The Kohler KD Series is an engine. It powers generator sets from Kohler, including the KD1250-4 and KD800.
Also known as: KOHLER KD Series
Compiled from service & troubleshooting documentation across every generator set that uses the Kohler KD Series.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Generator set exercise (loaded) | Test | 12 hr | After 12 hours cumulative low-load operation or at minimum once annually; 30-60 minutes loaded maintaining rated exhaust temperature 30 min minimum | |
| Fan bearing lubrication (KD2000-KD4000) | Lubricate | 500 hr | 500 Hrs. | |
| Fan belt(s) | Check | 500 hr | 12 mo | Yearly or 500 Hrs.; replace as necessary; follow engine manual |
| Fuel prefilter(s) | Replace | 500 hr | 24 mo | 2 Years or 500 Hrs.; follow engine manual |
| Main fuel Filter(s) | Replace | 1000 hr | 24 mo | 2 Years or 1000 Hrs.; follow engine manual |
| Water pump and alternator belts | Check | 2000 hr | 24 mo | 2 Years or 2000 Hrs.; replace as necessary; follow engine manual |
| Air cleaner service | Replace | 3000 hr | 24 mo | 2 Years or 3000 Hrs.; follow engine manual |
| DEF tank vent filter | Replace | 3000 hr | 24 mo | 2 Years or 3000 Hrs.; follow engine manual |
| Coolant, replace | Replace | 6000 hr | 48 mo | 4 Years or 6000 Hrs.; follow engine manual |
| AC electrical system, safety and alarm operation | Test | 6 mo | 6 Months; check | |
| Battery charger operation, charge rate | Check | 1 mo | Monthly | |
| Battery electrolyte level | Check | 1 mo | Monthly; not necessary with AGM batteries | |
| Battery recharge after engine start | Check | 1 mo | Monthly | |
| Battery specific gravity, charge state | Test | 1 mo | Monthly; not necessary with AGM batteries | |
| Circuit breakers, fuses | Inspect | 1 mo | Monthly; replace as necessary; do not break manufacturer's seals | |
| Clean and tighten battery terminals | Clean | 3 mo | Quarterly; check | |
| Coolant temperature | Test | 6 mo | 6 Months; follow engine manual | |
| Crankcase breather filter(s) | Replace | 3 mo | Quarterly; follow engine manual | |
| DEF fill neck filter | Inspect | 12 mo | Yearly; check; replace as necessary | |
| DEF suction module filter | Inspect | 12 mo | Yearly; check; replace as necessary | |
| Exhaust flexible connector(s) | Inspect | 6 mo | 6 Months | |
| Generator set exercise (extended) | Test | 4 mo | Conscious Care extended exercise; period must not exceed 4 months | |
| Generator set exercise (no-load/low-load) | Test | 1 mo | Conscious Care; minimum 10 minutes; period between exercise intervals must not exceed 1 month | |
| On-Load Test | Test | 12 mo | Yearly; perform loaded operation 30-60 minutes | |
| RTC Battery, APM802 | Replace | 36 mo | APM802, 3 Years; service by authorized Rehlko service representative | |
| Remove corrosion, clean and dry battery and rack | Clean | 1 mo | Monthly | |
| Start Test (monthly exercise with Conscious Care™) | Test | 1 mo | Monthly | |
| Tighten DC electrical connections | Other | 6 mo | 6 Months; tighten |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | 10 in. weld flange bolt circle diameter B | 361.95 | mm (14.25 in.) | |
| Other | 10 in. weld flange outside diameter C | 406.4 | mm (16.0 in.) | |
| Other | 10 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 12 in. weld flange bolt circle diameter B | 431.80 | mm (17.00 in.) | |
| Other | 12 in. weld flange outside diameter C | 482.6 | mm (19.0 in.) | |
| Other | 12 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 14 in. weld flange bolt circle diameter B | 476.25 | mm (18.75 in.) | |
| Other | 14 in. weld flange outside diameter C | 533.4 | mm (21.0 in.) | |
| Other | 14 in. weld flange quantity of bolts / bolt hole diameter D | 12, 28.58 | mm (1.13 in.) | |
| Other | 16 in. weld flange bolt circle diameter B | 539.75 | mm (21.25 in.) | |
| Other | 16 in. weld flange outside diameter C | 596.9 | mm (23.5 in.) | |
| Other | 16 in. weld flange quantity of bolts / bolt hole diameter D | 16, 28.58 | mm (1.13 in.) | |
| Other | 18 in. weld flange bolt circle diameter B | 577.85 | mm (22.75 in.) | |
| Other | 18 in. weld flange outside diameter C | 635.0 | mm (25.0 in.) | |
| Other | 18 in. weld flange quantity of bolts / bolt hole diameter D | 16, 31.75 | mm (1.25 in.) | |
| Other | 20 in. weld flange bolt circle diameter B | 635.00 | mm (25.00 in.) | |
| Other | 20 in. weld flange outside diameter C | 698.5 | mm (27.5 in.) | |
| Other | 20 in. weld flange quantity of bolts / bolt hole diameter D | 20, 31.75 | mm (1.25 in.) | |
| Other | 5 in. weld flange bolt circle diameter B | 215.90 | mm (8.50 in.) | |
| Other | 5 in. weld flange outside diameter C | 241.30 | mm (9.50 in.) | |
| Other | 5 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 6 in. weld flange bolt circle diameter B | 254.0 | mm (10.0 in.) | |
| Other | 6 in. weld flange outside diameter C | 279.4 | mm (11.0 in.) | |
| Other | 6 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 8 in. weld flange bolt circle diameter B | 298.45 | mm (11.75 in.) | |
| Other | 8 in. weld flange outside diameter C | 342.9 | mm (13.5 in.) | |
| Other | 8 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | Alternator thermal protection time delay at 200% rated current | 40 | seconds | 200% rated current |
| Other | Alternator thermal protection time delay at 300% rated current | 10 | seconds | 300% rated current |
| Other | Alternator thermal protection time delay at 425% rated current | 5 | seconds | 425% rated current |
| Other | Alternator thermal protection time delay at 950% rated current | 1 | second | 950% rated current |
| Other | Battery acid cleanup solution | 500 g (1 lb.) bicarbonate of soda to 4 L (1 gal.) water | ||
| Other | Controller power draw | 400 | mAmps at 24VDC | |
| Other | Controller power draw | 800 | mAmps at 12VDC | |
| Other | Coolant sample bottle minimum volume | 250 | ml (8.5 oz.) | if no laboratory-supplied bottle |
| Other | Coolant sample volume | 1 | liter (1 qt.) | collect after allowing about one liter to flow out |
| Other | DEF filter fill volume | 2/3 | full with DEF | to help prime DEF system |
| Other | Fan bearing grease | Lithium grease with EP additive, NLGI 2 | suitable for -28°C to +121°C (-20°F to +250°F) | |
| Other | Grease quantity 1-1/2 in. to 1-11/16 in. shaft | 9.5 (.32) | ml (Oz.) | approximate quantity |
| Other | Grease quantity 1-1/8 in. to 1-1/4 in. shaft | 3.0 (.10) | ml (Oz.) | approximate quantity |
| Other | Grease quantity 1-3/4 in. to 2 in. shaft | 14.8 (.50) | ml (Oz.) | approximate quantity |
| Other | Grease quantity 1-3/8 in. to 1-7/16 in. shaft | 6.5 (.22) | ml (Oz.) | approximate quantity |
| Other | Grease quantity 2 in. to 2-3/16 in. shaft | 16.3 (.55) | ml (Oz.) | approximate quantity |
| Other | Grease quantity 2-1/4 in. to 2-1/2 in. shaft | 19.2 (.65) | ml (Oz.) | approximate quantity |
| Other | Grease quantity 2-11/16 in. to 3 in. shaft | 25.1 (.85) | ml (Oz.) | approximate quantity |
| Other | Grease quantity 3-15/16 in. to 4 in. shaft | 74.0 (2.50) | ml (Oz.) | approximate quantity |
| Other | Grease quantity 3-3/16 in. to 3-1/2 in. shaft | 37.0 (1.25) | ml (Oz.) | approximate quantity |
| Other | Grease quantity 4-15/16 in. to 5 in. shaft | 140.5 (4.75) | ml (Oz.) | approximate quantity |
| Other | Grease quantity 4-7/16 in. to 4-1/2 in. shaft | 91.7 (3.10) | ml (Oz.) | approximate quantity |
| Other | Oil sample bottle minimum volume | 125 | ml (4.3 oz.) | if no laboratory-supplied bottle |
| Other | RTC battery life APM603 | 10 years powered; 2 years not powered | ||
| Other | RTC battery life APM802 | 3 years | powered by engine battery | |
| Other | Restriction gauge installation wrench | 16 | mm | use to install or remove restriction gauge |
| Other | Weld flange angle A (10, 12, 14 in. nominal pipe size) | 30 | deg. | |
| Other | Weld flange angle A (16, 18, 20 in. nominal pipe size) | 22.5 | deg. | |
| Other | Weld flange angle A (5, 6, 8 in. nominal pipe size) | 45 | deg. | |
| Speed | Fan belt tension KD2000-KD2500 High Ambient New Belt (10301001101-MA4 Module) | 67.4-69.7 | Hz | New Belt; deflection 58.7-62.7 N @ 9 mm (13.1-14.0 lbs @ 0.4 in.) |
| Speed | Fan belt tension KD2000-KD2500 High Ambient Used Belt | 62.4-64.9 | Hz | Used Belt; deflection 50.8-54.8 N @ 9 mm (11.4-12.3 lbs. @ 0.4 in.) |
| Speed | Fan belt tension KD2000-KD2500 Low Ambient New Belt (10301001101-MA3 Module) | 61.5-63.7 | Hz | New Belt; deflection 51.1-54.5 N @ 9 mm (11.5-12.2 lbs @ 0.4 in.) |
| Speed | Fan belt tension KD2000-KD2500 Low Ambient Used Belt | 57.0-59.3 | Hz | Used Belt; deflection 44.2-47.6 N @ 9 mm (9.9-10.7 lbs. @ 0.4 in.) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Def | ISO 22241-4 | Fill neck uses ISO 22241-4 fill nozzle with 190-micron filter. Store in locked cabinet. | |||
| Grease | Lithium grease with EP additive, NLGI 2 | -28°C to 121°C | For radiator fan bearings (KD2000-KD4000). Discontinue re-lubrication when clean grease purges through seal. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 0 | Water In Fuel | Severely High | Shutdown | |
| 1 | Fuel Supply Pressure | Severely Low | Warning | |
| 15 | Crankcase Pressure | High | Warning | |
| 16 | Aftertreatment SCR Common Rail DEF Pressure | Moderately High | Shutdown | |
| 17 | Oil Pressure | Low | Warning | |
| 2 | Barometric Pressure | Plausibility | Warning | |
| 3 | Fuel Supply Pressure | Shorted High | Warning | |
| 31 | Fuel Supply Pressure | Condition Exists | Warning | |
| 4 | Fuel Supply Pressure | Shorted Low | Warning | |
| M3.212 | APM INTERNAL BATTERY WARNING | Battery power is low on APM802 controller | Warning | Have an authorized Rehlko service representative service the controller. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ Hazardous voltage. Moving parts. Operate only when all guards and electrical enclosures are in place.
Tools: sonic tension meter, wrench
⚠ Sulfuric acid in batteries. Wear protective goggles and clothing.
Tools: wire brush
⚠ Hot coolant and steam. Stop generator set and allow to cool before removing pressure cap.
⚠ Hot coolant and steam. Do not add coolant to a hot engine.
⚠ Handling diesel exhaust fluid. Can cause skin, eye, respiratory irritation.
Tools: strap wrench or filter wrench, anti-static gloves, goggles
⚠ Explosive fuel vapors. Use extreme care when handling fuels.
⚠ Hazardous voltage. Moving parts. Operate only when all guards and electrical enclosures are in place.
Tools: grease gun
⚠ Explosive fuel vapors. Use extreme care when handling fuels.
Tools: strap wrench or filter wrench
Tools: Flash drive, PC (spreadsheet program)
⚠ Have setup and adjustments performed only by an authorized Kohler distributor.
⚠ The access level login expires after 1 hour.
Tools: External flash drive, SiteTech software, PC
⚠ Hazardous voltage. Moving parts. Operate only when all guards and electrical enclosures are in place.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The Kohler KD Series powers 2 generator set(s), including Kohler KD1250-4, Kohler KD800.
A commonly reported issue on generators using the Kohler KD Series is: APM INTERNAL power BATTERY WARNING.