The OHV GA-420 is a 420 L engine rated at 3600 rpm. It powers generator sets from Generac, including the PowerPact 5.6 kVA 50 Hz. It holds 1.1 L (0.3 gal) of oil.
Also known as: OHV GA-420
| Oil capacity | 1.1 L |
|---|---|
| Displacement | 420.0 L |
| Rated speed | 3600 rpm |
Compiled from service & troubleshooting documentation across every generator set that uses the OHV GA-420.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Oil level | Check | 24 hr | CorePower; monthly or 24 hours of continuous operation | |
| Air cleaner | Clean | 50 hr | 3 mo | PowerPact; 3 months or 50 hours |
| Oil | Change | 100 hr | 12 mo | First service — PowerPact; change after first 20 hours or 1 month, then 100 hours or 6 months |
| Oil filter | Change | 100 hr | 12 mo | First service — CorePower; change after first 8 hours, then every 100 hours or 1 year |
| Spark plug | Inspect | 100 hr | 6 mo | PowerPact; 6 months or 100 hours |
| Complete tune-up | Other | 200 hr | 12 mo | CorePower; to be completed by a dealer |
| Spark plug | Replace | 200 hr | 12 mo | CorePower; 1 year or 200 hours |
| Air cleaner | Replace | 300 hr | 12 mo | PowerPact; 1 year or 300 hours |
| Spark plug | Change | 300 hr | 12 mo | PowerPact; 1 year or 300 hours |
| Valve clearance | Check | 300 hr | 12 mo | First service — PowerPact; check after first 20 hours, then every 300 hours or 1 year |
| Battery - remove corrosion, ensure dryness | Clean | 12 mo | PowerPact; yearly | |
| Battery charge state | Check | 12 mo | PowerPact; yearly | |
| Battery electrolyte level | Check | 6 mo | CorePower; every 6 months | |
| Battery electrolyte level (unsealed batteries only) | Check | 6 mo | PowerPact; every 6 months | |
| Battery terminals - clean and tighten | Clean | 12 mo | PowerPact; yearly | |
| Fuel lines and connections | Inspect | 1 mo | CorePower; monthly | |
| Vibration, Noise, Leakage | Inspect | 1 mo | PowerPact; monthly | |
| Vibration, Noise, Leakage, Temperature | Inspect | 1 mo | CorePower; monthly |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Gap | Spark plug gap | 0.76 mm (0.030 inch) | mm | |
| Pressure | Cylinder leak down tester regulated pressure | 80 | PSI | 90 PSI air source |
| Pressure | Fuel pressure - LP gas - inlet side of fuel solenoid | 10-12 | inches water column | |
| Pressure | Fuel pressure - natural gas - inlet side of fuel solenoid | 5-7 | inches water column | |
| Pressure | Minimum allowable compression pressure | 60 | PSI | cold engine |
| Pressure | Normal oil pressure | 35-40 | psi | engine running |
| Pressure | Oil pressure - shut engine down immediately if below | 4.5 | psi | |
| Pressure | Oil pressure switch rating (single cylinder) | 10 | psi | |
| Resistance | Choke solenoid (component table) | 4 | ohms | |
| Resistance | Choke solenoid coil resistance | ~3.7 | ohms | |
| Resistance | Fuel solenoid FS1 nominal resistance | 14-16 | ohms | |
| Resistance | Main fuel solenoid | 16 | ohms | |
| Resistance | Rotor resistance - CorePower | 40 +/-20 | ohms | |
| Resistance | Rotor resistance - PowerPact | 50 +/-20 | ohms | |
| Resistance | Starter contactor | 8 | ohms | |
| Resistance | Stator DPE winding Blue (2)/Blue (6) - PowerPact | 1.85 | ohms | |
| Resistance | Stator DPE winding Blue/Blue - CorePower | 1.158 | ohms | |
| Resistance | Stator power winding 11/22 - PowerPact 50 Hz | 0.36 | ohms | |
| Resistance | Stator power winding 11/22 - PowerPact 60 Hz | 0.24 | ohms | |
| Resistance | Stator power winding 33/44 - PowerPact 50 Hz | 0.36 | ohms | |
| Resistance | Stator power winding 33/44 - PowerPact 60 Hz | 0.24 | ohms | |
| Resistance | Stator power winding Blue/Black - CorePower | 0.346 | ohms | |
| Resistance | Stator power winding White/Black - CorePower | 0.173 | ohms | |
| Resistance | Stator power winding White/Blue - CorePower | 0.173 | ohms | |
| Resistance | Stator sensing winding Green/White - CorePower | 0.064 | ohms | |
| Resistance | Stator sensing winding White (S1)/Green (S2) - PowerPact | 0.024 | ohms | |
| Resistance | Transfer relay | 115 | ohms | |
| Speed | No-load speed - 50 Hz | 3120 | RPM | 52 Hz |
| Speed | No-load speed - 60 Hz | 3750 | RPM | 62.5 Hz |
| Speed | Over speed shutdown - 50 Hz | 3600 | RPM | for three (3) seconds, or 3750 RPM immediately |
| Speed | Over speed shutdown - 60 Hz | 4320 | RPM | for three (3) seconds, or 4500 RPM immediately |
| Temperature | High oil temperature shutdown | 124 C (255 F) | C | |
| Temperature | High oil temperature switch - contacts close at | 293 | F | |
| Temperature | High oil temperature switch test range | 283-305 F (139-151 C) | F | |
| Torque | 3/8-16 screw to mounting foot | 5-8 | ft-lbs | |
| Torque | Governor lever clamp bolt - CorePower | 70 | in-lbs | |
| Torque | Governor lever clamp bolt - CorePower | 8 | Nm | |
| Torque | Governor pinch bolt nut - PowerPact | 62 | in-lbs | |
| Torque | M10 x 1.25 engine to vibration isolator | 15-20 | ft-lbs | |
| Torque | M3 x 0.5 screw into aluminum | 8-10 | in-lbs | |
| Torque | M3 x 0.5 taptite screw into extruded hole | 8-18 | in-lbs | |
| Torque | M5 x 0.5 screw into aluminum | 25-35 | in-lbs | |
| Torque | M5 x 0.8 screw on band clamp | 7.5-9 | ft-lbs | |
| Torque | M5 x 0.8 taptite screw into extruded hole | 25-50 | in-lbs | |
| Torque | M6 x 1.0 nyloc nut on dead front plate | 40-50 | in-lbs | |
| Torque | M6 x 1.0 screw flange nuts - airbox to cylinder head | 7-8 | ft-lbs | |
| Torque | M6 x 1.0 screw into aluminum | 50-60 | in-lbs | |
| Torque | M6 x 1.0 screw on band clamp | 14-15 | ft-lbs | |
| Torque | M6 x 1.0 taptite screw into extruded hole | 50-96 | in-lbs | |
| Torque | M8 x 1.0 nuts - exhaust to cylinder head | 20-22 | ft-lbs | |
| Torque | M8 x 1.25 taptite screw into extruded hole | 15-20 | ft-lbs | |
| Torque | M8 x 1.25 vibration isolator to base | 20-22 | ft-lbs | |
| Torque | Rocker arm jam nut | 70 to 106 | in-lbs | |
| Torque | Rotor bolt - CorePower | 30 | ft-lbs | |
| Torque | Rotor bolt - PowerPact | 27-33 | ft-lbs | |
| Torque | Stator bolts - CorePower | 6 | ft-lbs | |
| Torque | Stator bolts - PowerPact | 72 | in-lbs | |
| Valve clearance | Exhaust valve - CorePower | 0.007-0.009 in (0.18-0.22 mm) | in | cold |
| Valve clearance | Exhaust valve - PowerPact | 0.002-0.004 in (0.05-0.1 mm) | in | cold |
| Valve clearance | Intake valve - CorePower | 0.005-0.007 in (0.13-0.17 mm) | in | cold |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Engine oil | Synthetic SAE 5W-30 | API Service Class SJ, SL or better | for all temperature ranges; do not use synthetic until 50 hours of operation | ||
| Engine oil | SAE 10W-30 | API Service Class SJ, SL or better | -23°C to 4°C | between 40 and -10 F (4 and -23 C) | |
| Engine oil | SAE 30 | API Service Class SJ, SL or better | above 0°C | above 32 F (0 C); do not use special additives | |
| Fuel | LP vapor | at least 2,520 BTU per cubic foot | vapor withdrawal system only; fuel pressure must never drop below 10 inches water column | ||
| Fuel | Natural gas | at least 1,000 BTU per cubic foot | fuel pressure must never drop below 5 inches water column |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Tools: 13 mm wrench, frequency meter
Tools: feeler gauge, socket, wrench
Tools: compression gauge
Tools: Volt-Ohm-Meter
Tools: Volt-Ohm-Meter
Tools: needle nose pliers
⚠ Do not fill oil above the FULL mark.
⚠ Engine will crank and start!
⚠ If turning the unit off for longer than 24 hours, remove the F1 fuse from the generator controller.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The OHV GA-420 engine has an oil capacity of 1.1 liters.
The OHV GA-420 has a displacement of 420.0 liters.
The OHV GA-420 powers 1 generator set(s), including Generac PowerPact 5.6 kVA 50 Hz.
A commonly reported issue on generators using the OHV GA-420 is: Voltage and Frequency Drop Excessively When Loads Are Applied. Cause: TEST 9 – CHECK STATOR AC POWER WINDINGS. Fix: NOT PROVIDED IN THE TEXT.