| AC Sens Loss Shutdwn | Loss of AC sensing shutdown | Less than 5% of rated voltage measured on Phase A (or B or C if 3 phase) for 3 seconds, only in AUTO, only after acceptable voltage (> 5% of UV setting) has been detected. | Shutdown | Check for loose wiring and connections. Check all AC leads. Troubleshoot alternator. |
| AC Sens Loss Warning | Loss of AC sensing warning | Less than 5% of rated voltage measured on Phase A (or B or C on 3 phase), for 1 second, 10 seconds after crank disconnect. | Warning | Check for loose wiring and connections. Check all AC leads. Troubleshoot alternator. |
| AC Sens Lost | AC Sensing Lost | In Auto mode, generator output AC sensing is lost; starts 10 seconds after crank disconnect. Warning after 1 sec if no output detected; shutdown after 3 sec if voltage was present then lost. | Warning | Contact an authorized distributor/dealer for service. |
| ATS Com Error | ATS Communication Error | Warning is displayed if RXT interface connection is lost. | Warning | Check communication wiring between transfer switch interface board and generator set. |
| ATS ComError Warning | ATS communication error | The controller has lost communications with the RXT ATS that had previously been communicating properly. | Warning | Check connection to ATS module. |
| ATS Fail Xfr Warning | ATS fail to transfer | The RXT ATS has reported a fail to transfer; the digital output for ATS Fail To Transfer (PIM) is active. | Warning | Consult ATS manual for troubleshooting. |
| ATS PhaseRot | ATS Phase Rotation Mismatch | Transfer switch phase rotation does not match; ATS will not transfer. | Warning | Correct the ATS connection. Refer to the ATS Installation manual, wiring diagrams, and labels on the transfer switch. |
| ATS PhaseRot Warning | ATS phase rotation | The RXT ATS has reported a Phase Rotation Mismatch (3 phase only) and the ATS will not transfer. | Warning | Check wiring to ATS. Consult ATS manual. |
| Accy PwrOver | Accessory Power Overload | An over current fault (short circuit) on the accessory controller power output. | Warning | Contact an authorized distributor/dealer for service. |
| Accy PwrOver Warning | Accessory Power Overload | An over current fault (short circuit) on the accessory controller power output. | Warning | Contact an authorized distributor/dealer for service |
| Alt Protect Shtdwn | Alternator Protection Shutdown | High generator current has been detected. The generator set shuts down to protect the alternator from damage caused by overheating the windings. | Shutdown | Reduce the load. |
| Aux Input | Auxiliary Input | An optional customer-connected input is closed. (Digital input from optional PIM.) | Shutdown | Check customer-supplied equipment. |
| Aux Input Shutdwn | Auxiliary input shutdown | The digital input for a custom shutdown (AuxiliaryInputShutdown - PIM) was activated (low). | Shutdown | Check customer equipment connected to the PIM module. |
| Aux Input Warning | Auxiliary input warning | The digital input for a custom warning (AuxiliaryInputWarning - PIM) is active (low). | Warning | Check customer equipment connected to the PIM module. |
| Batt Chg Flt | Battery Charger Fault | Input to PIM from an external battery charger (not the built-in charger). | Warning | Check external battery charger. |
| Batt Chg Flt Warning | Battery charger fault warning | The digital input for Battery Charger Fault Warning (PIM) is active (low). For an external battery charger only. | Warning | Check customer equipment connected to the PIM module. |
| Battery High Warning | Battery high warning | Battery voltage above the high warning setting for 10 seconds or more. | Warning | Check cranking battery. |
| Battery Low Shutdwn | Battery low shutdown | Battery voltage dropped to 11 VDC or less for 30 seconds or more, after running at least one minute. | Shutdown | Check cranking battery. Check battery charger DC output voltage from RDC2 on lead CHO to the battery. |
| Battery Low Warning | Battery low warning | Battery voltage below the low warning setting for 90 seconds or more; checked before allowing an exercise to start. | Warning | Check cranking battery. Check battery charger DC output voltage from RDC2 on lead CHO to the battery. |
| Battery Voltage High | Battery Voltage High | Engine starting battery voltage rises above 125% of the battery voltage setting for more than 10 seconds. Inhibited during the engine crank cycle. Clears when the battery voltage returns to an acceptable level. | Warning | Check the battery rating/condition and the battery charger operation |
| Battery Voltage Low | Battery Voltage Low | Engine starting battery voltage falls below the battery voltage setting (typically 12.5 volts) for more than 90 seconds when the engine is not running. Inhibited during the engine crank cycle. | Warning | Check the battery rating and condition. Check the battery charger operation. Charge or replace the battery. |
| CAN Shutdown | CAN shutdown | The ECM shut down the engine and reported an unknown fault code. | Shutdown | Troubleshoot engine operation per the engine service manual. |
| CAN comm fault | Engine CAN Communications Fault | Engine CAN communications fault. | Shutdown | Check wiring to ECM; check power to ECM |
| Chk DateTime Warning | Check date and time warning | DC power to the controller has been interrupted and the date and time may not be correct. | Warning | Verify the time and date settings. |
| Compartmnt Temp Shutdwn | Compartment temperature shutdown | Engine compartment air temperature has exceeded 174_F (79_C). | Shutdown | Troubleshoot fan circuit failure and/or temperature sensor circuit. Check for blockage of intake or exhaust vents. |
| Compartmnt Temp Warning | Compartment temperature warning | Engine compartment temperature above 167_F (75_C). | Warning | Troubleshoot fan circuit failure and/or temperature sensor circuit. Check for blockage of intake or exhaust vents. |
| Coolant Level Low Shutdwn | Coolant level low shutdown | The coolant level sensor indicated low coolant for 5 seconds or more. | Shutdown | Check coolant level and fill as needed. Check for air in cooling system. Check the coolant level sensor operation. |
| Coolant Temp High Shutdwn | Coolant temperature high shutdown | The ECM shutdown the engine and reported high coolant temperature as the fault. | Shutdown | Check engine cooling system. Check radiator fans for proper operation. Check for blockage of inlet and exhaust vents. |
| Coolant Temp High Warning | Coolant temperature high warning | The ECM is reporting high coolant temperature. | Warning | Check engine cooling system. Check radiator fans. Check for blockage of vents. |
| Coolant Temp Low Warning | Coolant temperature low warning | The ECM is reporting low coolant temperature. | Warning | Check cooling system. |
| Coolant Temp No Sig Shutdwn | Coolant temperature no signal shutdown | The ECM shutdown the engine and reported no coolant temperature signal as the fault. | Shutdown | Check cooling system and coolant level sensor circuit. |
| Default Pars Warning | Default Parameters | The controller has been loaded with default parameters. | Warning | Configure settings as needed for desired operation. |
| ECM Addr Err Shutdwn | ECM address error shutdown | There is a conflict in addressing on the ECM CAN bus. | Shutdown | Verify no other devices connected and broadcasting on the CAN bus. |
| ECM Comm Err Shutdwn | ECM communication error shutdown | Communication with the ECM was lost for 4 or more seconds. | Shutdown | Check CAN communication wiring between controller and ECM. |
| ECM Mismatch Shutdwn | ECM mismatch shutdown | The ECM does not match any of the supported models. | Shutdown | Verify controller configuration using SiteTech. Consult local service technician. |
| Emerg Stop Shutdwn | Emergency stop shutdown | The emergency stop circuit was tripped (open circuit). | Shutdown | Check E-stop circuit for open switches, broken wires, disconnected wires, etc. |
| Engine Coolant Temperature High | Engine Coolant Temperature High | Engine coolant temperature exceeds the maximum temperature for more than 5 seconds. Function becomes active after crank disconnect. | Shutdown | Check for blocked air inlets and exhaust outlets. |
| Engine Oil Pressure Low | Engine Oil Pressure Low | The engine ECM indicates low oil pressure for more than 5 seconds. Function becomes active 30 seconds after crank disconnect. Does not protect against low oil level. | Shutdown | Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. |
| Engine Speed High Shutdwn | Engine speed high shutdown | Engine speed, as calculated from AC frequency, was above the high speed setting for 0.3 seconds or more; or the ECM reported overspeed. | Shutdown | Troubleshoot engine operation per the engine service manual. |
| Engine Speed Low Shutdwn | Engine speed low shutdown | After crank disconnect, engine speed was below the low speed setting for 3 seconds or more. | Shutdown | Troubleshoot engine operation per the engine service manual. |
| EngineSpeed High | Engine Speed High | Engine speed exceeds 115% of the normal running speed for more than 0.3 seconds. | Shutdown | Contact an authorized distributor/dealer for service. |
| EngineSpeed Low | Engine Speed Low | Engine speed drops below 85% of the normal running speed for more than 3 seconds. | Shutdown | Reduce the load; contact an authorized distributor/dealer for service |
| Exer Not Sch | Exercise Not Scheduled | No exercise has been scheduled on the RDC2 controller. | Warning | See Section 2.5 for instructions to set the exerciser. |
| Exer Not Sch Warning | Exercise not scheduled warning | There is no exercise scheduled. | Warning | Set the exercise schedule. |
| Frequency High Shutdwn | Frequency high shutdown | Frequency measured on Phase A exceeded the high frequency setting for 10 seconds, 10 seconds or more after crank disconnect. | Shutdown | Troubleshoot engine operation per the engine service manual. |
| Frequency Low Shutdwn | Frequency low shutdown | Frequency measured on Phase A was less than the low limit for 10 seconds, or 10 Hz or more below rated for 60 seconds or more, 10 seconds or more after crank disconnect. | Shutdown | Troubleshoot engine operation per the engine service manual. |
| Fuel Leak Shutdwn | Fuel leak shutdown | The digital input for Fuel Tank Leak Shutdown (PIM) was activated (low). | Shutdown | Check customer equipment connected to the PIM module. |
| Fuel Leak Warning | Fuel leak warning | The digital input for Fuel Tank Leak Warning (PIM) is active (low). | Warning | Check customer equipment connected to the PIM module. |
| Fuel Level Low Shutdwn | Fuel level low shutdown | The digital input for Low Fuel Level Shutdown (PIM) was activated (low). | Shutdown | Check customer equipment connected to the PIM module. |
| GenBrkerOpen Warning | Generator Circuit Breaker Open | There is voltage at the generator set but no voltage measured on the emergency side of the ATS (Model RXT transfer switch). | Warning | Check line circuit breaker. Check for and correct short circuits or overloading on the load side before resetting the circuit breaker. |
| Generator Frequency High | Generator Frequency High | Governed frequency exceeds 110% of the system frequency setpoint for more than 10 seconds. Function becomes active 10 seconds after engine start. | Shutdown | Contact an authorized distributor/dealer for service. |
| Generator Frequency Low | Generator Frequency Low | Governed frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below the system frequency setting for more than 60 seconds. Function becomes active 10 seconds after engine start. | Shutdown | Reduce the load and restart; contact an authorized distributor/dealer for service |
| Generator Voltage L1-L2 High | Generator Voltage High | Output voltage exceeds 120% of the system nominal voltage for more than 2 seconds. | Shutdown | Contact an authorized distributor/dealer for service. |
| Generator Voltage L1-L2 Low | Generator Voltage Low | Output voltage falls below 80% of the nominal system voltage for more than 10 seconds. | Shutdown | Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service. |
| Generator VoltageL1-L2 High | Generator Voltage High | Output voltage exceeds 120% of the system nominal voltage for more than 2 seconds. | Shutdown | Contact an authorized distributor/dealer for service |
| Generator VoltageL1-L2 Low | Generator Voltage Low | Output voltage falls below 80% of the nominal system voltage for more than 10 seconds. | Shutdown | Reduce the load and restart; contact an authorized distributor/dealer for service |
| Ground Fault Warning | Ground fault warning | The digital input for Ground Fault Warning (PIM) is active (low). | Warning | Check customer equipment connected to the PIM module. |
| Lo Crank Vlt | Low Cranking Voltage | Battery voltage falls below 60% of system battery voltage for more than 6 seconds while the starter is engaged. | Warning | Charge or replace the battery. |
| Lo Crank Vlt Warning | Low cranking voltage warning | During cranking, battery voltage less than 60% (7.2V or 14.4V) for 6 seconds or more during cranking. | Warning | Check cranking battery. |
| Locked Rotor | Locked Rotor | No engine rotation sensed during cranking; shuts down 3 seconds after fault detected. | Shutdown | Check the battery; check for loose connections; contact an authorized distributor/dealer for service |
| Locked Rotor Shutdwn | Locked rotor shutdown | No rotation of the engine or alternator was detected for 3 seconds or more during cranking. | Shutdown | Check cranking circuit. Troubleshoot the engine. Check alternator connections to controller and auxiliary winding circuit breaker. Troubleshoot the alternator. |
| MainPwrOverL Shutdown | Main Power Overload Shutdown | Over current fault on the controller power output (short circuit). | Shutdown | Contact an authorized distributor/dealer for service. |
| MainPwrOverL Shutdwn | Main power overload shutdown | The internal current limit circuit has tripped, indicating an overcurrent condition on the DC power supply circuit. | Shutdown | Check crank, run, and flash relay circuits for short circuits. |
| Not In Auto Warning | Not in auto warning | The RDC2 controller is not in AUTO; the generator will not start from an ATS or remote device. | Warning | Press the Auto button to ensure automatic system operation. |
| Not in Auto | Not in Auto | The generator set is not in Automatic (standby) mode. Remote start and stop commands from a transfer switch or remote switch will be ignored. | Warning | Press AUTO to place the generator set in Automatic mode, when appropriate. |
| OB1 CommLoss | Option board 1 communication loss | Communications with option board #1 (PIM, load management device, or RXT) has been lost. | Warning | Check RBUS wiring to inoperative option board. |
| OB2 CommLoss | Option board 2 communication loss | Communications with option board #2 has been lost. | Warning | Check RBUS wiring to inoperative option board. |
| OB3 CommLoss | Option board 3 communication loss | Communications with option board #3 has been lost. | Warning | Check RBUS wiring to inoperative option board. |
| OB4 CommLoss | Option board 4 communication loss | Communications with option board #4 has been lost. | Warning | Check RBUS wiring to inoperative option board. |
| Oil Pressure Low Shutdwn | Oil pressure low shutdown | The ECM shutdown the engine and reported low oil pressure as the fault. | Shutdown | Check for oil leaks. Check the oil level and add oil if low. Check the oil pressure sensor. |
| Oil Pressure Low Warning | Oil pressure low warning | The ECM is reporting a low oil pressure warning. | Warning | Check the oil level and add oil if low. Check the oil pressure sensor. |
| Oil Pressure No Sig Shutdwn | Oil pressure no signal shutdown | The ECM shutdown the engine and reported no oil pressure signal as the fault. | Shutdown | Check engine oil pressure sensor and wiring to the ECM. Troubleshoot engine. |
| Over Crank | Over Crank | Three unsuccessful starting attempts. | Shutdown | Check the fuel supply, spark plug, and battery; check for loose connections; contact an authorized distributor/dealer for service |
| Over Crank Shutdwn | Overcrank shutdown | The engine was not successfully started after the completion of the last crank cycle plus the 15 second delay. | Shutdown | Check fuel supply. Check cranking circuit. Check cranking battery. Troubleshoot engine. |
| RBUS ComError Warning | RBUS communication error warning | The controller has lost communications with a PIM or load management device that had previously been communicating properly. | Warning | Check connection to the PIM or load management device. |
| Spd Sens Flt Shutdwn | Speed sensor fault shutdown | The controller, or the ECM, shutdown the generator because the speed signal was lost. | Shutdown | Check speed sensor and circuitry to ECM. |
| Speed Sensor Fault | Speed Sensor Fault | Engine speed sensor has failed or engine stalled. | Shutdown | Contact an authorized distributor/dealer for service. |
| Total Power High ShtDwn | Total Power High Shutdown | Measured load is greater than 102% of the generator set power rating for more than 1 minute. | Shutdown | Reduce the load. |
| Volts L1-L2 High Shutdwn | Volts L1-L2 high shutdown | Voltage measured from Phase A to Phase B exceeded the high limit for a time greater than the delay setting (default 2 seconds). | Shutdown | Troubleshoot alternator; see alternator service manual. |
| Volts L1-L2 Low Shutdwn | Volts L1-L2 low shutdown | Voltage measured from Phase A to Phase B was greater than 5% of rated but less than the low voltage setting for a time greater than the delay setting (default 10 seconds). | Shutdown | Troubleshoot alternator; see alternator service manual. |