The Kohler 12RESV is an engine rated at 3600 rpm. It powers generator sets from Kohler. It holds 1.9 L (0.5 gal) of oil.
Also known as: Kohler 12RESV engine
| Oil capacity | 1.9 L |
|---|---|
| Rated speed | 3600 rpm |
| Code | Meaning | Remedy |
|---|---|---|
| Accy PwrOver Warning | Accy PwrOver Warning — controller internal circuit protection activated | Press OFF to reset. Contact an authorized Kohler distributor/dealer for service |
| MainPwrOverL Shutdown | MainPwrOverL Shutdown — controller internal circuit protection activated | Press OFF to reset. Contact an authorized Kohler distributor/dealer for service |
| Symptom | Cause | Remedy |
|---|---|---|
| Controller display backlight is off | Backlight turns off after about 1 minute with no activity | Backlight will turn on when a button is pressed or the generator set starts |
| Controller display is off | Low or no battery voltage | Check connections; Check generator set battery |
| The generator set does not crank | Battery weak or dead | Recharge or replace the battery |
| The generator set does not crank | Battery connections reversed or poor | Check the connections |
| The generator set does not crank | Fault shutdown | Check the controller display for fault messages. See Section 2.5. Correct the fault condition and reset the controller |
| The generator set does not crank | Generator set in the OFF mode | Press the RUN button to start the engine or press AUTO to allow remote starting |
| The generator set does not crank | Gererator thermostat tripped | For trips other than temperature (nuisance trips), reset the thermostat. See Section 2.6 |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Air cleaner clogged | Clean and/or replace the air cleaner |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Battery weak or dead | Recharge or replace the battery |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Battery connection poor | Clean and tighten the battery connections |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Spark plug wire connection loose | Check the spark plug wires |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Low oil pressure shutdown | Check for oil leaks. Check the oil level and add oil if necessary |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Fuel pressure insufficient | Check the fuel supply and valves |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Engine malfunction | Contact an authorized Kohler distributor/dealer |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Gererator thermostat tripped | For trips other than temperature (nuisance trips), reset the thermostat. See Section 2.6 |
| No AC output | Line circuit breaker in the OFF position | Place the circuit breaker in the ON position |
| No AC output | Line circuit breaker tripping because of overload | Reduce the load on the generator set |
| No AC output | Line circuit breaker tripping because of short circuit | Contact an authorized Kohler distributor/dealer for service |
| No AC output | Auxiliary winding circuit breaker tripped | Reset the circuit breaker (located in junction box). Contact an authorized Kohler distributor/dealer for service if breaker trips repeatedly |
| Low output or excessive drop in voltage | Generator set overloaded | Reduce the load |
| Generator set stops suddenly | Low oil pressure shutdown | Check for oil leaks. Check the oil level and add oil if necessary |
| Generator set stops suddenly | Out of fuel | Check fuel supply |
| Generator set stops suddenly | Overcrank shutdown | Reset the controller. If the overcrank fault occurs again, contact an authorized Kohler distributor/dealer |
| Generator set stops suddenly | Auxiliary winding circuit breaker tripped | Reset the circuit breaker (located in junction box.) Contact an authorized Kohler distributor/dealer for service if breaker trips repeatedly |
| Generator set stops suddenly | Fault shutdown | Check the controller display for fault messages. See Section 2.5. Correct the fault condition and reset the controller |
| Generator set stops suddenly | Generator set in the OFF mode | Press the RUN button to start the engine or press AUTO to allow remote starting |
| Generator set stops suddenly | Remote stop command received from a remote switch, ATS, or OnCuer Plus | Check the remote switch position. Check OnCue Plus |
| Generator set stops suddenly | Engine malfunction | Contact an authorized Kohler distributor/dealer |
Fault codes and symptom→remedy steps extracted from this engine’s service/owner documentation; verify against the official manual before servicing.
Compiled from service & troubleshooting documentation across every generator set that uses the Kohler 12RESV.
Step-by-step procedures compiled from the Kohler service manual for this engine.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Oil level | Check | 8 hr | Before each use and every 8 hours | |
| engine oil level | Check | 8 hr | Check before each use; for extended operation check every 8 hours | |
| Oil | Change | 100 hr | 12 mo | Yearly or 100 hours |
| Oil filter | Replace | 100 hr | 12 mo | Yearly or 100 hours |
| Valve lash (8RESV/L) | Adjust | 100 hr | 100 hours | |
| valve lash (8RESV) | Check | 100 hr | 8RESV models only; requires authorized service | |
| Air cleaner | Replace | 150 hr | 12 mo | Yearly or 150 hours |
| air cleaner | Other | 150 hr | 12 mo | Service more frequently under dusty conditions |
| engine oil and filter | Change | 400 hr | 12 mo | Use 5W-30 synthetic oil |
| Crankcase breather hose | Clean | 500 hr | 12 mo | Yearly or 500 hours |
| Spark plugs | Replace | 500 hr | 12 mo | Yearly or 500 hours |
| Stepper motor coupling and bushing | Replace | 500 hr | 500 hours | |
| Valve lash (10/12RESV/L) | Adjust | 500 hr | 500 hours | |
| valve lash (10/12RESV) | Check | 500 hr | 10/12RESV models only; requires authorized service | |
| Battery cleaner operation | Check | 1 mo | Monthly | |
| Battery electrolyte level | Check | 12 mo | Yearly | |
| Fuel flexible lines | Inspect | 3 mo | Quarterly | |
| battery | Check | 1 mo | Monthly for first year; annually thereafter |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Spark plug gap | Spark plug gap | 0.508 | mm | All models |
| Speed | Frequency regulation steady state | 1.0% | % | |
| Temperature | Carburetor heater thermostat OFF | 16 ± 3 | C (60 ± 5F) | |
| Temperature | Carburetor heater thermostat ON | 4 ± 4 | C (40 ± 7F) | |
| Temperature | Thermostat OFF | 16 ± 3 | °C | Thermostat OFF (60 ± 5°F) |
| Temperature | Thermostat ON | 4 ± 4 | °C | Thermostat ON (40 ± 7°F) |
| Torque | Spark plug installation torque | 24.4 - 29.8 | Nm | Installation |
| Voltage | Voltage regulation (no-load to full-load) | ±1.0% | RMS |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Engine oil | Full Pressure system | 1.9 L | With filter | ||
| Engine oil | 5W-30 | API Service Class SG, SH, or SJ synthetic | Synthetic oil oxidizes and thickens less; recommended for cleaner intake valves and pistons | ||
| Engine oil | 5W-30 API SG/SH/SJ synthetic | API SG/SH/SJ | Synthetic oil recommended | ||
| Fuel | Gasoline | Unleaded gasoline | LP or natural gas capable |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Tools: digital voltmeter, personal computer, SiteTech software
Tools: digital voltmeter
Tools: clamp-on DC current probe or DC current meter
Tools: Command prompt, Telnet Client
⚠ Accidental starting can cause severe injury or death; disconnect battery cables before working on the generator set, negative lead first.
⚠ Hazardous voltage will cause severe injury or death; disconnect all power sources before opening the enclosure.
⚠ Hot surfaces: disconnect power to the heater and allow it to cool before servicing.
⚠ Accidental starting can cause severe injury or death; disconnect battery cables before working on the generator set, negative lead first.
⚠ Hazardous voltage will cause severe injury or death; disconnect all power sources before opening the enclosure.
⚠ Hot surfaces: install the heater before connecting it to power; disconnect power and allow it to cool before servicing.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 100/200 | 1 | Single | ||
| 100/200 | 3 | Delta | ||
| 110/220 | 1 | Single | ||
| 110/220 | 3 | Delta | ||
| 115/230 | 1 | Single | ||
| 120 | 1 | Single | Genset System Voltage/Frequency/Phase table for controller setup | |
| 120/208 | 3 | Wye | ||
| 120/240 | 1 | Single | ||
| 120/240 | 3 | Delta | ||
| 127/220 | 3 | Wye | ||
| 220 | 1 | Single | ||
| 220/380 | 3 | Wye | ||
| 230 | 1 | Single | ||
| 230/400 | 3 | Wye | ||
| 240 | 1 | Single | ||
| 240/416 | 3 | Wye | ||
| 277/480 | 3 | Wye |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The Kohler 12RESV engine has an oil capacity of 1.9 liters.
The Kohler 12RESV powers 1 generator set(s), including Kohler 12RESV.
A commonly reported issue on generators using the Kohler 12RESV is: The generator set cranks but does not start, starts hard, lacks power, or operates erratically. Cause: Air cleaner clogged. Fix: Clean and/or replace the air cleaner.