| 1 | High Engine Temperature | Engine coolant temperature exceeded design limit | Shutdown | Add coolant, repair leaks, replace thermostat, clean raw water tubes, flush coolant system |
| 2 | Low Oil Pressure | Low oil pressure | Shutdown | Add engine oil or drain excess oil |
| 3 | Service Check | Indicates presence of second-level shutdown | Shutdown | Check second-level shutdown code by pressing STOP once |
| 4 | Overcrank | Cranking exceeded 20 to 60 seconds without start | Shutdown | Check fuel tank, open valves, remove blockage, tighten fittings, replace fuel filter, prime |
| 5 | Warning - Shutdown due to Vessel CO | Dangerous levels of Carbon Monoxide in vessel | Shutdown | Get everyone out into fresh air immediately and seek medical attention |
| 7 | Loss of Raw Water Flow | Low raw water pressure in heat exchanger | Shutdown | Open sea cock, clean strainer, reconnect hoses, replace impeller |
| 12 | Overvoltage | Controller unable to maintain rated voltage | Shutdown | See an authorized Onan dealer |
| 13 | Undervoltage | Controller unable to maintain rated voltage | Shutdown | Reduce number of connected appliances |
| 14 | Overfrequency | Engine governor unable to maintain rated frequency | Shutdown | Reset breaker after starting, tighten fuel fittings, prime fuel system |
| 15 | Underfrequency | Engine governor unable to maintain rated frequency | Shutdown | Reduce appliances, check fuel, remove blockage, tighten fittings, prime |
| 17 | Over-Prime | Prime mode exceeded 5 minutes | Shutdown | Remove object holding control switch in prime position |
| 22 | Governor Overload | Maximum allowable time at full-duty cycle exceeded | Shutdown | Reduce appliances, check fuel, remove blockage, tighten fittings, prime |
| 23 | Faulty Oil Pressure Sender | Controller sensed grounded sender | Shutdown | See an authorized Onan dealer |
| 24 | Faulty Temperature Sender | Controller sensed open sender | Shutdown | See an authorized Onan dealer |
| 27 | Loss of Voltage Sense | Controller unable to sense output voltage | Shutdown | See an authorized Onan dealer |
| 29 | High Battery Voltage | Battery system at more than 19.2V (12VDC) or 38.4V (24V) | Shutdown | Check battery bank connections, select lower boost charge rate |
| 32 | STARTING FAULT | Controller could not detect cranking speed (quadrature zero crossings) for 3 seconds | Shutdown | De-energize PTO, run propulsion engines while starting, service battery connections, change oil viscosity, check starter relay K4, check wiring, service starter motor, service engine, replace controller |
| 35 | Control Card Failure | Microprocessor EEPROM error during self-test | Shutdown | See an authorized Onan dealer |
| 36 | Engine Stopped | Engine stopped without command by controller | Shutdown | Open fuel valves, check fuel tank, check mechanical damage, remove blockage, prime |
| 37 | Invalid Genset Configuration | Controller cannot determine genset operating parameters | Shutdown | See an authorized Onan dealer |
| 38 | Field Overload | High field voltage induced by high rotor temperature or low power factor loads | Shutdown | Remove blockages to generator airflow, reduce appliances |
| 41 | Grounded Rotor | F+ grounded | Shutdown | See an authorized Onan dealer |
| 42 | Processor Failure | Microprocessor ROM error during self-test | Shutdown | See an authorized Onan dealer |
| 43 | Processor Failure | Microprocessor RAM error during self-test | Shutdown | See an authorized Onan dealer |
| 45 | SPEED SENSE LOST | After start disconnect, controller lost speed sense (quadrature zero crossings) for 0.25 seconds | Shutdown | Check for open/shorted field (P3-7 to P3-8) and quadrature (P3-4 to P3-5) windings, service generator, replace controller |
| 46 | Genset Overload | The genset Controller shutdown the genset because engine load exceeded 135 percent of genset rating for 10 seconds | Shutdown | Reduce the number of loads on the genset. |
| 48 | Processor Failure | Controller unable to sense field voltage | Shutdown | See an authorized Onan dealer |
| 57 | OVERPRIME | A local or remote control switch was held in the Prime position for more than 5 minutes | Shutdown | Remove object holding switch in prime position, replace faulty control switch |
| 58 | High Exhaust Temperature | Exhaust temperature exceeded design limits | Shutdown | Reconnect/replace raw water hoses, replace impeller |
| 59 | Low Coolant Level | Coolant level low | Shutdown | Add coolant, repair leaks |
| 61 | Emergency Shutdown | Genset was shut down by fire suppression system or other external control | Shutdown | Make necessary repairs and reset external control |
| Code No. 5 | Warning - Shutdown due to Vessel CO | Shutdown occurring due to the vessel CO detector | Warning | All status indicator lights in the control circuit will also blink the fault code. See Troubleshooting Chapter of the Operator Manual. |
| Code No. 61 | Emergency Shutdown | Shutdown occurring due to external emergency shutdown device | Shutdown | All status indicator lights in the control circuit will also blink the fault code. See Troubleshooting Chapter of the Operator Manual. |