Home›Engines›Onan Modified Ford In-line 4

Onan Modified Ford In-line 4 Engine

The Onan Modified Ford In-line 4 is an engine. It powers generator sets from Cummins/Onan, including the GGDB. It holds 4.5 L (1.2 gal) of oil.

Also known as: Onan Modified Ford In-line 4

4.5 L
Oil capacity

Engine specifications

Oil capacity4.5 L

Generator sets powered by this engine

1
Cummins/Onan GGDB

Common problems

15
  • The engine lacks power or is unstable — Engine misfires on LPG or NG or backfires on LPG at high loads
    Cause: Engine misfires on LPG or NG or backfires on LPG at high loads.
    Fix: Air fuel ratio too lean. Adjust main fuel valve. Refer to Gaseous Fuel Adjustment in Section 8; Inspect spark plugs/gap (0.044"); Check spark plug wires (6,000 ohms/foot); Check ignition coil primary (0.5 to 1.3 ohms); LPG liquid withdrawal - defective LPL converter.
  • The engine lacks power or is unstable — LPG liquid converter frosts
    Cause: LPG liquid converter frosts.
    Fix: Low coolant. Fill cooling system; Air in cooling system. Bleed cooling system.
  • Engine shuts down within 1 to 5 seconds
    Cause: S7 low coolant level switch (optional) may not be operating properly
    Fix: Check S7 low coolant level switch (optional) for proper operation.
  • Engine shuts down due to any of the four faults but no signal is supplied to remote monitor device from Dry Contact Module (DCM)
    Cause: Engine Relay (K8) function on DCM
    Fix: Check Engine Relay (K8) function on DCM.
  • The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run. FAULT 1
    Cause: The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay.
  • The engine lacks power or is unstable — Engine has preignition on LPG at high loads
    Cause: Engine has preignition on LPG at high loads.
    Fix: Check ignition timing, refer to Section 8.
  • The engine lacks power or is unstable — (Begin Spec D) Manifold absolute pressure sensor (MAP) is not functioning properly
    Cause: (Begin Spec D) Manifold absolute pressure sensor (MAP) is not functioning properly.
    Fix: Check between pins A and C of sensor plug for 5 VDC. If present, sensor may be defective. Low reading or not present, defective harness or ignition control module.
  • The phase currents are unbalanced (3-phase generators) — The stator windings are faulty (open or shorted)
    Cause: The stator windings are faulty (open or shorted)
    Fix: Shut down the set and check stator winding resistances according to instructions in this section. Replace the generator stator assembly if stator winding resistances do not meet specifications.
  • The phase currents are unbalanced (3-phase generators) — The connected loads are distributed unevenly among the phases
    Cause: The connected loads are distributed unevenly among the phases
    Fix: Shut down the set and redistribute the loads as evenly as possible.
  • The phase currents are unbalanced (3-phase generators) — Improper connections have been made at the generator output terminals
    Cause: Improper connections have been made at the generator output terminals
    Fix: Shut down the set and reconnect according to the reconnection diagram in Section 9.
  • The phase currents are unbalanced (3-phase generators) — A load has a ground fault or short circuit
    Cause: A load has a ground fault or short circuit
    Fix: Service the faulty equipment as necessary.
  • The OVERSPEED lamp comes on and the engine shuts down. 1
    Fix: A. Reset the ECM by pushing the Run-Stop-Remote switch to Stop and the Reset switch to Reset and restart the set, monitoring engine speed. Spec A & B: Readjust the cutout speed if it is lower than specified. Replace the overspeed switch if it cannot be readjusted (see Section 3). Begin Spec C: If engine speed is correct and the set still shuts down, replace the ignition control module. b. Adjust the governor (see Section 8). c. If the governor cannot be adjusted to prevent shutdown due to overspeed, check for binding in the linkage. Repair and adjust the linkage as necessary. d. If the set still shuts down due to overspeed, re-install the magnetic speed pick-up unit to make sure the clearance with the flywheel gear teeth is correct. Replace the speed-pickup unit if output voltage at cranking speed is less than 1.5 VAC. (Intermittent open on magnetic speed pick-up lead can also cause an overspeed condition.) e. Replace the governor controller if the set still shuts down due to overspeed.
  • The green RUN lamp stays off but the set runs normally — The set mounted RUN lamp does not light, although the starter has disconnected normally and the engine is running. The remote RUN lamp does light (AC start disconnect is okay)
    Cause: Run lamp bulb, wiring connections or battery charging alternator problem; ECM problem.
    Fix: Press the panel Lamp Test switch and replace the run lamp bulb if it does not light; If the RUN lamp, wiring connections and battery charging alternator are all good and the RUN lamp does not light, replace the ECM.
  • The green RUN lamp stays off but the set runs normally — Both the remote and set mounted RUN lamps do not light, although the starter has disconnected normally and the engine is running
    Cause: Run lamp bulbs; AC disconnect circuit not working; loose or missing leads between the connectors and TB21-21 and TB21-32 inside the control box; ECM problem.
    Fix: Press the panel Lamp Test switch and replace the run lamp bulb if it does not light. Test the remote RUN lamp by suitable means and replace it if it does not light; If both lamps are good, this indicates that the AC disconnect circuit is not working. Check the AC voltmeter to determine whether or not there is generator output voltage and service as necessary. See There Is No Output Voltage in Troubleshooting; If there is generator output voltage, check for 120 VAC across pin connectors P1-1 and P1-2 on the ECM. If there is no voltage, check for loose or missing leads between the connectors and TB21-21 and TB21-32 inside the control box and service as necessary; Replace the ECM if there is 120 VAC across pin connectors P1-1 and P1-2 but neither RUN lamp lights during normal operation.
  • The field circuit breaker keeps tripping (Detector control) — Voltage Regulator VR21 is faulty
    Cause: Voltage Regulator VR21 is faulty
    Fix: Replace the voltage regulator.

Compiled from service & troubleshooting documentation across every generator set that uses the Onan Modified Ford In-line 4.

Maintenance schedule

ItemSpecCapacityPart #Interval
BatteryGround—100 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceOverspeed switch magnet-to-fly arm air gap (minimum)0.005inches (0.13 mm)replace switch if less
GapSpark plug gap0.044inches
PressureFuel changeover pressure switch3.5inch H2O or lessshould switch from natural gas to LPG
PressureFuel supply pressure (maximum permissible)13.6inches (350 mm) WCoperating or not operating
PressureFuel supply pressure (minimum)7inches (178 mm) WCgenset operating at rated load
PressureLow fuel indicator5inches (127 mm) WCsingle/dual fuel systems
PressureLow oil pressure shutdown (LOP)14psi (97 kPa)naturally aspirated
PressureLow oil pressure shutdown (LOP)25psi (173 kPa)turbocharged
PressureNatural gas energy content1000BTU per cubic foot
PressureNormal oil pressure40 to 65psi (276 to 449 kPa)at normal operating temperature
PressurePre-low oil pressure warning20psi (137 kPa)naturally aspirated
PressurePre-low oil pressure warning30psi (207 kPa)turbocharged
PressurePropane energy content2500BTU per cubic foot
ResistanceCrank position sensor315 to 385ohmsBegin Spec C
ResistanceExciter rotor winding resistance0.49 to 0.59ohms
ResistanceExciter stator winding resistance (F1-F2)13 to 16ohms
ResistanceIgnition coil primary0.5 to 1.3ohms
ResistanceMagnetic speed pickup unit resistance1,000 to 1,050ohms
ResistanceMain rotor winding resistance (12-lead, 12.5 in)2.75ohms
ResistanceMain rotor winding resistance (12-lead, 13.75 in)1.80ohms
ResistanceMain rotor winding resistance (4-lead single-phase)2.75ohms
ResistanceMain stator winding resistance (12-lead three-phase)0.104-0.115ohmsreference stack 178 mm (7.0 in)
ResistanceMain stator winding resistance (12-lead three-phase)0.108-0.119ohmsreference stack 146 mm (5.75 in)
ResistanceMain stator winding resistance (4-lead single-phase)0.053-0.059ohmsreference stack 146 mm (5.75 in)
ResistanceMain stator winding resistance (6-lead 347/600 V three-phase)0.47-0.51ohmsreference stack 146 mm (5.75 in)
ResistancePolarization indexat least 2ratio (10 min / 1 min)
ResistanceSpark plug wires6,000ohms/foot
ResistanceVoltage adjusting rheostat0 to approximately 1000ohmsturning adjusting screw fully each way
ResistanceWinding insulation resistance (in service)not less than 1megohm
ResistanceWinding insulation resistance (new generator, dry windings)at least 5megohmsat 1 minute and 10 minutes
SpeedGovernor arm angle64degrees (±2)throttle lever closed
SpeedGovernor idle speed800rpmthrottle closed by hand
SpeedMagnetic speed pickup unit back-off1/4turnafter touching ring gear tooth
SpeedOverspeed shutdown (ignition module)2500RPM50/60 Hz sets, Begin Spec C
SpeedOverspeed shutdown (mechanical switch, 50 Hz sets)2100RPMSpec A & B
SpeedOverspeed shutdown (mechanical switch, 60 Hz sets)2500RPMSpec A & B
SpeedStart disconnect (electronic overspeed/start disconnect module)about 660rpmSpec A & B
SpeedStarter disconnectabout 600RPM
TemperatureHigh engine temperature shutdown230°F (110°C)
TemperatureLow engine temperature warning65°F (18°C)selectable on Sensor board
TemperatureLow engine temperature warning (alternate)90°F (32°C)selectable on Sensor board
TemperatureNormal coolant temperature165 to 195°F (74 to 91°C)normal operating
TemperaturePre-high engine temperature warning220°F (104°C)
TorqueDrive disc eight bolts37-42ft-lb (50-57 N-m)remounting drive disc
TorqueDrive disc-to-flywheel six bolts27-29ft-lb (37-39 N-m)remounting rotor to flywheel
TorqueEnd bell cover plate four screws8in-lb (3.8 N-m)
TorqueExciter stator two mounting screws8ft-lb (11 N-m)remounting exciter stator
TorqueFlywheel housing bolts60ft-lb (81 N-m)remounting
TorqueGenerator through-stud nuts (end bell)19-21ft-lb (26-28 N-m)mounting end bell
TorqueMain rotor F1+/F2- terminal nuts24lb-in (2.7 N-m)when reassembling
TorqueOverspeed switch center rotor bolt18ft-lbs (25 N-m)when replacing the switch
TorqueOverspeed switch rotor bolt18ft-lb (25 N-m)mounting rotor element/switch
TorqueRotating rectifier diode terminal nuts24lb-in (2.6 N-m)
VoltageB+ auxiliary terminals current (maximum)7ampscustomer accessories at TB1-5
VoltageBattery charging voltage12 to 14voltsnormal
VoltageFully charged battery specific gravity1.260at 80°F (27°C)
VoltageMAP sensor supply5VDCbetween pins A and C of sensor plug
VoltageMPU output at cranking speed (minimum)1.5VAC
VoltageOil pressure sender (replace if greater than)3.1VDCacross sensor terminals
VoltageTemperature sender (replace if less than)1.1VDCacross sender terminals

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Electric Governor Adjustment adjustment

Tools: Tachometer or frequency meter

  1. Check the dip switch (SW1-SW4) settings for the application frequency and spec.
  2. Start the set, warm up under a partial load (at least 1/4 rated load), then disconnect all loads.
  3. If the governor was replaced, adjust the Gain to approximately 5 and Stability to 3.5.
  4. Adjust the Gain pot until the engine is stable and responsive; turn counterclockwise to eliminate hunting.
  5. Bump the throttle lever a couple of times to check for hunting.
  6. Apply full load and adjust the Stability pot to minimize overshoot.
  7. Attach a tachometer or frequency meter and adjust the Speed Trim pot to the desired speed.
  8. Shut down and restart the genset to check for overspeed shutdown on startup.
Gaseous Fuel Adjustments adjustment

⚠ Gaseous fuels are flammable and explosive and can cause severe personal injury or death. Keep a type ABC fire extinguisher handy.

Tools: Tachometer

  1. Start the engine and let the set warm up under a partial load (at least 1/4 rated load).
  2. Disconnect all loads, shut down, connect a tachometer and disconnect the governor linkage at the carburetor.
  3. Start the engine and hold the throttle closed by hand so the engine does not overspeed.
  4. Adjust the throttle idle position screw to obtain 800 rpm; reconnect the governor linkage.
  5. Connect full rated load and turn the main fuel valve to full-rich.
  6. Slowly turn the main fuel valve toward lean until the engine begins to lose speed.
  7. Slowly back toward rich until the engine carries the full load smoothly.
  8. For dual fuel, switch to LPG by closing the manual shutoff valve in the natural gas supply line.
  9. Turn the LPG flow adjustment valve clockwise until the engine begins to lose speed.
  10. Slowly turn it back counterclockwise until the engine carries full load smoothly.
Ignition Timing adjustment
  1. Modification of connections is required only when converting the generator set fuel system.
  2. Natural gas only (Spec A & B): connect EH lead P10 to IM pin #6.
  3. Natural gas only (Spec A & B): connect EH lead P11 to IM pin #7.
  4. LPG only (Spec A & B): connect EH lead P10 to IM pin #6; leave EH lead P11 and IM pin #7 disconnected.
  5. Dual fuel (Spec A & B): connect EH lead P10 to IM pin #6; connect EH lead P11 to DFH lead P11; leave DFH lead P7 and IM pin #7 disconnected.
  6. Begin Spec C: refer to the DC Wiring Diagram in Section 9.
Linkage Adjustment adjustment
  1. With the genset stopped, remove the governor rod and spring from the throttle lever.
  2. With the actuator shaft full counterclockwise, check the governor arm angle is 64° ±2°.
  3. Loosen the governor arm screw to adjust the governor arm.
  4. Verify the ball joint screw is in the third hole from the outside end of the governor arm.
  5. Attach the governor rod and spring to the throttle lever.
  6. With the throttle lever closed, adjust the governor rod so the arm angle is 64° ±2°.
Magnetic Speed Pickup Unit Adjustment adjustment

Tools: Ohmmeter

  1. Measure MPU resistance; replace if not between 1,000 and 1,050 ohms.
  2. With the MPU removed, rotate the ring gear until a tooth lines up in the center of the mounting hole.
  3. Thread the pickup in gently by hand until it just touches the ring gear tooth.
  4. Back it out 1/4 turn and set the locknut.
  5. Check output voltage; replace the MPU if output voltage at cranking speed is less than 1.5 VAC.
Stability Adjustment adjustment
  1. Run the generator set at rated frequency and no load.
  2. Slowly turn the STABILITY pot clockwise until voltage becomes stable.
  3. Turn counterclockwise until voltage again becomes unstable.
  4. Turn the pot slightly clockwise from this position for maximum stability.
  5. Readjust voltage after a stability adjustment.
UFRO Adjustment adjustment

Tools: Frequency meter

  1. Check that the frequency selection jumper is connected for the application (50 Hz or 60 Hz).
  2. Adjust the UFRO pot so the LED lights as frequency drops to 47 Hz (50 Hz) or 57 Hz (60 Hz).
  3. Turn the pot clockwise to reduce the knee point frequency.
Voltage Adjustment adjustment

⚠ HAZARDOUS VOLTAGE! Touching uninsulated parts inside the control and power output boxes can result in severe personal injury or death.

Tools: AC-DC multimeter

  1. Turn the voltage trimmer (Detector control) to its mid position.
  2. Turn the VOLTS pot on the voltage regulator fully counterclockwise.
  3. Turn the STABILITY pot on the voltage regulator to its mid position.
  4. Start and operate the generator set at rated frequency and no load.
  5. If the LED lights, see UFRO Adjustment.
  6. Slowly turn the VOLTS pot clockwise until rated voltage is obtained.
  7. See Stability Adjustment if voltage is unstable.
Testing Winding Insulation Resistance diagnostic

⚠ Disconnect starting battery cables (negative first) before performing tests.

Tools: 500 VAC megger

  1. Apply the test potential between the winding and ground (winding laminations) for 10 minutes.
  2. Record resistance at 1 minute and again at 10 minutes.
  3. For a new generator with dry windings, obtain at least 5 megohms.
  4. Polarization index should be at least 2.
  5. For a set in service, resistance should not be less than 1 megohm.
Field Flashing repair

⚠ The voltage regulator could be damaged if the flashing circuit is connected for more than 5 seconds.

⚠ HAZARDOUS VOLTAGE! Stand on a dry wooden platform or rubber insulating mat, make sure clothing and shoes are dry, remove jewelry and use tools with insulated handles.

Tools: 12 volt battery, 10 ohm resistor, 18 volt voltage suppressor, 12 A, 300 V diode

  1. Assemble a 12 volt battery, 10 ohm resistor, 18 volt voltage suppressor and 12 amp 300 volt diode.
  2. While the set runs at nominal frequency, momentarily connect the positive (+) side to voltage regulator terminal VR21-F1 (X).
  3. Connect the negative (-) side to voltage regulator terminal VR21-F2 (XX).
  4. Check output voltage, shut down the set and restart it.
Generator Disassembly repair

⚠ The generator is heavy; you will need an assistant and hoist of sufficient capacity.

⚠ Disconnect battery charger from AC source before disconnecting battery cables.

⚠ Disconnect the negative (-) cable first and reconnect last.

Tools: Hoist and straps, Gear puller

  1. Disconnect all power output and remote control connections and conduit; mark each lead.
  2. Remove the end bell cover; disconnect the overspeed/start disconnect module plug and F1/F2 wires.
  3. Remove the overspeed/start disconnect rotor element or overspeed switch assembly from the shaft end.
  4. Disconnect generator leads and engine wiring harness from all terminals inside the control box.
  5. Remove the four bolts securing the two saddle brackets of the control box to the generator.
  6. Remove the two nuts and washers of the top generator through-studs.
  7. Slide the control housing assembly off of the through-studs.
  8. Cinch a hoisting strap around the middle of the generator stator and take up slack.
  9. Scribe lines to register the parts before separating stator, flywheel housing and end bell.
  10. Remove the remaining two through-stud nuts and tap the end bell free of the stator assembly.
  11. Tap the generator stator free of the adaptor housing and draw it straight back.
  12. Remove the generator through-studs.
  13. Remove the air baffle, then the drive disc mounting bolts if rotor removal is needed.
  14. Remove the two mounting screws if the exciter stator must be removed from the end bell.
  15. Use a gear puller if the rotor bearing must be removed.
Generator Reassembly repair

⚠ Do not start the generator set until the DC start disconnect module has been remounted and reconnected.

Tools: Torque wrench

  1. Press a new rotor bearing up to the shoulder of the shaft (do not lubricate); apply force to the inner race.
  2. Torque the eight drive disc bolts to 37-42 ft-lb (50-57 N-m).
  3. Torque the six drive disc-to-flywheel bolts to 27-29 ft-lb (37-39 N-m).
  4. Install the air baffle using four bolts.
  5. Torque the flywheel housing bolts to 60 ft-lb (81 N-m).
  6. Thread generator through-studs into the flywheel housing with the short-thread ends in the housing.
  7. Mate the generator stator and flywheel housing making the scribed index lines register.
  8. Torque the exciter stator two screws to 8 ft-lb (11 N-m); connect F1 and F2 leads.
  9. Wipe the bearing bore in the end bell with molybdenum disulfide grease; make sure the O-ring is in place.
  10. Mount the end bell; torque the through-stud nuts to 19-21 ft-lb (26-28 N-m).
  11. Mount the overspeed switch assembly on the rotor and torque the bolt to 18 ft-lb (25 N-m).
  12. Remount and reconnect all other components disconnected or removed under Disassembly.
  13. Route and reconnect the control box wires and F1/F2 leads to the stator connection board.
  14. Secure the end bell cover plate and torque the four screws to 8 in-lb (3.8 N-m).

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
Spec A & B - Dual fuel (NG/LPG) onlyConnect EH lead P10 to IM pin #6; connect EH lead P11 to DFH lead P11; leave DFH lead P7 and IM pin #7 disconnectedIgnition timing; required only when converting fuel system
Spec A & B - LPG onlyConnect EH lead P10 to IM pin #6; leave EH lead P11 and IM pin #7 disconnectedIgnition timing; required only when converting fuel system
Spec A & B - Natural Gas (NG) onlyConnect EH lead P10 to IM pin #6 (yellow/black with wire tie); connect EH lead P11 to IM pin #7 (yellow/black without wire tie)Ignition timing; required only when converting fuel system

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Onan Modified Ford In-line 4?

The Onan Modified Ford In-line 4 engine has an oil capacity of 4.5 liters.

Which generators use the Onan Modified Ford In-line 4 engine?

The Onan Modified Ford In-line 4 powers 1 generator set(s), including Cummins/Onan GGDB.

What is a common problem with the Onan Modified Ford In-line 4 engine?

A commonly reported issue on generators using the Onan Modified Ford In-line 4 is: The engine lacks power or is unstable — Engine misfires on LPG or NG or backfires on LPG at high loads. Cause: Engine misfires on LPG or NG or backfires on LPG at high loads.. Fix: Air fuel ratio too lean. Adjust main fuel valve. Refer to Gaseous Fuel Adjustment in Section 8; Inspect spark plugs/gap (0.044"); Check spark plug wires (6,000 ohms/foot); Check ignition coil primary (0.5 to 1.3 ohms); LPG liquid withdrawal - defective LPL converter..