Kohler CH1006 Engine

The Kohler CH1006 is a 1 L 2-cylinder natural engine rated at 3600 rpm, producing up to 26.1 kW. It powers generator sets from Kohler, including the 26RCA. It holds 1.9 L (0.5 gal) of oil.

Also known as: Kohler CH1006

0.999 L
Displacement
2
Cylinders
3600 rpm
Rated speed
26 kW
Gross power

Engine specifications

Oil capacity1.9 L
Displacement0.999 L
Cylinders2
AspirationNatural
Rated speed3600 rpm
Gross power26 kW

Common problems

15
  • This generator has absorbed more than 25% reactive power (magnetic excitation current) for 20 seconds. LossOfField
    Cause: Generator voltage on this generator is not calibrated correctly. Generator voltage on other generator is not calibrated correctly. Bus voltage on this generator is not calibrated correctly. Bus voltage on the other generator is not calibrated correctly.
  • This generator does not know if the metering is connected or the orientation of the connection. This means that the generators can’t share load accurately until this information is known. MeterUnknown
    Cause: System commissioning and startup not yet complete. See the APM instructions.
  • The two generators that are intended to be paralleled have incompatible model numbers. CfgModelNum
    Cause: Incorrect configuration of one of the generators. Different generator types. The paralleled generator sets must be the same kW model. (i.e. two 14 kW or two 20 kWor 26 kW models).
  • The system voltage of the two generators intended to be paralleled is not the same. CfgSysVolt
    Cause: One of the two generators is incorrectly configured. Intermittent connections on RBUS network wiring.
  • The primary controller has lost communication with the secondary controller. (A secondary controller was detected, then communication was lost.) LossOfComm2
    Cause: RBUS disconnected, secondary controller battery disconnected, updating firmware in secondary controller, or intermittent RBUS connections.
  • The power metering on this controller gives a signal that is not consistent with the system configuration. Reversing the power direction does not resolve the problem. ErraticSig
    Cause: Bad wiring to the CT. Too much tension on wires from the CT to the controller.
  • The generator has verified that the metering is connected correctly and that the direction is consistent with expected power direction. MeteringOk
    Cause: Status message indicates that the CT is connected to the generator correctly.
  • The generator has been attempting to synchronize for over 2 minutes without success. SyncFailure
    Cause: Generator is hunting. Advanced speed control settings need adjustment. Load is changing frequently to disturb the online generator.
  • The generator has applied load (using the other generator) and has observed no current on the power sensing inputs. NoCurrent
    Cause: The CT is not connected to the controller. The output leads from the generator do not go through the CT in the correct direction. See the APM instructions.
  • The bus is measured to be live when no generators are connected to it (both contactors open). BusLiveDead
    Cause: Bus metering V9A and V9B connections to V9 of paralleling protection harness are connected incorrectly.
  • The bus is measured to be dead when one of the generators is supposed to be supplying voltage to the bus (closed contactor). BusDeadLive
    Cause: Bus metering V9A and V9B connections to V9 of paralleling protection harness are connected incorrectly.
  • The Automatic Paralleling Module has stopped communicating on RBUS. (An APM was detected on the RBUS network but is no longer communicating). LossOfComAPM
    Cause: APM is unplugged. Primary controller is powered down. Check the battery connections. See previous page for more information. Intermittent connections on RBUS network wiring.
  • Successful auto-discovery of APM connections. ContactorOk
    Cause: Auto-discovery was activated by placing other generator in OFF and this generator in RUN.
  • Short circuits can cause bodily injury and/or equipment damage.
    Fix: Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (–) lead first when disconnecting the battery. Reconnect the negative (–) lead last when reconnecting the battery. Never connect the negative (–) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
  • Failure to Auto-Discover APM connections. ConCheckFail
    Cause: Wires 9A and 9B crossed between the generators. Wires 9A or 9B not connected.

Compiled from service & troubleshooting documentation across every generator set that uses the Kohler CH1006.

Maintenance schedule

ItemSpecCapacityPart #Interval
Oil filterCartridge type

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

20
ItemActionHoursMonthsNotes
Oil level, 14 kW modelsCheck8 hrEvery 8 hours of engine operation
Oil level, 20 kW modelsCheck8 hr
Oil level, 26 kW modelsCheck24 hr
Brushes and collector ringInspect300 hr12 moAuthorized dealer only; Yearly or 300 hours
Wire-cable insulation conditionInspect500 hr36 mo3 years or 500 hours
Air ducts, louversClean12 moYearly
Battery and rack corrosionClean12 moYearly
Battery charger operation, charge rateCheck1 moMonthly
Battery electrolyte level and specific gravityCheck12 moNot necessary for maintenance-free batteries; Yearly
Battery terminals and bootsClean12 moYearly
Control and power wiring connectionsCheck12 moTighten; Yearly
Exhaust insulation, fire hazardsInspect12 moYearly
Flexible fuel lines and connectionsInspect3 moReplace as necessary; Quarterly
Fuel pipingInspect12 moYearly
Generator, visible wear or damageInspect3 moQuarterly
Interior of sound enclosureClean3 moQuarterly
Remote control system, if equippedTest1 moMonthly
Winding insulation resistance readings (Megger)Test36 moAuthorized dealer only, SCR assembly/rectifier and load leads disconnected; 3 years
Wire abrasions where subject to motionCheck6 mo6 months
Wiring visible wear or damageInspect3 moQuarterly

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

17
TypeItemValueUnitCondition
GapSpark plug gap0.76mm (0.030 in.)
OtherBattery wrap length1067 (42)mm (in.)
OtherBattery wrap length864 (34)mm (in.)
OtherHeater wrap rating50Watts
OtherHeater wrap rating65Watts
OtherPlug cord length75 (3)mm (in.)
OtherPower cord length1677 (66)mm (in.)
OtherPower cord length1830 (72)mm (in.)
OtherPower cord length483 (19)mm (in.)
SpeedEngine speed high shutdown115% of normal running speed for >0.3 sec
SpeedEngine speed low shutdown85% of normal running speed for >3 sec
SpeedFrequency regulation steady state0.5%%
TemperatureThermostat off temperature27C (80 F)
TemperatureThermostat on temperature16C (60 F)
TorqueSpark plug24.4-29.8Nm (18-22 ft. lb.)
VoltageBattery charger output13.4 ±2%VDC, max 2.5 A
VoltageVoltage regulation (no-load to full-load)1.0%RMS

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilFull Pressure system1.9 LWith filter. Integral oil cooler.
Engine oil10W-50 extended-life synthetic1.9 L (qt.)Premium oil option, 26 kW models, requires fewer oil changes
Engine oil5W-30 or 10W-30 API Service Class SG, SH, or SJ syntheticAPI SG/SH/SJ1.8 L (qt.)14 kW models
Engine oilSynthetic, API Service Class SG or higherAPI SG or higherCheck oil level at or near, not over, full mark on dipstick before operation

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

24
CodeNameMeaningSeverityAction
AC Sens LossAC Sens LossAC sensing lost in Auto mode; generator output AC sensing lost. Detection begins 10 seconds after crank disconnect. Warning after 1 sec if no output detected after crank disconnect; Shutdown after 3 sec if voltage was present and then lost.WarningContact an authorized dealer for service.
ATS ComErrorATS Communication ErrorATS communication error. Warning displayed if ATS interface connection is lost.WarningCheck communication wiring between transfer switch interface board and generator set.
ATS PhaseRotATS Phase RotationATS phase rotation mismatch. Transfer switch phase rotation does not match; ATS will not transfer.WarningCorrect the ATS connection. Refer to the ATS Installation manual, wiring diagrams, and labels on the transfer switch.
Accy PwrOver WarningAccessory Power Overload WarningAn over current fault (short circuit) on the accessory controller power output.WarningContact an authorized dealer for service.
Advanced DiagnosticAdvanced DiagnosticShutdown during the reduced speed portion of an exercise. Event history shows Advanced Diagnostic Active. Engine restarts, runs at full speed for 2 minutes, and stops. Controller returns to AUTO mode.ShutdownIf the generator set does not restart and return to AUTO, check for other faults that prevent generator set operation.
Aux InputAuxiliary InputAn optional customer-connected input is closed (digital input from optional PIM).ShutdownCheck customer-supplied equipment.
Batt Chg FltBattery Charger FaultInput to PIM from an external battery charger (not the built-in battery charger).WarningCheck external battery charger.
Battery CrLo WarningLow Cranking Battery Voltage WarningEngine starting battery voltage falls below 11 VDC for more than 10 seconds. Inhibited during crank cycle. Clears when battery voltage returns to acceptable level.WarningCheck the battery rating and condition. Check the battery charger operation. Charge or replace the battery.
Battery Voltage HighBattery Voltage HighEngine starting battery voltage rises above 16 VDC for more than 10 seconds. Inhibited during crank cycle. Clears when voltage returns to acceptable level.WarningCheck the battery rating and condition. Check the battery charger operation.
Battery Voltage LowBattery Voltage LowEngine starting battery voltage falls below 12.5 VDC for more than 90 seconds when engine not running. Not operative during crank cycle. Clears when voltage returns to acceptable level.WarningCheck the battery rating and condition. Check the battery charger operation. Charge or replace the battery.
Engine Speed HighEngine Speed HighEngine speed exceeds 115% of the normal running speed for more than 0.3 seconds.ShutdownContact an authorized dealer for service.
Engine Speed LowEngine Speed LowEngine speed drops below 85% of the normal running speed for more than 3 seconds.ShutdownReduce the load. Check enclosure thermostat and reset if tripped. Contact an authorized dealer for service.
Exer Not SchExercise Not ScheduledNo exercise is scheduled on the controller.WarningSee the Setting the Exerciser section for instructions to set the exerciser.
Frequency HighFrequency HighGoverned frequency exceeds 110% of the system's frequency setpoint for more than 10 seconds. Active 10 seconds after engine start.ShutdownContact an authorized dealer for service.
Frequency LowFrequency LowGoverned frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below setting for more than 60 seconds. Active 10 seconds after engine start.ShutdownReduce the load and restart the generator set. Check enclosure thermostat and reset if tripped. Contact an authorized dealer for service.
Lo Crank VltLow Cranking VoltageBattery voltage dropped below 3.5 VDC during engine cranking.WarningCharge or replace the battery.
Locked RotorLocked RotorNo engine rotation is sensed during cranking. Shuts down 3 seconds after fault is detected.ShutdownCheck the battery. Check for loose connections. Contact an authorized dealer for service.
Low Oil Level or Oil PressureLow Oil Level or Oil PressureOil level switch on the 26 kW indicates low oil level. LOP switch indicates low oil pressure for more than 5 seconds. Active 30 seconds after crank disconnect. Does not protect against low oil level.ShutdownCheck for leaks in the lubrication system. Check the oil level and add oil if low. Check the oil level or oil pressure switch and wiring. If fault persists, do not run the generator set; contact an authorized dealer.
MainPwrOverLMain Power OverloadMain power overload; an over current fault on the controller output (short circuit).ShutdownContact an authorized dealer for service.
Not in AutoNot in AutoThe generator set is not in Automatic (standby) mode. Remote start and stop commands from a transfer switch or remote switch will be ignored.WarningPress AUTO to place the generator set in Automatic mode, when appropriate.
Over CrankOver CrankThree unsuccessful starting attempts.ShutdownCheck the fuel supply, spark plug, and battery. Check for loose connections. Contact an authorized dealer for service.
Spd Sens FltSpeed Sensor FaultEngine speed sensor has failed or engine stalled.ShutdownContact an authorized dealer for service.
Volts L1-L2 HighGenerator Voltage HighOutput voltage exceeds 120% of the system nominal voltage for more than 2 seconds.ShutdownContact an authorized dealer for service.
Volts L1-L2 LowGenerator Voltage LowOutput voltage falls below 80% of the nominal system voltage for more than 10 seconds.ShutdownReduce the load and restart the generator set. Check enclosure thermostat and reset if tripped. Contact an authorized dealer for service.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Resetting the Controller After a Fault Shutdown diagnostic

⚠ Always identify and correct cause of fault before resetting

  1. Press Select to go to Overview menu while fault message is displayed
  2. Press Select again to show active fault message
  3. Press Select; 'Confirm Clear Fault: NO' displayed
  4. Press UP arrow; 'Confirm Clear Fault: YES' displayed
  5. Press Select to clear fault
  6. Press Select to return to overview menu; controller changes to OFF mode
  7. Press AUTO to place generator set in automatic mode
Access the Air Intake Area installation
  1. Unlock and raise the enclosure roof.
  2. Pull the air intake panel up and off its four bushings.
  3. Remove the cover panel over the terminal block to make electrical connections.
  4. After connections complete and battery installed, reinstall panels.
Battery Installation Procedure installation

⚠ Battery acid can cause severe injury or death

⚠ Explosion hazard from battery gases

  1. Ensure starting battery is fully charged before placing in service.
  2. Clean battery posts and/or adapters if necessary.
  3. Install battery post adapters, if needed.
  4. Place battery in the housing.
  5. Connect positive (+) lead to engine starting battery.
  6. Connect negative (-) lead to engine starting battery.
Fuel Conversion from NG to LPG, 14RCA/L (Original Fuel System) installation

⚠ Disconnect battery before working on generator set

⚠ Explosive fuel vapors can cause severe injury or death

Tools: straight-blade screwdriver, gas leak detector

  1. Press OFF button on generator set controller.
  2. Disconnect utility power to the generator.
  3. Disconnect engine starting battery, negative lead first.
  4. Turn off and disconnect the fuel supply.
  5. Remove hose clamp and fuel hose from hose fitting.
  6. Use straight-blade screwdriver to remove NG orifice from hose fitting.
  7. Insert LPG orifice into hose fitting and tighten until snug.
  8. Slide hose onto hose fitting and secure with clamp.
  9. Disconnect ignition timing leads 65 and N3 for LPG.
  10. Connect and turn on the new fuel supply.
  11. Reconnect battery leads, negative lead last.
  12. Reconnect utility power to the generator.
  13. Start generator by pressing RUN button.
  14. Check for leaks using a gas leak detector.
  15. Run generator and check operation; press OFF when done.
Fuel Selection, Revised Fuel System, 14/20/26RCA/L installation

⚠ Explosive fuel vapors can cause severe injury or death

Tools: gas leak detector

  1. Press OFF button on generator set controller.
  2. Disconnect utility power to the generator set.
  3. Disconnect engine starting battery, negative lead first.
  4. Turn off the fuel supply.
  5. For NG, turn selection knob clockwise to UP arrow; for LPG, turn counterclockwise about 1/4 turn.
  6. For NG, connect ignition timing lead 65 to N3; for LPG, disconnect lead 65 from N3.
  7. Connect and turn on fuel supply, ensuring it matches the fuel setting.
  8. Reconnect battery leads, negative lead last.
  9. Reconnect utility power to the generator.
  10. Change fuel type setting on RDC2 controller in Genset System menu.
  11. Start generator by pressing RUN button.
  12. Check for leaks using a gas leak detector.
  13. Run generator and check operation; press OFF when done.
Air Cleaner Service, 14 kW Models maintenance

⚠ Do not operate generator set with air cleaner removed

  1. Press OFF on controller
  2. Disconnect utility power
  3. Disconnect battery negative lead first
  4. Loosen cover retaining knob and remove cover
  5. Remove element cover nut, element cover, and paper element
  6. Replace element if dirty, bent, or damaged (do not wash or use pressurized air)
  7. Check air cleaner base and element cover, replace damaged components
  8. Reinstall element, cover, nut, and cover; secure with knob
  9. Reconnect utility power and battery negative last
Air Cleaner Service, 20/26 kW Models maintenance

⚠ Do not operate generator set with air cleaner removed

  1. Loosen two cover retaining knobs and remove cover
  2. Remove paper element
  3. Replace if dirty, bent, or damaged (do not wash or use pressurized air)
  4. Check air cleaner base, secure and undamaged
  5. Reinstall element flat and properly seated
  6. Install cover and secure with two knobs
Oil Change Procedure maintenance

⚠ Disconnect battery cables before working on generator set, negative lead first

⚠ Do not work on generator set until it cools

Tools: oil filter wrench

  1. Press OFF on controller
  2. Disconnect utility power
  3. Disconnect battery negative lead first
  4. Remove end panels to access oil drain valve/hose
  5. Clean area around dipstick and oil fill cap
  6. Remove drain hose cap and lower into container
  7. Open oil drain valve
  8. Remove dipstick and fill cap, drain completely
  9. Close drain valve, replace hose cap and clip, replace dipstick
  10. Loosen and remove old oil filter, allow to drain (20/26 kW)
  11. Clean gasket sealing surface, oil new filter seal, install new filter
  12. Fill with oil to F mark on dipstick
  13. Reconnect battery negative last, reconnect utility power
  14. Press RUN, run briefly, recheck oil level, check for leaks
  15. Reset the maintenance timer on the controller
Resetting the Maintenance Timer maintenance
  1. From Overview menu, step down to Genset Run Time menu
  2. Press Select, step down to Next Maintenance screen
  3. Press Select
  4. Press Up arrow so 'Reset Maint Timer? Yes' is displayed
  5. Press Select; new interval and date displayed after ~2 minutes
Spark Plug Service maintenance

⚠ Disconnect battery cables before working on generator set

Tools: wire feeler gauge, spark plug socket/torque wrench

  1. Clean area around spark plug base
  2. Remove spark plug and check condition, replace if worn
  3. Check gap with wire feeler gauge, adjust by bending ground electrode
  4. Reinstall spark plug, torque to 24.4-29.8 Nm (18-22 ft. lb.)
Storage Procedure maintenance

⚠ Perform battery storage last

  1. Operate generator set to operating temperature (~15 min), then stop
  2. Drain warm engine oil, refill crankcase, run briefly to distribute, stop
  3. Start generator set, shut off gas supply, run until engine stops, press OFF
  4. Remove spark plugs, pour one tablespoon of oil into each hole, install plugs, ground leads (do not connect), crank 2-3 revolutions
  5. Clean exterior, seal openings with nonabsorbent tape, mask electrical contacts, oil unpainted metal surfaces
  6. Press OFF, disconnect battery negative first, clean battery, store in warm dry location, connect to float/equalize or trickle charger monthly
Resetting the Thermostat repair

⚠ Do not work on the generator set until it cools

  1. Disconnect utility power by opening the building distribution panel breaker
  2. Open enclosure roof and secure with roof stay
  3. Remove air intake panel
  4. Press button on thermostat to reset
  5. Replace air intake panel
  6. Reconnect utility power
  7. Reset fault on controller

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12-volt engine electrical system, single starter motor, negative groundBattery negative to ground terminal on or near starter motor; battery positive to positive terminal on starter solenoidAll generator set models use a negative ground with a 12-volt engine electrical system
Engine start connection for non-RXT transfer switch or remote start/stop switchTerminals 3 and 4 on generator set terminal blockRoute engine start leads through separate conduit from AC power and load leads
RXT transfer switch to generator set terminal block A, B, PWR, COMP10-1 through P10-4 (transfer switch) to A, B, PWR, COM (generator set)Terminal block connections 3 and 4 not used with Model RXT ATS

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Kohler CH1006?

The Kohler CH1006 engine has an oil capacity of 1.9 liters.

What is the displacement of the Kohler CH1006?

The Kohler CH1006 has a displacement of 0.999 liters with 2 cylinders.

Which generators use the Kohler CH1006 engine?

The Kohler CH1006 powers 1 generator set(s), including Kohler 26RCA.

What is a common problem with the Kohler CH1006 engine?

A commonly reported issue on generators using the Kohler CH1006 is: This generator has absorbed more than 25% reactive power (magnetic excitation current) for 20 seconds.. Cause: Generator voltage on this generator is not calibrated correctly. Generator voltage on other generator is not calibrated correctly. Bus voltage on this generator is not calibrated correctly. Bus voltage on the other generator is not calibrated correctly..