John Deere PE6090HFG95 Engine

The John Deere PE6090HFG95 is a 9 L 6-cylinder turbocharged engine rated at 1800 rpm, producing up to 328 kW. It powers generator sets from Magnum, including the MMG330.

Also known as: John Deere PE6090HFG95

9.0 L
Displacement
6
Cylinders
1800 rpm
Rated speed
328 kW
Gross power

Engine specifications

Displacement9.0 L
Cylinders6
Aspirationturbocharged
Rated speed1800 rpm
Gross power328 kW

Common problems

6
  • Overspeed or underspeed shut down
    Fix: 1. Disconnect all loads and restart the generator. Read the frequency (Hz) on the LCD display. With no loads on the generator, the frequency should read 60.0 Hz. 2. If the frequency is above or below 60.0 Hz, the engine speed will have to be adjusted. See the engine manual for throttle adjustments on mechanical governed units and see the electronic governor manual for electronically controlled units.
  • Overcrank shut down
    Fix: 1. Check the fuel level in the tank. 2. Check for proper operation of the fuel pump. 3. Check air filter for blockage. 4. If the engine will not start, consult the engine operation and maintenance manual for additional information on troubleshooting starting problems.
  • LOW OIL PRESSURE SHUTDOWN
    Cause: Oil pressure is less than 20 psi (138kPa).
    Fix: Check the engine oil level with a dipstick. Add oil if required. Visually inspect for oil leaks. If oil level is good, restart and verify loss of oil pressure. Check the oil pressure sender.
  • LOW FUEL LEVEL SHUT DOWN
    Cause: Fuel level is low or fuel tank has leaks.
    Fix: Check the fuel level on the LCD window. Ensure no leaks in the fuel tank. Check the fuel level sender and connecting wiring for damage.
  • LOW COOLANT LEVEL SHUT DOWN
    Fix: Allow engine to cool. Check coolant level in the radiator. Access the radiator cap by removing the access panel.
  • High Coolant Temperature shut down
    Fix: 1. Check the coolant level in the overflow jug. 2. Restart the engine and read the coolant temperature to verify High Coolant Temperature shut down. Stop the engine immediately if the coolant temperature is 230°F (110°C) or more. 3. Allow the engine to cool. Add coolant to the overflow jug if it is low and then check the level of coolant in the radiator. To access the radiator cap, you must remove the access panel from the top of the enclosure directly above the radiator. Add coolant until it is 3/4 in (2 cm) below the filler neck. Secure the radiator cap back into its original position. 4. Check the radiator shroud and ducting for blockage and remove any foreign matter. 5. Inspect coolant hoses, engine block and water pump for visible leaks. 6. Check the tension of the serpentine drive belt for the water pump. 7. If no other problems are found, remove the load on the generator and restart the engine. Check the coolant temperature and shut the engine down immediately if it starts to overheat.

Compiled from service & troubleshooting documentation across every generator set that uses the John Deere PE6090HFG95.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

7
ItemActionHoursMonthsNotes
Engine maintenance/service reminder (MDC "WrnMaintenance")Other250 hrMagnum Digital Controller default service reminder interval; reset to 250 hours after servicing
Engine oil and oil filterChange500 hrFirst service — Subsequent changes every 500 hours when using John Deere Plus-50 II oil or equivalent; every 250 hours otherwise
Fan/serpentine beltInspect500 hr12 moRemove and check for wear; inspect pulleys and bearings while removed
Primary air cleaner elementReplace500 hrOr when dust valve restriction indicator gauge shows a vacuum of 25 in. H2O, whichever comes first
Exhaust filter (DPF) ash removalOther3000 hrExpected service interval at least 3000 or 4500 hours based on engine power and operating conditions; actual service when indicator light appears
Trailer wheel bearing lubricationLubricate12 moMinimum recommended lubrication is every 12 months or 12,000 miles (19,312 km)
Trailer wheel lug nutsAdjustFirst service — Re-torque lug nuts in sequence after the first road use

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

11
TypeItemValueUnitCondition
OtherAir Filter Restriction Indicator (filter minder gauge)20in. H2Oreplace air filter when yellow center bar reaches red section
OtherLow Fuel Level Shutdown5% of tank remaining
PressureLow Oil Pressure Shutdown20psi (138 kPa)engine controller shuts down engine below this pressure
PressureOil Pressure Restart Check5psi (34 kPa)shut engine down immediately if pressure does not reach this value within 5 seconds of restart
SpeedNo-Load Frequency60.0Hzno loads on the generator
TemperatureHigh Coolant Temperature Shutdown230°F (110°C) or more
TorqueGenerator drive plate bolts33ft-lb (45 Nm)
TorqueTrailer wheel lug nuts, first pass20-25ft-lbs (27-33 Nm)first pass
TorqueTrailer wheel lug nuts, second pass50-60ft-lbs (67-81 Nm)second pass
TorqueTrailer wheel lug nuts, third pass90-120ft-lbs (122-162 Nm)third pass
VoltageVoltage Regulation+/- 1%

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Fuelultra low sulfur diesel459.0 gal (1738 L)Usable fuel volume 423 gal (1601 L)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

7
CodeNameMeaningSeverityAction
Coolant temperature shutdownCoolant temperature shutdown - 230°FShutdown
Coolant temperature warningCoolant temperature warning - 220°FWarning
Fuel level shutdownFuel level shutdown - 5%Shutdown
Fuel level warningFuel level warning - 15%Warning
Oil pressure shutdownOil pressure shutdown - 20 psiShutdown
Oil pressure warningOil pressure warning - 25 psiWarning
OverspeedOverspeed protection - 115%Shutdown

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

3
Checking Generator Drive Plate Torque maintenance
  1. Disconnect the engine starting battery
  2. Remove the generator fan guard
  3. Torque each of the drive plate bolts to the specification (MMG330: 33 ft-lb / 45 Nm)
  4. Reinstall the generator fan guard and reconnect the battery
Resetting of the Time to Service Reminder maintenance
  1. With the unit shut down, power up the controller with the Control On/Off toggle switch
  2. Press Page Select until Engine Protect line is reached and press Enter
  3. "WrnMaintanance" appears with the current service time hour setting below it
  4. Press Enter; current run time in hours appears on the display
  5. Reset the current run time hour setting to 250
  6. Press Enter to save the run time hour setting
  7. Move the Control On/I toggle switch to Control Off/O
Towing the Trailer / Wheel Lug Torque Sequence maintenance
  1. Start all lug nuts by hand
  2. First pass: tighten to 20-25 ft-lbs (27-33 Nm)
  3. Second pass: tighten to 50-60 ft-lbs (67-81 Nm)
  4. Third pass: tighten to 90-120 ft-lbs (122-162 Nm)
  5. After the first road use, re-torque the lug nuts in sequence

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the displacement of the John Deere PE6090HFG95?

The John Deere PE6090HFG95 has a displacement of 9.0 liters with 6 cylinders.

Which generators use the John Deere PE6090HFG95 engine?

The John Deere PE6090HFG95 powers 1 generator set(s), including Magnum MMG330.

What is a common problem with the John Deere PE6090HFG95 engine?

A commonly reported issue on generators using the John Deere PE6090HFG95 is: Overspeed or underspeed shut down. Fix: 1. Disconnect all loads and restart the generator. Read the frequency (Hz) on the LCD display. With no loads on the generator, the frequency should read 60.0 Hz. 2. If the frequency is above or below 60.0 Hz, the engine speed will have to be adjusted. See the engine manual for throttle adjustments on mechanical governed units and see the electronic governor manual for electronically controlled units..