-Somer Digidrive SK Size 2 to 6

Compiled from Leroy-Somer service manuals and controller documentation. 2 code numbers mean different things on different controllers; each meaning is listed with the models it applies to. Cause/remedy shown where extracted; always verify against the manual for your exact model.

Common questions

What does Leroy-Somer fault code AC.Lt mean?

Drive is in current limit. Remedy: See Menu 10 in the Digidrive SK Advanced User Guide.

What does Leroy-Somer fault code br.rS mean?

Braking resistor overload. Remedy: See Menu 10 in the Digidrive SK Advanced User Guide.