Kohler KG6208 6.2L Engine

The Kohler KG6208 6.2L is a 6.2 L 6-cylinder natural aspiration and turbocharged engine rated at 1800 rpm, producing up to 77 kW. It powers generator sets from Kohler, including the 48RCLC, 60RCLA, 60RCLB and KG60. It holds 7.1 L (1.9 gal) of oil and 21.3 L (5.6 gal) of coolant.

Also known as: Kohler KG6208 6.2L

6.2 L
Displacement
6
Cylinders
1800 rpm
Rated speed
77 kW
Gross power

Engine specifications

Oil capacity7.1 L
Coolant capacity21.3 L
Displacement6.2 L
Cylinders6
AspirationNatural Aspiration and Turbocharged
Rated speed1800 rpm
Gross power77 kW

Generator sets powered by this engine

4

This engine also powers 1 machine(s) on Power Equipment Info.

How to read your Kohler engine serial & model number →

Common problems

15
  • The generator set does not crank.
    Cause: Battery weak or dead, Battery connections reversed or poor, Blown fuse(s)
    Fix: Recharge or replace the battery, Check the connections, Replace the fuse. Contact an authorized Kohler distributor/dealer for service if fuse blows repeatedly
  • The generator set cranks but does not start, starts hard, lacks power, or operates erratically.
    Cause: Air cleaner clogged, Battery weak or dead, Battery connection poor, Spark plug wire connection loose
    Fix: Clean and/or replace the air cleaner element, Recharge or replace the battery, Clean and tighten the battery connections, Check the spark plug wires
  • Remote stop command received from a remote switch, ATS, or OnCuer.
    Fix: Check the remote switch position
  • No AC output.
    Cause: AC circuit breaker in the OFF position
    Fix: Place the circuit breaker in the ON position
  • Low output or excessive drop in voltage.
    Cause: Generator set overloaded
    Fix: Reduce the load by unplugging non-essential appliances
  • Low oil pressure shutdown.
    Fix: Check for oil leaks. Check the oil level and add oil if necessary
  • Load management relays do not operate.
    Cause: Bad connections
    Fix: Check wiring and connections. Verify that cable size and length of run comply with the instructions in the Installation manual, Low or no battery voltage
  • Generator set stops suddenly.
    Cause: Low oil pressure shutdown, Out of fuel, Overcrank shutdown, Blown fuse(s), Overspeed shutdown
    Fix: Check for oil leaks. Check the oil level and add oil if necessary, Check fuel supply, Reset the controller. If the overcrank fault occurs again, contact an authorized Kohler distributor/dealer, Replace the fuse. If the fuse blows again, contact an authorized Kohler distributor/dealer, Reset the controller. If the overspeed fault occurs again, contact an authorized Kohler distributor/dealer
  • Generator set is OFF.
    Cause: Press the RUN button to start the engine or press AUTO to allow remote starting
  • Fuel pressure insufficient.
    Fix: Check the fuel supply and valves
  • Fans run after engine shuts down.
    Fix: The fans continue to run for 2 minutes after the engine shuts down to evacuate the engine compartment
  • Engine malfunction.
    Fix: Contact an authorized Kohler distributor/dealer
  • Date is flashing.
    Cause: Controller power was disconnected and then reconnected
    Fix: Check battery connections. See Figure 5-1, Check utility power connection for the built-in battery charger
  • Controller LCD display is off.
    Cause: Low or no battery voltage
    Fix: Check connections, Check generator set battery. See Figure 5-1
  • Controller display backlight is off.
    Cause: Backlight turns off after about 1 minute with no activity
    Fix: Backlight will turn on when a button is pressed or the generator set starts

Compiled from service & troubleshooting documentation across every generator set that uses the Kohler KG6208 6.2L.

Maintenance schedule

ItemSpecCapacityPart #Interval
Oil filterKOH-48RCLB-OILF150 hr Amazon eBay
BeltTensioner, 6.2L drive beltGM102050 Amazon eBay
Oil7.1 LKOH-48RCLB-OIL500 hr Amazon eBay

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

29
ItemActionHoursMonthsNotes
Air cleaner elementCheck150 hr12 moYearly or 150 hours; more frequently under dusty conditions
Crankcase breather hoseInspect150 hr12 moYearly or 150 hours
Engine oil and oil filterChange150 hr12 moYearly or 150 hours
Spark plugsCheck150 hr12 moYearly or 150 hours
Air cleaner elementReplace400 hr12 moYearly or 400 hours; more frequently under dusty conditions
Engine air induction systemCheck500 hr36 mo3 years or 500 hours; check for leaks
Engine air induction system leaksCheck500 hr36 mo3 Years or 500 hours
Engine coolantChange500 hr36 mo3 years or 500 hours; when long-life coolant is used the change interval is 5000 hours or 5 years
Spark plug gapAdjust500 hr36 mo3 years or 500 hours; replace spark plugs if discolored or damaged
Spark plug wiresCheck500 hr36 mo3 Years or 500 hours; cuts, hardening, abrasions
Spark plug wiresReplace500 hr36 mo3 years or 500 hours; check for cuts, hardening or abrasions and replace as needed
Winding resistance readingsTest500 hr36 mo3 years or 500 hours; measure with insulation tester (Megger) with SCR assembly or rectifier and load leads disconnected; have this service performed by an authorized distributor or dealer
Wire-cable insulationCheck500 hr36 mo3 years or 500 hours
Wire-cable insulation conditionCheck500 hr36 mo3 Years or 500 hours
Engine maintenance requirementsOther2000 hr60 mo5 years or 2000 hours; see the Engine Operation Manual
Battery and rack corrosionClean12 moYearly; remove corrosion, clean and dry
Battery charger operation, charge rateCheck1 moMonthly
Battery electrolyte level and specific gravityCheck12 moYearly; not necessary for maintenance-free batteries
Battery terminals and bootsClean12 moYearly; clean and tighten, inspect boots
Control and power wiring connectionsAdjust12 moYearly; tighten
DEPR fuel pressureCheck12 moYearly; see Engine Operation Manual
Drive belt cracks, splitting, breaksCheck12 moYearly; see Engine Operation Manual
Engine and generator visible wear or damageCheck3 moQuarterly
Fuel lines and connectionsCheck3 moQuarterly
Fuel pipingInspect12 moYearly
Interior of sound enclosureCheck3 moQuarterly
Radiator exteriorClean12 moYearly; check and clean
Remote control system, if equippedCheck3 moQuarterly
Wire abrasions where subject to motionCheck6 moEvery 6 Months

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
GapSpark plug gap0.76mm (0.03 in.)
GapSpark plug gap0.9mm
Other10 in. weld flange bolt circle diameter B361.95mm (14.25 in.)
Other10 in. weld flange outside diameter C406.4mm (16.0 in.)
Other10 in. weld flange quantity of bolts / bolt hole diameter D12, 25.40mm (1.00 in.)
Other12 in. weld flange bolt circle diameter B431.80mm (17.00 in.)
Other12 in. weld flange outside diameter C482.6mm (19.0 in.)
Other12 in. weld flange quantity of bolts / bolt hole diameter D12, 25.40mm (1.00 in.)
Other14 in. weld flange bolt circle diameter B476.25mm (18.75 in.)
Other14 in. weld flange outside diameter C533.4mm (21.0 in.)
Other14 in. weld flange quantity of bolts / bolt hole diameter D12, 28.58mm (1.13 in.)
Other16 in. weld flange bolt circle diameter B539.75mm (21.25 in.)
Other16 in. weld flange outside diameter C596.9mm (23.5 in.)
Other16 in. weld flange quantity of bolts / bolt hole diameter D16, 28.58mm (1.13 in.)
Other18 in. weld flange bolt circle diameter B577.85mm (22.75 in.)
Other18 in. weld flange outside diameter C635.0mm (25.0 in.)
Other18 in. weld flange quantity of bolts / bolt hole diameter D16, 31.75mm (1.25 in.)
Other20 in. weld flange bolt circle diameter B635.00mm (25.00 in.)
Other20 in. weld flange outside diameter C698.5mm (27.5 in.)
Other20 in. weld flange quantity of bolts / bolt hole diameter D20, 31.75mm (1.25 in.)
Other5 in. weld flange bolt circle diameter B215.90mm (8.50 in.)
Other5 in. weld flange outside diameter C241.30mm (9.50 in.)
Other5 in. weld flange quantity of bolts / bolt hole diameter D8, 22.23mm (0.88 in.)
Other6 in. weld flange bolt circle diameter B254.0mm (10.0 in.)
Other6 in. weld flange outside diameter C279.4mm (11.0 in.)
Other6 in. weld flange quantity of bolts / bolt hole diameter D8, 22.23mm (0.88 in.)
Other8 in. weld flange bolt circle diameter B298.45mm (11.75 in.)
Other8 in. weld flange outside diameter C342.9mm (13.5 in.)
Other8 in. weld flange quantity of bolts / bolt hole diameter D8, 22.23mm (0.88 in.)
OtherBattery cell specific gravity difference (maximum)0.01
OtherBattery specific gravity, fully charged1.260at 80 F (26.7 C)
OtherBattery specific gravity, needs charging (below)1.215at 80 F (26.7 C)
OtherBattery wrap length1067 (42)mm (in.)
OtherBattery wrap length864 (34)mm (in.)
OtherHeater wrap rating50Watts
OtherHeater wrap rating65Watts
OtherPlug cord length75 (3)mm (in.)
OtherPower cord length1677 (66)mm (in.)
OtherPower cord length1830 (72)mm (in.)
OtherPower cord length483 (19)mm (in.)
OtherVoltage regulator gain (outer loop) adjustment range1--255default 16
OtherVoltage regulator volts/Hz cut-in frequency42--62Hzdefault 59
OtherVoltage regulator volts/Hz slope1--10%default 4
OtherWeld flange angle A (10, 12, 14 in. nominal pipe size)30deg.
OtherWeld flange angle A (16, 18, 20 in. nominal pipe size)22.5deg.
OtherWeld flange angle A (5, 6, 8 in. nominal pipe size)45deg.
PressureFuel supply pressure, LPG1.2--2.7kPa (5--11 inches H2O)generator running at rated load
PressureFuel supply pressure, NG1.7--2.7kPa (7--11 inches H2O)generator running at rated load
PressurePressure cap rating83--110kPa (12--16 psi)
PressurePressure cap rating83-110kPa (12-16 psi)
PressureRadiator pressure cap rating83--110kPa
PressureSecondary fuel regulator maximum inlet pressure2.7kPa (6 oz./in.2) or 280 mm (11 in.) water column
ResistanceEngine compartment temperature sensor resistance at 100_C (212_F)180--200Ohms100_C (212_F)
ResistanceEngine compartment temperature sensor resistance at 30_C (86_F)2100--2400Ohms30_C (86_F)
SpeedEngine crank disconnect speed750RPM
SpeedEngine idle speed (default)1350RPM
SpeedEngine run speed (50 Hz)1500RPM50 Hz
SpeedEngine run speed (60 Hz)1800RPM60 Hz
SpeedNormal running speed (engine metering display)1800RPM
TemperatureBlock heater thermostat cut-off temperature27--38°Ccoolant temperature

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50% ethylene glycol0.6 LProvides freezing protection to --37_C (--34_F) and overheating protection to 129_C (265_F). Do not use alcohol or methanol antifreeze. Coolant added after block heater installation is approximately 0.6 L (0.2 gal).
Coolant50% ethylene glycol and 50% clean, softened water21.3 LProvides freezing protection to -37_C (-34_F) and overheating protection to 129_C (265_F). Do not use alcohol or methanol antifreeze. Do not use less than 50% or more than 50% ethylene glycol. 21.9 L (5.8 gal.) with block heater.
Coolant50% ethylene glycol-based long-life coolant / 50% clean, softened water-37°C to 129°C20.8 L48RCLB; freeze protection to -37C (-34F), overheat protection to 129C (265F)
Coolant50% ethylene glycol-based long-life coolant and 50% clean, softened water-37°C to 129°C20.8 LCapacity 20.8 L (5.5 gal.); with block heater 21.4 L (5.7 gal.). Do not mix long-life and conventional coolants. Do not use alcohol or methanol antifreeze. When long-life coolant is used, change interval is 5000 hours or 5 years.
CoolantEthylene glycol-based long-life coolant-37°C to 129°C20.8 L50% coolant/50% water mix; 5.5 gal.; with block heater 21.4 L (5.7 gal.); -37C (-34F) freeze protection, 129C (265F) boil protection at 50% mix
Engine oilSAE 10W-40KOHLER Genuine Oil; zinc 1000--1200 ppm; phosphorous 1000--1200 ppm; sulfated ash 1% or lower4.7 LFully synthetic, engineered for gaseous-fueled (NG/LPG) engines; capacity 4.7 L (5.0 qt.) for 48RCLB and 60RCLA
Engine oilSAE 15W-40Rotella T4 or equivalent (zinc 1000-1200 ppm, phosphorous 1000-1200 ppm, sulfated ash ≤1.0%)4.7 L5.0 qt.
FuelNatural Gas or LP Gas vapor withdrawalFuel supply line inlet 1 in. NPT; natural gas fuel supply pressure 1.24-2.74 kPa (7-11 in. H2O); LPG vapor withdrawal fuel supply pressure 1.24-2.74 kPa (5-11 in. H2O)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
AC Sens Loss ShutdwnLoss of AC sensing shutdownLess than 5% of rated voltage measured on Phase A (or B or C if 3 phase) for 3 seconds, only in AUTO, only after acceptable voltage (> 5% of UV setting) has been detected.ShutdownCheck for loose wiring and connections. Check all AC leads. Troubleshoot alternator.
AC Sens Loss WarningLoss of AC sensing warningLess than 5% of rated voltage measured on Phase A (or B or C on 3 phase), for 1 second, 10 seconds after crank disconnect.WarningCheck for loose wiring and connections. Check all AC leads. Troubleshoot alternator.
AC Sens LostAC Sensing LostIn Auto mode, generator output AC sensing is lost; starts 10 seconds after crank disconnect. Warning after 1 sec if no output detected; shutdown after 3 sec if voltage was present then lost.WarningContact an authorized distributor/dealer for service.
ATS Com ErrorATS Communication ErrorWarning is displayed if RXT interface connection is lost.WarningCheck communication wiring between transfer switch interface board and generator set.
ATS ComError WarningATS communication errorThe controller has lost communications with the RXT ATS that had previously been communicating properly.WarningCheck connection to ATS module.
ATS Fail Xfr WarningATS fail to transferThe RXT ATS has reported a fail to transfer; the digital output for ATS Fail To Transfer (PIM) is active.WarningConsult ATS manual for troubleshooting.
ATS PhaseRotATS Phase Rotation MismatchTransfer switch phase rotation does not match; ATS will not transfer.WarningCorrect the ATS connection. Refer to the ATS Installation manual, wiring diagrams, and labels on the transfer switch.
ATS PhaseRot WarningATS phase rotationThe RXT ATS has reported a Phase Rotation Mismatch (3 phase only) and the ATS will not transfer.WarningCheck wiring to ATS. Consult ATS manual.
Accy PwrOverAccessory Power OverloadAn over current fault (short circuit) on the accessory controller power output.WarningContact an authorized distributor/dealer for service.
Accy PwrOver WarningAccessory Power OverloadAn over current fault (short circuit) on the accessory controller power output.WarningContact an authorized distributor/dealer for service
Alt Protect ShtdwnAlternator Protection ShutdownHigh generator current has been detected. The generator set shuts down to protect the alternator from damage caused by overheating the windings.ShutdownReduce the load.
Aux InputAuxiliary InputAn optional customer-connected input is closed. (Digital input from optional PIM.)ShutdownCheck customer-supplied equipment.
Aux Input ShutdwnAuxiliary input shutdownThe digital input for a custom shutdown (AuxiliaryInputShutdown - PIM) was activated (low).ShutdownCheck customer equipment connected to the PIM module.
Aux Input WarningAuxiliary input warningThe digital input for a custom warning (AuxiliaryInputWarning - PIM) is active (low).WarningCheck customer equipment connected to the PIM module.
Batt Chg FltBattery Charger FaultInput to PIM from an external battery charger (not the built-in charger).WarningCheck external battery charger.
Batt Chg Flt WarningBattery charger fault warningThe digital input for Battery Charger Fault Warning (PIM) is active (low). For an external battery charger only.WarningCheck customer equipment connected to the PIM module.
Battery High WarningBattery high warningBattery voltage above the high warning setting for 10 seconds or more.WarningCheck cranking battery.
Battery Low ShutdwnBattery low shutdownBattery voltage dropped to 11 VDC or less for 30 seconds or more, after running at least one minute.ShutdownCheck cranking battery. Check battery charger DC output voltage from RDC2 on lead CHO to the battery.
Battery Low WarningBattery low warningBattery voltage below the low warning setting for 90 seconds or more; checked before allowing an exercise to start.WarningCheck cranking battery. Check battery charger DC output voltage from RDC2 on lead CHO to the battery.
Battery Voltage HighBattery Voltage HighEngine starting battery voltage rises above 125% of the battery voltage setting for more than 10 seconds. Inhibited during the engine crank cycle. Clears when the battery voltage returns to an acceptable level.WarningCheck the battery rating/condition and the battery charger operation
Battery Voltage LowBattery Voltage LowEngine starting battery voltage falls below the battery voltage setting (typically 12.5 volts) for more than 90 seconds when the engine is not running. Inhibited during the engine crank cycle.WarningCheck the battery rating and condition. Check the battery charger operation. Charge or replace the battery.
CAN ShutdownCAN shutdownThe ECM shut down the engine and reported an unknown fault code.ShutdownTroubleshoot engine operation per the engine service manual.
CAN comm faultEngine CAN Communications FaultEngine CAN communications fault.ShutdownCheck wiring to ECM; check power to ECM
Chk DateTime WarningCheck date and time warningDC power to the controller has been interrupted and the date and time may not be correct.WarningVerify the time and date settings.
Compartmnt Temp ShutdwnCompartment temperature shutdownEngine compartment air temperature has exceeded 174_F (79_C).ShutdownTroubleshoot fan circuit failure and/or temperature sensor circuit. Check for blockage of intake or exhaust vents.
Compartmnt Temp WarningCompartment temperature warningEngine compartment temperature above 167_F (75_C).WarningTroubleshoot fan circuit failure and/or temperature sensor circuit. Check for blockage of intake or exhaust vents.
Coolant Level Low ShutdwnCoolant level low shutdownThe coolant level sensor indicated low coolant for 5 seconds or more.ShutdownCheck coolant level and fill as needed. Check for air in cooling system. Check the coolant level sensor operation.
Coolant Temp High ShutdwnCoolant temperature high shutdownThe ECM shutdown the engine and reported high coolant temperature as the fault.ShutdownCheck engine cooling system. Check radiator fans for proper operation. Check for blockage of inlet and exhaust vents.
Coolant Temp High WarningCoolant temperature high warningThe ECM is reporting high coolant temperature.WarningCheck engine cooling system. Check radiator fans. Check for blockage of vents.
Coolant Temp Low WarningCoolant temperature low warningThe ECM is reporting low coolant temperature.WarningCheck cooling system.
Coolant Temp No Sig ShutdwnCoolant temperature no signal shutdownThe ECM shutdown the engine and reported no coolant temperature signal as the fault.ShutdownCheck cooling system and coolant level sensor circuit.
Default Pars WarningDefault ParametersThe controller has been loaded with default parameters.WarningConfigure settings as needed for desired operation.
ECM Addr Err ShutdwnECM address error shutdownThere is a conflict in addressing on the ECM CAN bus.ShutdownVerify no other devices connected and broadcasting on the CAN bus.
ECM Comm Err ShutdwnECM communication error shutdownCommunication with the ECM was lost for 4 or more seconds.ShutdownCheck CAN communication wiring between controller and ECM.
ECM Mismatch ShutdwnECM mismatch shutdownThe ECM does not match any of the supported models.ShutdownVerify controller configuration using SiteTech. Consult local service technician.
Emerg Stop ShutdwnEmergency stop shutdownThe emergency stop circuit was tripped (open circuit).ShutdownCheck E-stop circuit for open switches, broken wires, disconnected wires, etc.
Engine Coolant Temperature HighEngine Coolant Temperature HighEngine coolant temperature exceeds the maximum temperature for more than 5 seconds. Function becomes active after crank disconnect.ShutdownCheck for blocked air inlets and exhaust outlets.
Engine Oil Pressure LowEngine Oil Pressure LowThe engine ECM indicates low oil pressure for more than 5 seconds. Function becomes active 30 seconds after crank disconnect. Does not protect against low oil level.ShutdownCheck for leaks in the lubrication system. Check the oil level and add oil if the level is low.
Engine Speed High ShutdwnEngine speed high shutdownEngine speed, as calculated from AC frequency, was above the high speed setting for 0.3 seconds or more; or the ECM reported overspeed.ShutdownTroubleshoot engine operation per the engine service manual.
Engine Speed Low ShutdwnEngine speed low shutdownAfter crank disconnect, engine speed was below the low speed setting for 3 seconds or more.ShutdownTroubleshoot engine operation per the engine service manual.
EngineSpeed HighEngine Speed HighEngine speed exceeds 115% of the normal running speed for more than 0.3 seconds.ShutdownContact an authorized distributor/dealer for service.
EngineSpeed LowEngine Speed LowEngine speed drops below 85% of the normal running speed for more than 3 seconds.ShutdownReduce the load; contact an authorized distributor/dealer for service
Exer Not SchExercise Not ScheduledNo exercise has been scheduled on the RDC2 controller.WarningSee Section 2.5 for instructions to set the exerciser.
Exer Not Sch WarningExercise not scheduled warningThere is no exercise scheduled.WarningSet the exercise schedule.
Frequency High ShutdwnFrequency high shutdownFrequency measured on Phase A exceeded the high frequency setting for 10 seconds, 10 seconds or more after crank disconnect.ShutdownTroubleshoot engine operation per the engine service manual.
Frequency Low ShutdwnFrequency low shutdownFrequency measured on Phase A was less than the low limit for 10 seconds, or 10 Hz or more below rated for 60 seconds or more, 10 seconds or more after crank disconnect.ShutdownTroubleshoot engine operation per the engine service manual.
Fuel Leak ShutdwnFuel leak shutdownThe digital input for Fuel Tank Leak Shutdown (PIM) was activated (low).ShutdownCheck customer equipment connected to the PIM module.
Fuel Leak WarningFuel leak warningThe digital input for Fuel Tank Leak Warning (PIM) is active (low).WarningCheck customer equipment connected to the PIM module.
Fuel Level Low ShutdwnFuel level low shutdownThe digital input for Low Fuel Level Shutdown (PIM) was activated (low).ShutdownCheck customer equipment connected to the PIM module.
GenBrkerOpen WarningGenerator Circuit Breaker OpenThere is voltage at the generator set but no voltage measured on the emergency side of the ATS (Model RXT transfer switch).WarningCheck line circuit breaker. Check for and correct short circuits or overloading on the load side before resetting the circuit breaker.
Generator Frequency HighGenerator Frequency HighGoverned frequency exceeds 110% of the system frequency setpoint for more than 10 seconds. Function becomes active 10 seconds after engine start.ShutdownContact an authorized distributor/dealer for service.
Generator Frequency LowGenerator Frequency LowGoverned frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below the system frequency setting for more than 60 seconds. Function becomes active 10 seconds after engine start.ShutdownReduce the load and restart; contact an authorized distributor/dealer for service
Generator Voltage L1-L2 HighGenerator Voltage HighOutput voltage exceeds 120% of the system nominal voltage for more than 2 seconds.ShutdownContact an authorized distributor/dealer for service.
Generator Voltage L1-L2 LowGenerator Voltage LowOutput voltage falls below 80% of the nominal system voltage for more than 10 seconds.ShutdownReduce the load and restart the generator set. Contact an authorized distributor/dealer for service.
Generator VoltageL1-L2 HighGenerator Voltage HighOutput voltage exceeds 120% of the system nominal voltage for more than 2 seconds.ShutdownContact an authorized distributor/dealer for service
Generator VoltageL1-L2 LowGenerator Voltage LowOutput voltage falls below 80% of the nominal system voltage for more than 10 seconds.ShutdownReduce the load and restart; contact an authorized distributor/dealer for service
Ground Fault WarningGround fault warningThe digital input for Ground Fault Warning (PIM) is active (low).WarningCheck customer equipment connected to the PIM module.
Lo Crank VltLow Cranking VoltageBattery voltage falls below 60% of system battery voltage for more than 6 seconds while the starter is engaged.WarningCharge or replace the battery.
Lo Crank Vlt WarningLow cranking voltage warningDuring cranking, battery voltage less than 60% (7.2V or 14.4V) for 6 seconds or more during cranking.WarningCheck cranking battery.
Locked RotorLocked RotorNo engine rotation sensed during cranking; shuts down 3 seconds after fault detected.ShutdownCheck the battery; check for loose connections; contact an authorized distributor/dealer for service
Locked Rotor ShutdwnLocked rotor shutdownNo rotation of the engine or alternator was detected for 3 seconds or more during cranking.ShutdownCheck cranking circuit. Troubleshoot the engine. Check alternator connections to controller and auxiliary winding circuit breaker. Troubleshoot the alternator.
MainPwrOverL ShutdownMain Power Overload ShutdownOver current fault on the controller power output (short circuit).ShutdownContact an authorized distributor/dealer for service.
MainPwrOverL ShutdwnMain power overload shutdownThe internal current limit circuit has tripped, indicating an overcurrent condition on the DC power supply circuit.ShutdownCheck crank, run, and flash relay circuits for short circuits.
Not In Auto WarningNot in auto warningThe RDC2 controller is not in AUTO; the generator will not start from an ATS or remote device.WarningPress the Auto button to ensure automatic system operation.
Not in AutoNot in AutoThe generator set is not in Automatic (standby) mode. Remote start and stop commands from a transfer switch or remote switch will be ignored.WarningPress AUTO to place the generator set in Automatic mode, when appropriate.
OB1 CommLossOption board 1 communication lossCommunications with option board #1 (PIM, load management device, or RXT) has been lost.WarningCheck RBUS wiring to inoperative option board.
OB2 CommLossOption board 2 communication lossCommunications with option board #2 has been lost.WarningCheck RBUS wiring to inoperative option board.
OB3 CommLossOption board 3 communication lossCommunications with option board #3 has been lost.WarningCheck RBUS wiring to inoperative option board.
OB4 CommLossOption board 4 communication lossCommunications with option board #4 has been lost.WarningCheck RBUS wiring to inoperative option board.
Oil Pressure Low ShutdwnOil pressure low shutdownThe ECM shutdown the engine and reported low oil pressure as the fault.ShutdownCheck for oil leaks. Check the oil level and add oil if low. Check the oil pressure sensor.
Oil Pressure Low WarningOil pressure low warningThe ECM is reporting a low oil pressure warning.WarningCheck the oil level and add oil if low. Check the oil pressure sensor.
Oil Pressure No Sig ShutdwnOil pressure no signal shutdownThe ECM shutdown the engine and reported no oil pressure signal as the fault.ShutdownCheck engine oil pressure sensor and wiring to the ECM. Troubleshoot engine.
Over CrankOver CrankThree unsuccessful starting attempts.ShutdownCheck the fuel supply, spark plug, and battery; check for loose connections; contact an authorized distributor/dealer for service
Over Crank ShutdwnOvercrank shutdownThe engine was not successfully started after the completion of the last crank cycle plus the 15 second delay.ShutdownCheck fuel supply. Check cranking circuit. Check cranking battery. Troubleshoot engine.
RBUS ComError WarningRBUS communication error warningThe controller has lost communications with a PIM or load management device that had previously been communicating properly.WarningCheck connection to the PIM or load management device.
Spd Sens Flt ShutdwnSpeed sensor fault shutdownThe controller, or the ECM, shutdown the generator because the speed signal was lost.ShutdownCheck speed sensor and circuitry to ECM.
Speed Sensor FaultSpeed Sensor FaultEngine speed sensor has failed or engine stalled.ShutdownContact an authorized distributor/dealer for service.
Total Power High ShtDwnTotal Power High ShutdownMeasured load is greater than 102% of the generator set power rating for more than 1 minute.ShutdownReduce the load.
Volts L1-L2 High ShutdwnVolts L1-L2 high shutdownVoltage measured from Phase A to Phase B exceeded the high limit for a time greater than the delay setting (default 2 seconds).ShutdownTroubleshoot alternator; see alternator service manual.
Volts L1-L2 Low ShutdwnVolts L1-L2 low shutdownVoltage measured from Phase A to Phase B was greater than 5% of rated but less than the low voltage setting for a time greater than the delay setting (default 10 seconds).ShutdownTroubleshoot alternator; see alternator service manual.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Engine Speed Governor Settings adjustment

Tools: RDC2 controller keypad or SiteTech software

  1. Adjust the Engine Speed Adjustment (range 0 to 99; default 50) from the front panel or SiteTech.
  2. Calculate resulting speed: (System Frequency x 30) + (Setting - 50) = RPM.
  3. Note that Engine Speed Gain Adjustment has no effect (gain controlled by engine ECM).
Procedure to Change Settings adjustment

⚠ Use caution when navigating the controller menus; in some menus pressing the Select button can enable editing of the controller settings.

  1. Press the Select button to enter the main menu.
  2. Press the down arrow button until the desired menu is displayed.
  3. Press the Select button to enter the selected menu.
  4. Press the down arrow button to step through the parameters in the selected menu.
  5. To change a setting, press the Select button; the selected setting flashes.
  6. Press the up or down arrow buttons to increase or decrease the setting.
  7. When the desired setting is shown, press Select; the value stops flashing.
  8. Repeat steps 5 through 7 for each setting on the screen.
  9. Press the down arrow to step to the next screen.
  10. To exit, press the down arrow button until Return is displayed and press Select.
  11. Press the AUTO or OFF button to exit the main menu.
RDC2 Voltage Calibration Using SiteTech adjustment

Tools: digital voltmeter, personal computer, SiteTech software

  1. Connect PC to controller via USB
  2. With generator off, connect multimeter across L1/L2 (AC volts)
  3. Start generator set
  4. Compare voltmeter reading to controller display
  5. Calculate new Genset Calibration Factor Voltage using (Vmeter / Vcontrol) x Fold = Fnew
  6. Enter new value into SiteTech and click Apply Changes
  7. Verify voltmeter matches controller display
  8. Repeat for L2-L3 and L3-L1 if three-phase
  9. Press OFF to stop generator set
RDC2 Voltage Calibration Using the Controller Keypad adjustment

Tools: digital voltmeter

  1. With generator off, connect digital multimeter across L1 and L2, set to AC volts
  2. Start generator set with RUN button
  3. Navigate to Generator Metering menu, press Select; Volts L1-L2 displayed
  4. Press Select; voltage number flashes
  5. Use up/down arrows to match voltmeter reading
  6. Press Select to confirm
  7. Step to Return screen
  8. Press OFF to stop generator set
VSC Current (Load) Calibration Using the Controller Keypad adjustment

Tools: clamp-on DC current probe or DC current meter

  1. Connect DC current probe/clamp meter to measure generator current
  2. Start generator with RUN button
  3. Adjust system voltage to obtain rated current output with battery bank attached (or use load bank)
  4. Trip output breaker
  5. Navigate to Generator Metering menu, select Generator Load
  6. Press and hold Select for No-Load Calibration; verify breaker open, confirm Yes
  7. Close output breaker; verify rated output current, confirm Yes
  8. Verify displayed load is correct; recalibrate if necessary
  9. Press OFF to stop generator set
Voltage Calibration Using SiteTech adjustment

⚠ Testing live electrical circuits. Hazardous voltage or current will cause severe injury or death.

Tools: Digital voltmeter, Personal computer with SiteTech, USB cable

  1. With generator off, connect a digital multimeter across L1 and L2 (AC volts).
  2. Start the generator set by pressing RUN.
  3. Compare the voltmeter reading to the controller-displayed voltage.
  4. Calculate a new value: (Vmeter / Vcontrol) x Fold = Fnew.
  5. Enter the new Genset Calibration Factor Voltage L1-L2 in SiteTech and click Apply Changes.
  6. Wait a few seconds and re-compare voltmeter and controller readings.
  7. Press OFF to stop the generator set.
  8. Repeat for L2-L3 and L3-L1 if necessary (three-phase only).
Voltage Calibration using the RDC2 Controller Keypad and Menus adjustment

⚠ Testing live electrical circuits. Hazardous voltage or current will cause severe injury or death.

Tools: Digital voltmeter, RDC2 controller keypad

  1. With generator off, connect a digital multimeter to measure output voltage across L1 and L2 (AC volts).
  2. Start the generator set by pressing RUN.
  3. Navigate to the Generator Metering menu.
  4. Display Volts L1-L2 and compare with the voltmeter reading.
  5. Press Select; the voltage flashes. Adjust with up/down arrows to match the voltmeter.
  6. Press Select to save; wait 30 to 60 seconds for the reading to stabilize.
  7. For three-phase models, repeat for L2-L3 and L3-L1.
  8. Step down to Return and press Select to exit.
  9. Press OFF to stop the generator set.
Fuel Valve Operation Test Procedure diagnostic

⚠ Explosive fuel vapors. Use extreme care when handling, storing, and using fuels.

Tools: 12 VDC power source

  1. Disconnect the positive (+) battery lead from the gas valve terminal.
  2. Apply 12 VDC to the gas valve terminal and listen for an audible click indicating actuation.
  3. Repeat steps 1 and 2 on the second solenoid valve.
  4. Replace the gas valve if either valve does not actuate in step 2.
LED Optic Board Test Procedure diagnostic

⚠ Testing the photo transistor circuit board. Hazardous voltage will cause severe injury or death. Do not expose the photo transistor board to external light.

⚠ Disconnecting the electrical load. Hazardous voltage will cause severe injury or death.

Tools: Flashlight, Voltmeter, Black electrical tape

  1. Remove the enclosure rear panel from the generator end.
  2. Remove the LED optic board and holder.
  3. With the generator running at no load, shine a flashlight at the exposed photo transistor.
  4. Observe AC output voltage; high output indicates the FRX activator board is functioning, and voltage should drop when the flashlight is removed.
  5. If high voltage exists with the flashlight off, stop the unit and tape over the photo transistor; restart to check for external light.
  6. With the generator running at no load, approximately 1--2 volts DC should be observed at 3B (+) and 5B (--) at the LED optic board.
  7. Shine the flashlight; the DC voltage reading should drop.
  8. Stop the generator set.
Procedure to Reset the Controller after a Fault Shutdown diagnostic

⚠ Always identify and correct the cause of a fault shutdown before resetting the controller.

  1. Press the Select button to go to the Overview menu.
  2. Press Select again; the active fault is displayed.
  3. Press Select; Confirm Clear Fault: NO is displayed.
  4. Press the Up arrow button; Confirm Clear Fault: YES is displayed.
  5. Press the Select button to enter YES and clear the fault.
  6. Press the Select button to return to the overview menu.
  7. Press AUTO to put the generator set into automatic mode.
Temperature Sensor Test Procedure diagnostic

Tools: Ohmmeter

  1. Press OFF to stop the generator set and allow it to cool.
  2. Disconnect the temperature sensor and measure resistance across it with an ohmmeter; resistance varies with temperature per Figure 6-11.
  3. If resistance is very low (short) or very high (open), replace the sensor.
12-Lead Generator Reconnection installation

⚠ Disconnect battery cables before working on the generator set, negative lead first

Tools: digital multimeter (DVM), voltmeter

  1. Press OFF on the RDC2 controller
  2. Disconnect engine starting battery, negative lead first
  3. Disconnect utility power to the generator set
  4. Verify line circuit breaker is sized correctly for new voltage/amperage; replace if necessary
  5. Select desired voltage connection and connect leads per diagram
  6. Reconnect engine starting battery, negative lead last
  7. Enter the RDC2 Genset System menu; check and change system voltage, frequency, and phase settings
  8. Connect a digital multimeter to the generator set output
  9. Press RUN to start the generator set
  10. Use a voltmeter to check for correct voltage output; calibrate per Section 3.5 if necessary
  11. Press OFF to stop the generator set
  12. Reconnect utility power
  13. Press AUTO to place the generator set in automatic mode

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
LPG ConfigurationConnect lead 49 to lead N17 (ground)Change fuel type in Genset System menu on RDC2 controller
Natural Gas ConfigurationDisconnect lead 49 from N17Change fuel type in Genset System menu on RDC2 controller
3Delta, Low Wye, High Wye, Dogleg12-lead reconnectable alternator4-lead alternators are not reconnectable. Setting system voltage above 300 VAC automatically switches the controller from low wye to high wye.
100/2001Single
100/2003Delta
110/2201Single
110/2203Delta
115/2301Single
1201SingleGenset System Voltage/Frequency/Phase table for controller setup
120/2083Three-Phase Wye
120/2083Wye
120/2401Single
120/2401Single Phase
120/2403Delta
120/2403Three-Phase Delta
127/2203Three-Phase Wye
127/2203Wye
2201Single
220/3803Three-Phase Wye
220/3803Wye
2301Single
230/4003Three-Phase Wye
230/4003Wye
2401Single
240/4163Three-Phase Wye
240/4163Wye
277/4803Three-Phase Wye
277/4803Wye

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Kohler KG6208 6.2L?

The Kohler KG6208 6.2L engine has an oil capacity of 7.1 liters.

What is the displacement of the Kohler KG6208 6.2L?

The Kohler KG6208 6.2L has a displacement of 6.2 liters with 6 cylinders.

Which generators use the Kohler KG6208 6.2L engine?

The Kohler KG6208 6.2L powers 4 generator set(s), including Kohler 48RCLC, Kohler 60RCLA, Kohler 60RCLB, Kohler KG60.

How often should you change the oil in the Kohler KG6208 6.2L?

The Kohler KG6208 6.2L oil change interval is every 500 hours.

What is a common problem with the Kohler KG6208 6.2L engine?

A commonly reported issue on generators using the Kohler KG6208 6.2L is: The generator set does not crank.. Cause: Battery weak or dead, Battery connections reversed or poor, Blown fuse(s). Fix: Recharge or replace the battery, Check the connections, Replace the fuse. Contact an authorized Kohler distributor/dealer for service if fuse blows repeatedly.